Piping

6.9Connecting a Liebert XDV with Liebert Flex Pipe to an Operational Liebert XD System

NOTICE

Before connecting the Liebert XDV with Liebert Flex Pipe to the prefabricated piping mains, check the whole system for leaks.

Check the Liebert XDV to ensure that the unit has no refrigerant leaks. Read all instructions before beginning installation.

Tools Required

Two adjustable wrenches, with a maximum adjustment size of 2-1/2 inches

Two ladders

Lifting mechanism if the Liebert XDV is going to be suspended above the cabinet

NOTE

This operation requires two or more people.

1.Determine the port location of the supply and return piping overhead

2.Make sure the service valve for each port is closed

3.Remove cap for only the required ports. Do not remove caps from the unused ports.

4.Once Step 3 has been completed, remove the pipe plugs that are supplied on the Liebert Flex Pipe on the Liebert XDV.

Figure 28 Liebert XD prefabricated piping assembly

 

Return Main

Supply Main

Service Valve, typical

 

(all ports)

Threaded Cap (Typical)

5.Use system refrigerant to lubricate the face of the male coupling half, including the poppet valve face and the stainless steel delta ring.

6.Thread the return couplers together, the larger of the two couplers (Liebert Flex Pipe and return main).

7.Use one of the adjustable wrenches to hold the fixed side of the female coupler on the Liebert XDV stationary. With the other adjustable wrench, tighten the collar onto the coupler.

Tighten these only until the force required to tighten abruptly increases. See Figure 29.

NOTICE

Do not overtighten the couplers. Overtightening of couplers will damage the couplers.

26

Image 32
Contents Liebert XDV General Safety Guidelines Fluorinated Greenhouse Gas Requirements-European UnionTable of Contents Installation Checklist and System Fill for Startup MaintenanceSpecifications ElectricalFigures Page Example XDV10BK Liebert XDV component locationsPre-Installation Checks Installation ConsiderationsInstallation ReferencesGeneral Product Information Product/System DescriptionChecking and Unpacking Equipment Inspection Recyclable PackagingUnit Handling Unpacking the Unit Domestic PackagingExport Packaging Removing export shipping packageRemoving the Liebert XDV from the Pallet Removing Liebert XDV from shipping palletMechanical Considerations Determining Placement in the Conditioned SpaceDimensional data Changing the Air Intake Location Changing the Liebert XDV’s air intake locationBolting Liebert XDV to Top of Cabinet Mounting the Liebert XDV on Top of the CabinetMounting the Liebert XDV Bottom View Using Supplied Clips for Mounting Mounting clip placementSuspension hardware and bracket dimensional data Suspended Mounting Method11mm 22mm Top View 2 64mm 76mm 102mm DPN000770 Pg , RevSuspending the Liebert XDV from Unistruts Suspending the Liebert XDV from Overhead StructuresSuspending Liebert XDV from the overhead structure Mounting Liebert XDVs in Stacked Setup Stacking configuration offsetHanging Stacked Liebert XDVs from Unistruts Stacked Liebert XDVs suspended from UnistrutsHanging Stacked Liebert XDVs from the Overhead Structure Piping System Connection ConfigurationEuropean Union Fluorinated Greenhouse Gas Requirements Connection Methods and Points Piping Connections to Liebert XDP or Liebert XDCRight Side Liebert XDV Hard Piped Connection Sizes Holding Charge-Hard-Piped UnitsRecommended Piping Size Brazing Preparations-Hard-Piped UnitsConnection Methods-One-Shot Connections Branch piping sizes for refrigerant loopRefrigerant Charge-Pre-Charged Option Field Installation of Liebert Flex Pipe Kit on Liebert XDVConnecting Liebert XD Flex Pipe to Liebert XDV Modules Liebert XD prefabricated piping assembly Tools RequiredWith wrench OvertightenReturn Insulation Piping mains without Liebert XDV and Liebert Flex PipeConnecting High Voltage Cables for CSA/C-US Certified Units ElectricalRear Liebert XDV Rear of Liebert XDVLiebert XDV electrical connections for CE-approved units Rear View of Liebert Xdvto be N.E.C. Class Connecting Low Voltage Wiring-OptionalCondensate Detection Connections Checklist for Proper Installation Installation Checklist and System Fill for StartupStart the Liebert XDV OperationFluorinated Greenhouse Gas Requirements Internal AccessMaintenance Accessing Internal Electrical Components Accessing internal electrical componentsTo remove the fan tray Specifications Liebert XDV10 specificationsLiebert XDV8 specifications Liebert XD Liebert Flex Pipe assemblies, supply and return Page Ne t ItiTi n That