Piping and Filling with Refrigerant:
Table 9
Refrigerant Charge, lb. (kg)
Metal Liebert XD Flex Pipe Connector Length
Supply Line Diameter 1/2"
0.3lb. (0.14) 4 ft. Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply
0.5lb. (0.23) 6 ft. Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply
0.7lb. (0.32) 8 ft. Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply
0.8lb. (0.36) 10 ft. Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply
Return Line Diameter 5/8"
0.01lb. (0.01) 4 ft. Liebert XD Flex Pipe existing Liebert XDV systems
0.02lb. (0.01) 6 ft. Liebert XD Flex Pipe existing Liebert XDV systems
0.03lb. (0.01) 8 ft. Liebert XD Flex Pipe existing Liebert XDV systems
0.03lb. (0.01) 10 ft. Liebert XD Flex Pipe existing Liebert XDV systems
Return Line Diameter 1"
0.13lb. (0.06) 4 ft Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply
0.2lb. (0.096) 6 ft Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply
0.27lb. (0.126) 8 ft Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply
0.33lb. (0.15) 10 ft Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply
2.5.1Calculating Refrigerant Charge—Example
Using Tables 6, 7, 8 and 9, calculate the refrigerant charge of the individual sections of your Liebert XD system. Add the calculated charge amounts to determine the amount of
Table 10 Calculating refrigerant charge—example
| Number of Units |
|
|
| or Piping Length, | Pounds |
|
Components | feet | Per Component | Total, lb. |
Liebert XDC | 1 | 157 | 157 |
|
|
|
|
Liebert XDV8 Cooling Modules | 20 | 2.32 | 46.4 |
|
|
|
|
Supply Main, | 100 | 0.45 | 45 |
|
|
|
|
Return Main, | 100 | 0.28 | 28 |
|
|
|
|
Liebert XDV 1/2" supply Liebert XD Flex Pipes | 20 | 0.8 | 16 |
|
|
|
|
Liebert XDV 5/8" return Liebert XD Flex Pipes | 20 | 0.03 | 0.6 |
|
|
|
|
|
| Total | 293 |
Table 11 Worksheet to calculate refrigerant charge
| Number of Units | Pounds |
Components | or Piping Length | Per Component |
|
|
|
Total
Total
21