Liebert XDV manual Recommended Piping Size, Brazing Preparations-Hard-Piped Units

Page 29

Piping

Figure 25 Schrader valve location for venting holding charge

Front of Liebert XDV

Top of Liebert XDV

Schrader

Valve

SCHRADER VALVE

SUPPLY( IN)

RETURN (OUT)

Supply pipe

 

Return pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connection

 

Rear of XDV

 

(1/2" OD)

 

connection

 

 

 

 

 

 

 

 

 

(5/8" OD)

 

 

 

 

 

 

 

6.4.2Brazing Preparations—Hard-Piped Units

After the holding charge for a hard-piped Liebert XDV has been vented, a torch can be used to remove the caps over the ends of the supply and return lines.

During brazing, the lines must be filled with flowing dry nitrogen to prevent excessive oxidation and scale formation inside the piping. Prevailing good refrigeration practices must be employed for piping supports, leak testing, dehydration and charging. Failure to use good system practices may result in damage to the system. Refer to the ASHRAE refrigeration handbook for general good-practice refrig- eration piping.

6.5Recommended Piping Size

NOTICE

To minimize the amount of refrigerant required, do NOT oversize the piping.

Connect the main pipes between the Liebert XDV branch piping and the Liebert XDP or Liebert XDC according to Table 4. Elbows and restrictions must be minimized to ensure good fluid flow.

Please see Table 4 below for recommended pipe sizes and Figure 3 for piping segment locations.

23

Image 29
Contents Liebert XDV Fluorinated Greenhouse Gas Requirements-European Union General Safety GuidelinesTable of Contents Maintenance Installation Checklist and System Fill for StartupSpecifications ElectricalFigures Page Liebert XDV component locations Example XDV10BKInstallation Considerations Pre-Installation ChecksInstallation ReferencesGeneral Product Information Product/System DescriptionChecking and Unpacking Recyclable Packaging Equipment InspectionUnpacking the Unit Domestic Packaging Unit HandlingRemoving export shipping package Export PackagingRemoving Liebert XDV from shipping pallet Removing the Liebert XDV from the PalletMechanical Considerations Determining Placement in the Conditioned SpaceDimensional data Changing the Liebert XDV’s air intake location Changing the Air Intake LocationBolting Liebert XDV to Top of Cabinet Mounting the Liebert XDV on Top of the CabinetMounting the Liebert XDV Bottom View Mounting clip placement Using Supplied Clips for MountingSuspended Mounting Method Suspension hardware and bracket dimensional data11mm 22mm Top View 2 64mm 76mm 102mm DPN000770 Pg , RevSuspending the Liebert XDV from Overhead Structures Suspending the Liebert XDV from UnistrutsSuspending Liebert XDV from the overhead structure Stacking configuration offset Mounting Liebert XDVs in Stacked SetupStacked Liebert XDVs suspended from Unistruts Hanging Stacked Liebert XDVs from UnistrutsHanging Stacked Liebert XDVs from the Overhead Structure Piping System Connection ConfigurationEuropean Union Fluorinated Greenhouse Gas Requirements Piping Connections to Liebert XDP or Liebert XDC Connection Methods and PointsRight Side Liebert XDV Holding Charge-Hard-Piped Units Hard Piped Connection SizesBrazing Preparations-Hard-Piped Units Recommended Piping SizeBranch piping sizes for refrigerant loop Connection Methods-One-Shot ConnectionsRefrigerant Charge-Pre-Charged Option Field Installation of Liebert Flex Pipe Kit on Liebert XDVConnecting Liebert XD Flex Pipe to Liebert XDV Modules Tools Required Liebert XD prefabricated piping assemblyOvertighten With wrenchReturn Piping mains without Liebert XDV and Liebert Flex Pipe InsulationElectrical Connecting High Voltage Cables for CSA/C-US Certified UnitsRear Liebert XDV Rear of Liebert XDVLiebert XDV electrical connections for CE-approved units Rear View of Liebert Xdvto be N.E.C. Class Connecting Low Voltage Wiring-OptionalCondensate Detection Connections Installation Checklist and System Fill for Startup Checklist for Proper InstallationOperation Start the Liebert XDVFluorinated Greenhouse Gas Requirements Internal AccessMaintenance Accessing internal electrical components Accessing Internal Electrical ComponentsTo remove the fan tray Liebert XDV10 specifications SpecificationsLiebert XDV8 specifications Liebert XD Liebert Flex Pipe assemblies, supply and return Page Iti Ne tTi n That