Liebert XDV manual Connecting High Voltage Cables for CSA/C-US Certified Units, Electrical

Page 36

Electrical

7.0ELECTRICAL

The unit must be installed in accordance with national wiring regulations. Refer to the unit’s serial tag for electrical requirements. Refer to Table 5 for details.

Replacement of any wiring or supply cord must be performed only by the manufacturer, the manufac- turer’s service agent or a similarly qualified person.

7.1Connecting High Voltage Cables for CSA/C-US Certified Units

! WARNING

Risk of electric shock. Can cause injury or death.

Disconnect all local and remote electric power before working within the unit.

Connect IEC power cords to each receptacle on the Liebert XDV and to power sources. If only one power source is available, then only the power connection labeled “SECONDARY” should be con- nected to the power source. See Figures 33 and 34 for location of power connections.

Figure 33 Liebert XDV electrical connections for CSA-approved units

60Hz MODELS ONLY.

FIELD WIRING

CONNECTIONS

AT TERMINAL STRIP TO BE N.E.C. CLASS 2 USE SWITCH CONTACTS WITH 75 V.A.

MINIMUM

50Hz MODELS ONLY.

FIELD WIRING

CONNECTIONS

AT TERMINAL STRIP FOR SAFETY EXTRA LOW VOLTAGE CIRCUITS ONLY. USE SWITCH CONTACTS RATED

75 V.A. MINIMUM,

24 VOLTS AC

MAXIMUM.

1774241 P1 REV1

82 83

A

M

P

PRIMARY

POWER

SOURCE

SECONDARY

1774241P1

Rear of

Liebert XDV

Right Side of Liebert XDV

Condensate Detection

Dry Contacts – Low

Voltage Connections

Primary

Circuit

Breaker

IEC Primary and

Secondary

Power Inlet

60Hz MODELS ONLY

Field wiring connections at terminal strip to be NEC Class 2. Use switch contacts with 75VA minimum rating.

50Hz MODELS ONLY

Field wiring connections at terminal strip for safety extra low voltage circuits only. Use

switch contacts rated 75VA minimum, 24VAC maximum.

A

M

P

Secondary Circuit Breaker

Rear of Liebert XDV

30

Image 36
Contents Liebert XDV General Safety Guidelines Fluorinated Greenhouse Gas Requirements-European UnionTable of Contents Installation Checklist and System Fill for Startup MaintenanceSpecifications ElectricalFigures Page Example XDV10BK Liebert XDV component locationsPre-Installation Checks Installation ConsiderationsInstallation ReferencesProduct/System Description Checking and UnpackingGeneral Product Information Equipment Inspection Recyclable PackagingUnit Handling Unpacking the Unit Domestic PackagingExport Packaging Removing export shipping packageRemoving the Liebert XDV from the Pallet Removing Liebert XDV from shipping palletDetermining Placement in the Conditioned Space Dimensional dataMechanical Considerations Changing the Air Intake Location Changing the Liebert XDV’s air intake locationMounting the Liebert XDV on Top of the Cabinet Mounting the Liebert XDVBolting Liebert XDV to Top of Cabinet Bottom View Using Supplied Clips for Mounting Mounting clip placementSuspension hardware and bracket dimensional data Suspended Mounting Method11mm 22mm Top View 2 64mm 76mm 102mm DPN000770 Pg , RevSuspending the Liebert XDV from Unistruts Suspending the Liebert XDV from Overhead StructuresSuspending Liebert XDV from the overhead structure Mounting Liebert XDVs in Stacked Setup Stacking configuration offsetHanging Stacked Liebert XDVs from Unistruts Stacked Liebert XDVs suspended from UnistrutsHanging Stacked Liebert XDVs from the Overhead Structure System Connection Configuration European Union Fluorinated Greenhouse Gas RequirementsPiping Connection Methods and Points Piping Connections to Liebert XDP or Liebert XDCRight Side Liebert XDV Hard Piped Connection Sizes Holding Charge-Hard-Piped UnitsRecommended Piping Size Brazing Preparations-Hard-Piped UnitsConnection Methods-One-Shot Connections Branch piping sizes for refrigerant loopField Installation of Liebert Flex Pipe Kit on Liebert XDV Connecting Liebert XD Flex Pipe to Liebert XDV ModulesRefrigerant Charge-Pre-Charged Option Liebert XD prefabricated piping assembly Tools RequiredWith wrench OvertightenReturn Insulation Piping mains without Liebert XDV and Liebert Flex PipeConnecting High Voltage Cables for CSA/C-US Certified Units ElectricalRear Liebert XDV Rear of Liebert XDVLiebert XDV electrical connections for CE-approved units Connecting Low Voltage Wiring-Optional Condensate Detection ConnectionsRear View of Liebert Xdvto be N.E.C. Class Checklist for Proper Installation Installation Checklist and System Fill for StartupStart the Liebert XDV OperationInternal Access MaintenanceFluorinated Greenhouse Gas Requirements Accessing Internal Electrical Components Accessing internal electrical componentsTo remove the fan tray Specifications Liebert XDV10 specificationsLiebert XDV8 specifications Liebert XD Liebert Flex Pipe assemblies, supply and return Page Ne t ItiTi n That