Checklist for Liebert XDC Startup

4.1System Refrigerant Charges Over 35 lb. (15.9kg) Require Additional Oil

System charges over 35 lb. (15.9kg) require additional oil charge to be added. See Figure 30 for the amount required for various charge levels.

Once the system has been fully charged with refrigerant, use a hand pump to add the additional oil at the suction side of the system while the system is running.

The amount of oil added by field service must be recorded on a tag attached at the tandem the amount added along with the date it was added. This will be documented on a tag located at the tandem com- pressor and marked “Oil Added Field Service Record.”

Figure 30 Additional oil requirements for refrigerant charge

Ounces

140

Each circuit contains ZRT250KCE Tandem

 

 

 

 

 

130

 

 

 

 

Circuit,

120

 

 

 

 

110

 

 

 

 

100

 

 

 

 

Per

90

 

 

 

 

80

 

 

 

 

Required

 

 

 

 

70

 

 

 

 

60

 

 

 

 

40

 

 

 

 

50

 

 

 

 

Oil

 

 

 

 

30

 

 

 

 

Additional

10

 

 

 

 

20

 

 

 

 

0

100

200

300

400

0

XDC160 System Refrigerant Field Charge Per Circuit, Pounds

 

! CAUTION

Risk of improper compressor lubrication. Can cause compressor and refrigerant system damage.

Failure to use oil types, viscosities and quantities recommended by the compressor manufacturer may reduce compressor life and void the compressor warranty. See oil types specified in Table 19.

Do not mix polyolester (POE) and mineral-based oils.

Do not mix oils of different viscosities.

Consult Emerson or the compressor manufacturer if questions arise.

Table 19 Compressor oil types

 

 

Refrigerant Type

Compressor Type

 

 

 

R-22

 

R-407c

 

 

 

 

Carlyle Semi-Hermetic

Mineral Oil

 

POE OIL - ISO 68 Viscosity

 

 

 

Copeland Scroll and Digital Scroll

POE OIL - ISO 32 Viscosity

 

 

 

 

1.Use Carlyle Mineral Oil Totaline P903-2001, Witco Suniso 3GS or other Carlyle-approved oil.

2.Use Carlyle POE Totaline P903-1001, Castrol SW68 or other Carlyle-approved oil.

3.Use Copeland® POE Oil ULTRA 22CC, Mobil EAL Arctic 22CC, Copeland brand Ultra 22 CC, Copeland brand Ultra 32 CC, Copeland brand Ultra 32-3MAF, Mobil EALArctic 22 CC or Uniqema RL32-3MAF or other Copeland-approved oil.

34

Image 40
Contents Liebert XDC Voltage-phase-frequency Density system = 380/415-3ph-50Hz General Safety GuidelinesExample XDC160AA Table of Contents Alarm Descriptions and Solutions SpecificationsFigures Tables General Product Information Equipment InspectionEquipment Handling Product DescriptionHandling With Skid Removal of SkidRemove tie-down brackets Liebert XDC dimensions, weight Mechanical ConsiderationsRemoving Piano Jacks Positioning the Liebert XDCPiping locations Liebert XDC piping connection sizesPlacing the Liebert XDC on a Floor Stand Detail a Liebert XDC water/glycol piping connection SizesTOP View of Floor Stand Dimensions and clearances for Liebert XDC on floor stand Positioning the Liebert XDC with Floor StandConnecting High-Voltage Cables High Voltage ConnectionsElectrical enclosure knockout locations for field wiring Contactors Extra Low Voltage Connections Liebert XDC heat rejection connection pointsField Connections-Optional for All Units Field Connections-All UnitsField Connections-Air Cooled Units only Extra Low Voltage field connections points European Union Fluorinated Greenhouse Gas Requirements Recommended Pipe SizeLiebert XDC Interconnection With Liebert XD Cooling Module Supply, return pipe sizes for Liebert XD refrigerant loopPiping Installation-R-134a Pumped Circuit Piping Installation MethodPiping Mains Bypass flow controllers for a Liebert XDC-based system Bypass Flow ControllersRequired Number Insulation Evacuation and Leak Check-R-134a Pumped CircuitLiebert XDP Liebert XDC Filling the Pumped Circuit-R-134a System refrigerant charge for the supply and return mainsCalculating refrigerant charge-example Calculating Refrigerant Charge-ExampleWorksheet to calculate refrigerant charge Install Double Discharge Risers Double discharge riser layoutPage Installation data-Lee-Temp, one-circuit, four-fan model See for details on piping connections Piping Schematic General arrangement air cooled Liebert XDC Lee-Temp Control Recommended refrigerant line sizes, DX R-407c, OD copperRecommended refrigerant line sizes for DCSL616 For mounting instructions, refer to Figure Lee-Temp Piping Lee-Temp Control Materials SuppliedFilling the Direct Expansion DX Circuit-R-407c Indoor unit refrigerant charge-R-407cOutdoor air condenser charge-R-407c Indoor water/glycol cooled module R-407C refrigerant chargeInstallation Checklist Liebert XDC pump light indicator Checklist for Liebert XDC StartupIndicator Lights Description Green Red Refrigerant Type Compressor oil typesCompressor Type 407c Liebert XDC system is now ready to be turned on Feature Overview Microprocessor ControlDisplay User interface keypad functionsFeature Overview Viewing or Changing SettingsControls Main MenuSetpoint functions, default values and allowable ranges SetpointsMIN Temp SP HI AIR TempActive Alarms Alarm HistoryStatus TimeSetup Operation RestartDegrees Pump Start TDPump OFF TD Lead PumpLead Tandem DipswchSetpt Password Setup PasswordAlarm Enable Calibrate SensorsCOM Alarm Enable Alarm Time DelayCustom Alarms Diagnostics Custom TextAlarm Descriptions Alarm Descriptions and SolutionsRed and Green Lamp Indicators Alarm Time Delays Enable / Disable AlarmsView Active Alarms View Alarm History System Shutdown CausesTroubleshooting Liebert XDC troubleshootingToo warm Fluorinated Greenhouse Gas Requirements MaintenanceAir Cooled Condenser Testing the Water Regulating Valve Function Glycol Solution MaintenanceWater/Glycol Floor Stand Condenser Shell and Tube CondensersSpecifications Liebert XDC specificationsPerformance Data Heat Rejection EquipmentPiping Connections Performance Data204 Page Ne t ItiTi n That