Liebert XDV manual Return

Page 34

Piping

6.10Disconnecting a Liebert XDV With Liebert Flex Pipe From a Liebert XD System

! CAUTION

Risk of sudden discharge of pressurized refrigerant. Can cause equipment damage or injury.

Do not disconnect threaded refrigerant couplers at the unit cabinet end without relieving system pressure. Reclaim any refrigerant during removal of unit from system.

NOTICE

Before uninstalling a Liebert XDV with Liebert Flex Pipe from the prefabricated piping mains: With the fans running, close the supply service valve, wait approximately

two minutes, then close the return service valve.

Removing a Liebert XDV from above a cabinet will require two people. Read all instructions before beginning.

Tools Required

Two adjustable wrenches, maximum adjustment size of 2-1/2 inches

Two ladders

Phillips head #2 screwdriver

Lift mechanism, if the Liebert XDV is suspended above cabinet

1.Ensure the Liebert XDV fan switches are both On and the fans are operational.

2.Close the service valve in the supply line to the Liebert XDV (smaller coupler).

3.With the Liebert XDV fans running, wait two minutes.

4.Close the service valve in the return line to the Liebert XDV (larger coupler).

5.Turn the fan power switches to the Off position. Once the fan switches are turned Off, unplug the power cords from their power source.

6.Locate and have at the ready the caps and plugs for both ends of the supply and return couplers.

7.Loosen the female supply coupler from the male supply coupler (smaller coupler). This requires two adjustable wrenches. Refer to Figure 29.

8.The Liebert XDV side of the female coupler must be held stationary while the collar on the coupler is being loosened. Refer to Figure 29.

9.Disconnect the coupler.

Figure 31 Profile view of the Liebert XD system with one-shot connections

One-Shot Connections

One-Shot Support Bracket

Serial Tag

Liquid Sensing (optional) Disconnect wiring prior to moving XDV

Primary and

Return

Secondary

Line

IEC Power

 

Cord

 

Fan Power

Switches

Rear of the XDV

Service

Valve

Supply

Line

10.Place the protective dust cap and plug back onto both ends of the coupler on the Liebert XDV and the port pipe.

28

Image 34
Contents Liebert XDV General Safety Guidelines Fluorinated Greenhouse Gas Requirements-European UnionTable of Contents Specifications Installation Checklist and System Fill for StartupMaintenance ElectricalFigures Page Example XDV10BK Liebert XDV component locationsInstallation Pre-Installation ChecksInstallation Considerations ReferencesChecking and Unpacking Product/System DescriptionGeneral Product Information Equipment Inspection Recyclable PackagingUnit Handling Unpacking the Unit Domestic PackagingExport Packaging Removing export shipping packageRemoving the Liebert XDV from the Pallet Removing Liebert XDV from shipping palletDimensional data Determining Placement in the Conditioned SpaceMechanical Considerations Changing the Air Intake Location Changing the Liebert XDV’s air intake locationMounting the Liebert XDV Mounting the Liebert XDV on Top of the CabinetBolting Liebert XDV to Top of Cabinet Bottom View Using Supplied Clips for Mounting Mounting clip placement11mm 22mm Top View 2 64mm 76mm 102mm DPN000770 Suspension hardware and bracket dimensional dataSuspended Mounting Method Pg , RevSuspending the Liebert XDV from Unistruts Suspending the Liebert XDV from Overhead StructuresSuspending Liebert XDV from the overhead structure Mounting Liebert XDVs in Stacked Setup Stacking configuration offsetHanging Stacked Liebert XDVs from Unistruts Stacked Liebert XDVs suspended from UnistrutsHanging Stacked Liebert XDVs from the Overhead Structure European Union Fluorinated Greenhouse Gas Requirements System Connection ConfigurationPiping Connection Methods and Points Piping Connections to Liebert XDP or Liebert XDCRight Side Liebert XDV Hard Piped Connection Sizes Holding Charge-Hard-Piped UnitsRecommended Piping Size Brazing Preparations-Hard-Piped UnitsConnection Methods-One-Shot Connections Branch piping sizes for refrigerant loopConnecting Liebert XD Flex Pipe to Liebert XDV Modules Field Installation of Liebert Flex Pipe Kit on Liebert XDVRefrigerant Charge-Pre-Charged Option Liebert XD prefabricated piping assembly Tools RequiredWith wrench OvertightenReturn Insulation Piping mains without Liebert XDV and Liebert Flex PipeRear Liebert XDV Connecting High Voltage Cables for CSA/C-US Certified UnitsElectrical Rear of Liebert XDVLiebert XDV electrical connections for CE-approved units Condensate Detection Connections Connecting Low Voltage Wiring-OptionalRear View of Liebert Xdvto be N.E.C. Class Checklist for Proper Installation Installation Checklist and System Fill for StartupStart the Liebert XDV OperationMaintenance Internal AccessFluorinated Greenhouse Gas Requirements Accessing Internal Electrical Components Accessing internal electrical componentsTo remove the fan tray Specifications Liebert XDV10 specificationsLiebert XDV8 specifications Liebert XD Liebert Flex Pipe assemblies, supply and return Page Ti n Ne tIti That