Liebert XDV Connection Methods-One-Shot Connections, Branch piping sizes for refrigerant loop

Page 30

Piping

Table 4

Branch piping sizes for refrigerant loop

 

 

 

 

Pipe Function

Size / Equivalent Pipe Length

 

 

Liebert XDP/Liebert XDC supply line, from

1-1/8" OD (1.025" ID) for lengths up to 60 feet (18m)

Liebert XDP/Liebert XDC supply

 

1-3/8" OD (1.265" ID) for lengths over 60 but less than 175 feet (18 to 53m)

to farthest Liebert XDV

 

Liebert XDP/Liebert XDC return line, from

2-1/8" OD (1.985" ID) for lengths up to 60 feet (18m)

farthest Liebert XDV

 

2-5/8" OD (2.465" ID) for lengths over 60 but less than 175 feet (18 to 53m)

to Liebert XDP/Liebert XDC return

 

From Liebert XDV supply to supply line of

1/2" OD (0.430" ID) for lengths up to 6 feet (1.8m)

Liebert XDP/Liebert XDC

5/8" OD (0.545" ID) for lengths over 6 feet but less than 35 feet (1.8-10.6m)

From Liebert XDV return to return line of

5/8" OD (0.545" ID) for lengths up to 6 feet (1.8m)

Liebert XDP/Liebert XDC

7/8" OD (0.785" ID) for lengths over 6 feet but less than 35 feet (1.8-10.6m)

6.6Connection Methods—One-Shot Connections

The assembly and connection means used for piping in the Liebert XD system are the same as those used in conventional refrigeration systems. Observe all standard practices during installation and startup to prevent damage and contamination.

Both supply and return fittings may be supplied with optional, one-shot connections. These fittings contain pressurized R-134a refrigerant inside the Liebert XDV.

! CAUTION

Risk of sudden refrigerant discharge. Can cause injury and loss of charge.

If the optional pre-charged option is chosen, the Liebert XDV unit is shipped with a full charge of R-134a refrigerant under pressure. Do not remove the pipe caps or plugs before the unit is ready for connection to Liebert XD Piping.

Supply and return fittings on the pre-charged Liebert XDV units are one-shot connections. Do not disconnect one-shot connections after they have been connected. Disconnection will release pressurized R-134a refrigerant from the Liebert XDV.

If the unit includes the optional, factory-installed, one-shot style connections, proceed with 6.7 - Field Installation of Liebert Flex Pipe Kit on Liebert XDV and see Figure 26.

If the unit does not include flex piping, refer to 6.4.1 - Holding Charge—Hard-Piped Units.

Figure 26 Piping location and connection sizes—pre-charged units with one-shot connections

Top View

Supply Connection 1/2"

Return￿

Connection￿

5/8"

Detail

Area “A”

Detail “A”

24

Image 30
Contents Liebert XDV General Safety Guidelines Fluorinated Greenhouse Gas Requirements-European UnionTable of Contents Specifications Installation Checklist and System Fill for StartupMaintenance ElectricalFigures Page Example XDV10BK Liebert XDV component locationsInstallation Pre-Installation ChecksInstallation Considerations ReferencesProduct/System Description Checking and UnpackingGeneral Product Information Equipment Inspection Recyclable PackagingUnit Handling Unpacking the Unit Domestic PackagingExport Packaging Removing export shipping packageRemoving the Liebert XDV from the Pallet Removing Liebert XDV from shipping palletDetermining Placement in the Conditioned Space Dimensional dataMechanical Considerations Changing the Air Intake Location Changing the Liebert XDV’s air intake locationMounting the Liebert XDV on Top of the Cabinet Mounting the Liebert XDVBolting Liebert XDV to Top of Cabinet Bottom View Using Supplied Clips for Mounting Mounting clip placement11mm 22mm Top View 2 64mm 76mm 102mm DPN000770 Suspension hardware and bracket dimensional dataSuspended Mounting Method Pg , RevSuspending the Liebert XDV from Unistruts Suspending the Liebert XDV from Overhead StructuresSuspending Liebert XDV from the overhead structure Mounting Liebert XDVs in Stacked Setup Stacking configuration offsetHanging Stacked Liebert XDVs from Unistruts Stacked Liebert XDVs suspended from UnistrutsHanging Stacked Liebert XDVs from the Overhead Structure System Connection Configuration European Union Fluorinated Greenhouse Gas RequirementsPiping Connection Methods and Points Piping Connections to Liebert XDP or Liebert XDCRight Side Liebert XDV Hard Piped Connection Sizes Holding Charge-Hard-Piped UnitsRecommended Piping Size Brazing Preparations-Hard-Piped UnitsConnection Methods-One-Shot Connections Branch piping sizes for refrigerant loopField Installation of Liebert Flex Pipe Kit on Liebert XDV Connecting Liebert XD Flex Pipe to Liebert XDV ModulesRefrigerant Charge-Pre-Charged Option Liebert XD prefabricated piping assembly Tools RequiredWith wrench OvertightenReturn Insulation Piping mains without Liebert XDV and Liebert Flex PipeRear Liebert XDV Connecting High Voltage Cables for CSA/C-US Certified UnitsElectrical Rear of Liebert XDVLiebert XDV electrical connections for CE-approved units Connecting Low Voltage Wiring-Optional Condensate Detection ConnectionsRear View of Liebert Xdvto be N.E.C. Class Checklist for Proper Installation Installation Checklist and System Fill for StartupStart the Liebert XDV OperationInternal Access MaintenanceFluorinated Greenhouse Gas Requirements Accessing Internal Electrical Components Accessing internal electrical componentsTo remove the fan tray Specifications Liebert XDV10 specificationsLiebert XDV8 specifications Liebert XD Liebert Flex Pipe assemblies, supply and return Page Ti n Ne tIti That