Liebert XDC user manual Setpoints, MIN Temp SP, HI AIR Temp, LO AIR Temp

Page 44

Microprocessor Control

5.3.2 SETPOINTS

Selecting SETPOINTS from the Main Menu will reveal the following menu items:

Table 21 Setpoint functions, default values and allowable ranges

Menu Item

Function

Default

Range

 

 

 

 

MIN TEMP SP *

Minimum room temperature setpoint

72 (22)

50-80 (10-27)

 

 

 

 

HI AIR TEMP

High room air temperature alarm

80 (27)

35 to 95 (2-35)

 

 

 

 

LO AIR TEMP

Low room air temperature alarm

55 (13)

35 to 95 (2-35)

 

 

 

 

* For optimal cooling performance, the minimum temperature setpoint should be at least 1-2° below the expected temperature at the remote sensor, which may require additional consideration of the remote sensor location or minimum temperature setting. If the minimum temperature setpoint is set above the typical remote temperature sensor reading, this will reduce the Liebert XD cooling output and, in extreme cases, cause erratic Liebert XD performance.

To reach the SETPOINTS menu:

1.Press the MENU button.

2.Press ENTER when the SETPOINTS menu is displayed.

3.Use the up and down arrow keys to move through the menu and view the setpoints.

To change a setpoint, follow the steps above, then:

1.Press the ENTER key to change a setpoint. (The control will ask for a setpoint password if passwords are enabled. Use the up and down arrow keys and ENTER key to enter the three-digit password when prompted.)

2.Use the up and down arrow keys to change the setpoint.

3.Then, press ENTER to accept the new setpoint. When finished, press the ESC key two to three times to return to the main display.

NOTE

Setpoints and system setup parameters are kept in non-volatile memory.

The user setpoints and ranges are:

MIN TEMP SP

This setpoint is used to keep the room temperature above the setpoint. The Liebert XDC can lower the room temperature too much depending on the room dew point and load. This setpoint will back off the cooling to keep the room temperature above this temperature, see 5.3.1 - Viewing or Changing Settings.

NOTE

This is not a true room temperature setpoint. The Liebert XDC will try to cool as much as possible. If it is able to cool the room to this setpoint, it will back off its cooling capability to try to keep the room temperature at or above this setpoint, but the Liebert XDC has no heaters, so it cannot warm the room.

HI AIR TEMP

This is the temperature at which the HIGH REMOTE TEMP and HIGH LOCAL TEMP alarms will be activated, see 5.3.1 - Viewing or Changing Settings.

LO AIR TEMP

This is the temperature at which the LOW REMOTE TEMP and LOW LOCAL TEMP alarms will be activated, see 5.3.1 - Viewing or Changing Settings.

38

Image 44
Contents Liebert XDC Example XDC160AA General Safety GuidelinesVoltage-phase-frequency Density system = 380/415-3ph-50Hz Table of Contents Alarm Descriptions and Solutions SpecificationsFigures Tables General Product Information Equipment InspectionEquipment Handling Product DescriptionHandling With Skid Removal of SkidRemove tie-down brackets Liebert XDC dimensions, weight Mechanical ConsiderationsRemoving Piano Jacks Positioning the Liebert XDCPiping locations Liebert XDC piping connection sizesPlacing the Liebert XDC on a Floor Stand Detail a Liebert XDC water/glycol piping connection SizesTOP View of Floor Stand Dimensions and clearances for Liebert XDC on floor stand Positioning the Liebert XDC with Floor StandConnecting High-Voltage Cables High Voltage ConnectionsElectrical enclosure knockout locations for field wiring Contactors Extra Low Voltage Connections Liebert XDC heat rejection connection pointsField Connections-Air Cooled Units only Field Connections-All UnitsField Connections-Optional for All Units Extra Low Voltage field connections points European Union Fluorinated Greenhouse Gas Requirements Recommended Pipe SizeLiebert XDC Interconnection With Liebert XD Cooling Module Supply, return pipe sizes for Liebert XD refrigerant loopPiping Mains Piping Installation MethodPiping Installation-R-134a Pumped Circuit Required Number Bypass Flow ControllersBypass flow controllers for a Liebert XDC-based system Liebert XDP Liebert XDC Evacuation and Leak Check-R-134a Pumped CircuitInsulation Filling the Pumped Circuit-R-134a System refrigerant charge for the supply and return mainsWorksheet to calculate refrigerant charge Calculating Refrigerant Charge-ExampleCalculating refrigerant charge-example Install Double Discharge Risers Double discharge riser layoutPage Installation data-Lee-Temp, one-circuit, four-fan model See for details on piping connections Piping Schematic General arrangement air cooled Liebert XDC Lee-Temp Control Recommended refrigerant line sizes, DX R-407c, OD copperRecommended refrigerant line sizes for DCSL616 For mounting instructions, refer to Figure Lee-Temp Piping Lee-Temp Control Materials SuppliedFilling the Direct Expansion DX Circuit-R-407c Indoor unit refrigerant charge-R-407cOutdoor air condenser charge-R-407c Indoor water/glycol cooled module R-407C refrigerant chargeInstallation Checklist Indicator Lights Description Green Red Checklist for Liebert XDC StartupLiebert XDC pump light indicator Compressor Type 407c Compressor oil typesRefrigerant Type Liebert XDC system is now ready to be turned on Feature Overview Microprocessor ControlDisplay User interface keypad functionsFeature Overview Viewing or Changing SettingsControls Main MenuSetpoint functions, default values and allowable ranges SetpointsMIN Temp SP HI AIR TempActive Alarms Alarm HistoryStatus TimeSetup Operation RestartDegrees Pump Start TDPump OFF TD Lead PumpLead Tandem DipswchSetpt Password Setup PasswordAlarm Enable Calibrate SensorsCustom Alarms Alarm Time DelayCOM Alarm Enable Diagnostics Custom TextAlarm Descriptions Alarm Descriptions and SolutionsRed and Green Lamp Indicators View Active Alarms Enable / Disable AlarmsAlarm Time Delays View Alarm History System Shutdown CausesTroubleshooting Liebert XDC troubleshootingToo warm Air Cooled Condenser MaintenanceFluorinated Greenhouse Gas Requirements Testing the Water Regulating Valve Function Glycol Solution MaintenanceWater/Glycol Floor Stand Condenser Shell and Tube CondensersSpecifications Liebert XDC specificationsPerformance Data Heat Rejection EquipmentPiping Connections Performance Data204 Page Ne t ItiTi n That