Liebert user manual Placing the Liebert XDC on a Floor Stand

Page 12

Product Description

1.4.2Placing the Liebert XDC on a Floor Stand

! WARNING

Risk of top-heavy unit falling over. Improper handling can cause equipment damage, injury or death.

Read all of the following instructions before attempting to move, lift, remove packaging from or preparing unit for installation.

! CAUTION

Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move, lift, remove packaging from or prepare unit for installation.

The water/glycol floor stand can be located beneath the XDC unit or can be installed nearby.

NOTE

Consult the factory if the XDC is not installed on the water/glycol condenser floor stand to prevent exceeding maximum the piping distances.

Refer to the floor stand installation sheet shipped inside the water regulating valve package.

1.Move the floor stand assembly to its installation area and uncrate the unit.

2.Position the floor stand in its final location.

3.Insert leveler pads into each floor stand leg.

4.Level the top of the floor stand to the specified height with the flanged adjusting nut.

5.Tighten jam nuts on all legs against flanged adjusting nuts.

6.Using an appropriate lifting device or method, raise the Liebert XDC and move it above the floor stand.

7.Align the welded tabs on top of the floor stand with the inside of the unit frame base (see Detail A in Figure 7).

8.Maintaining the alignment of the Liebert XDC and the floor stand, lower the Liebert XDC onto the floor stand.

9.Connect the hot gas refrigerant lines from the Liebert XDC to the floor stand with 1-3/8" tubing (see Figures 7 and 8).

10.Connect the liquid refrigerant lines as shown from the Liebert XDC unit to the floor stand with 7/8" tubing (see Figures 7 and 8).

11.Connect the water lines as shown with the provided valving (see Figures 7 and 8).

12.Connect capillary lines from each water regulating valve to condensers in the floor stand (see Figures 7 and 8).

Capillary length is limited to 48" (1219mm).

13.Check the pipes for leaks and evacuate air from all pipes.

14.Insulate all water/glycol lines.

15.Charge each condenser loop with R-407c (see Table 17).

6

Image 12
Contents Liebert XDC General Safety Guidelines Voltage-phase-frequency Density system = 380/415-3ph-50HzExample XDC160AA Table of Contents Alarm Descriptions and Solutions SpecificationsFigures Tables General Product Information Equipment InspectionEquipment Handling Product DescriptionHandling With Skid Removal of SkidRemove tie-down brackets Liebert XDC dimensions, weight Mechanical ConsiderationsRemoving Piano Jacks Positioning the Liebert XDCPiping locations Liebert XDC piping connection sizesPlacing the Liebert XDC on a Floor Stand Detail a Liebert XDC water/glycol piping connection SizesTOP View of Floor Stand Dimensions and clearances for Liebert XDC on floor stand Positioning the Liebert XDC with Floor StandConnecting High-Voltage Cables High Voltage ConnectionsElectrical enclosure knockout locations for field wiring Contactors Extra Low Voltage Connections Liebert XDC heat rejection connection pointsField Connections-All Units Field Connections-Optional for All UnitsField Connections-Air Cooled Units only Extra Low Voltage field connections points European Union Fluorinated Greenhouse Gas Requirements Recommended Pipe SizeLiebert XDC Interconnection With Liebert XD Cooling Module Supply, return pipe sizes for Liebert XD refrigerant loopPiping Installation Method Piping Installation-R-134a Pumped CircuitPiping Mains Bypass Flow Controllers Bypass flow controllers for a Liebert XDC-based systemRequired Number Evacuation and Leak Check-R-134a Pumped Circuit InsulationLiebert XDP Liebert XDC Filling the Pumped Circuit-R-134a System refrigerant charge for the supply and return mainsCalculating Refrigerant Charge-Example Calculating refrigerant charge-exampleWorksheet to calculate refrigerant charge Install Double Discharge Risers Double discharge riser layoutPage Installation data-Lee-Temp, one-circuit, four-fan model See for details on piping connections Piping Schematic General arrangement air cooled Liebert XDC Lee-Temp Control Recommended refrigerant line sizes, DX R-407c, OD copperRecommended refrigerant line sizes for DCSL616 For mounting instructions, refer to Figure Lee-Temp Piping Lee-Temp Control Materials SuppliedFilling the Direct Expansion DX Circuit-R-407c Indoor unit refrigerant charge-R-407cOutdoor air condenser charge-R-407c Indoor water/glycol cooled module R-407C refrigerant chargeInstallation Checklist Checklist for Liebert XDC Startup Liebert XDC pump light indicatorIndicator Lights Description Green Red Compressor oil types Refrigerant TypeCompressor Type 407c Liebert XDC system is now ready to be turned on Feature Overview Microprocessor ControlDisplay User interface keypad functionsFeature Overview Viewing or Changing SettingsControls Main MenuSetpoint functions, default values and allowable ranges SetpointsMIN Temp SP HI AIR TempActive Alarms Alarm HistoryStatus TimeSetup Operation RestartDegrees Pump Start TDPump OFF TD Lead PumpLead Tandem DipswchSetpt Password Setup PasswordAlarm Enable Calibrate SensorsAlarm Time Delay COM Alarm EnableCustom Alarms Diagnostics Custom TextAlarm Descriptions Alarm Descriptions and SolutionsRed and Green Lamp Indicators Enable / Disable Alarms Alarm Time DelaysView Active Alarms View Alarm History System Shutdown CausesTroubleshooting Liebert XDC troubleshootingToo warm Maintenance Fluorinated Greenhouse Gas RequirementsAir Cooled Condenser Testing the Water Regulating Valve Function Glycol Solution MaintenanceWater/Glycol Floor Stand Condenser Shell and Tube CondensersSpecifications Liebert XDC specificationsPerformance Data Heat Rejection EquipmentPiping Connections Performance Data204 Page Ne t ItiTi n That