Piping
Table 4 | Branch piping sizes for refrigerant loop | ||
|
|
| |
| Pipe Function | Size / Equivalent Pipe Length | |
|
| ||
Liebert XDP/Liebert XDC supply line, from | |||
Liebert XDP/Liebert XDC supply |
| ||
to farthest Liebert XDV | |||
| |||
Liebert XDP/Liebert XDC return line, from | |||
farthest Liebert XDV |
| ||
to Liebert XDP/Liebert XDC return | |||
| |||
From Liebert XDV supply to supply line of | 1/2" OD (0.430" ID) for lengths up to 6 feet (1.8m) | ||
Liebert XDP/Liebert XDC | 5/8" OD (0.545" ID) for lengths over 6 feet but less than 35 feet | ||
From Liebert XDV return to return line of | 5/8" OD (0.545" ID) for lengths up to 6 feet (1.8m) | ||
Liebert XDP/Liebert XDC | 7/8" OD (0.785" ID) for lengths over 6 feet but less than 35 feet |
6.6Connection Methods—One-Shot Connections
The assembly and connection means used for piping in the Liebert XD system are the same as those used in conventional refrigeration systems. Observe all standard practices during installation and startup to prevent damage and contamination.
Both supply and return fittings may be supplied with optional,
! CAUTION
Risk of sudden refrigerant discharge. Can cause injury and loss of charge.
If the optional
Supply and return fittings on the
If the unit includes the optional,
If the unit does not include flex piping, refer to 6.4.1 - Holding
Figure 26 Piping location and connection sizes—pre-charged units with one-shot connections
Top View
Supply Connection 1/2"
Return
Connection
5/8"
Detail
Area “A”
Detail “A”
24