Liebert XDC user manual Setup Operation, Restart, Degrees, Pump Start TD, Pump Wait TD

Page 46

Microprocessor Control

5.3.8SETUP OPERATION

NOTE

None of these setpoints should be changed before consulting a Liebert representative. Changing any of these setpoints could drastically affect the system.

Selecting Setpoint/Setup from the Main Menu will display the following selections:

Table 22 Setup operation functions default values and allowable ranges.

Menu Item

Function

Default

Range

 

 

 

 

RESTART

Restart time delay

0.1 min

0 to 9.9 min

(0 = manual restart)

 

 

 

C/F DEGREES

Celsius or Fahrenheit

F

C or F

 

 

 

 

PUMP START TD

Pump start time delay

10 sec

3 - 120 sec

 

 

 

 

PUMP WAIT TD

Pump wait time delay

10 sec

3 - 120 sec

 

 

 

 

PUMP OFF TD

Pump off time delay

5 sec

5 - 120 sec

 

 

 

 

LEAD PUMP

Lead Pump

Pump 1

Pump 1/Pump 2

 

 

 

 

DIPSWCH

DIP switch status

NA

NA

 

 

 

 

To view the SETUP OPERATION menu

1.Press the MENU key.

2.Use the up and down arrow keys to move to the SETUP OPERATIONS menu.

3.Press the ENTER key to enter into the menu.

4.Use the up and down arrow keys to move through the menu and view the setpoints.

5.Press the ENTER key to change a setpoint. (The control will ask for a service password if passwords are enabled. Use the up and down arrow keys and ENTER key to enter the three-digit password when prompted.)

6.Use the up and down arrow keys to change the setpoint.

7.Press ENTER to accept the new setpoint.

8.When finished, press the ESC key two to three times to return to the main display.

NOTE

Setpoints and system setup parameters are kept in non-volatile memory.

RESTART

This is the time delay after which the control will attempt to restart the Liebert XDC after a loss of power. It is programmable from 0.1-9.9 minutes in 6-second (0.1 minute) increments. The user can also select NO. If NO is selected, the system WILL NOT automatically restart. The default is 0.1 min- utes.

C/F DEGREES

The user may select control and alarm parameters in either Celsius or Fahrenheit. The default is degrees Fahrenheit.

PUMP START TD

The user may set a Pump Start Time Delay to ensure that refrigerant begins flowing when the pump starts. If refrigerant does not begin flowing before the user-set delay expires, the pump will be turned off (see PUMP OFF TD).

PUMP WAIT TD

The user may set the pump wait time delay to prevent the pump from continuing to run when refrig- erant is not flowing. If a pump is running normally and refrigerant flow is lost, the pump will stay on for the specified amount of time trying to re-establish refrigerant flow. If refrigerant flow resumes during the specified interval, the pump will continue operating. If the wait time expires and refriger- ant flow has not resumed, the pump will shut down (see PUMP OFF TD).

40

Image 46
Contents Liebert XDC Voltage-phase-frequency Density system = 380/415-3ph-50Hz General Safety GuidelinesExample XDC160AA Table of Contents Alarm Descriptions and Solutions SpecificationsFigures Tables Equipment Handling General Product InformationEquipment Inspection Product DescriptionHandling With Skid Removal of SkidRemove tie-down brackets Removing Piano Jacks Liebert XDC dimensions, weightMechanical Considerations Positioning the Liebert XDCPiping locations Liebert XDC piping connection sizesPlacing the Liebert XDC on a Floor Stand Detail a Liebert XDC water/glycol piping connection SizesTOP View of Floor Stand Dimensions and clearances for Liebert XDC on floor stand Positioning the Liebert XDC with Floor StandConnecting High-Voltage Cables High Voltage ConnectionsElectrical enclosure knockout locations for field wiring Contactors Extra Low Voltage Connections Liebert XDC heat rejection connection pointsField Connections-Optional for All Units Field Connections-All UnitsField Connections-Air Cooled Units only Extra Low Voltage field connections points Liebert XDC Interconnection With Liebert XD Cooling Module European Union Fluorinated Greenhouse Gas RequirementsRecommended Pipe Size Supply, return pipe sizes for Liebert XD refrigerant loopPiping Installation-R-134a Pumped Circuit Piping Installation MethodPiping Mains Bypass flow controllers for a Liebert XDC-based system Bypass Flow ControllersRequired Number Insulation Evacuation and Leak Check-R-134a Pumped CircuitLiebert XDP Liebert XDC Filling the Pumped Circuit-R-134a System refrigerant charge for the supply and return mainsCalculating refrigerant charge-example Calculating Refrigerant Charge-ExampleWorksheet to calculate refrigerant charge Install Double Discharge Risers Double discharge riser layoutPage Installation data-Lee-Temp, one-circuit, four-fan model See for details on piping connections Piping Schematic General arrangement air cooled Liebert XDC Lee-Temp Control Recommended refrigerant line sizes, DX R-407c, OD copperRecommended refrigerant line sizes for DCSL616 For mounting instructions, refer to Figure Lee-Temp Piping Lee-Temp Control Materials SuppliedOutdoor air condenser charge-R-407c Filling the Direct Expansion DX Circuit-R-407cIndoor unit refrigerant charge-R-407c Indoor water/glycol cooled module R-407C refrigerant chargeInstallation Checklist Liebert XDC pump light indicator Checklist for Liebert XDC StartupIndicator Lights Description Green Red Refrigerant Type Compressor oil typesCompressor Type 407c Liebert XDC system is now ready to be turned on Display Feature OverviewMicroprocessor Control User interface keypad functionsControls Feature OverviewViewing or Changing Settings Main MenuMIN Temp SP Setpoint functions, default values and allowable rangesSetpoints HI AIR TempStatus Active AlarmsAlarm History TimeDegrees Setup OperationRestart Pump Start TDLead Tandem Pump OFF TDLead Pump DipswchSetpt Password Setup PasswordAlarm Enable Calibrate SensorsCOM Alarm Enable Alarm Time DelayCustom Alarms Diagnostics Custom TextAlarm Descriptions Alarm Descriptions and SolutionsRed and Green Lamp Indicators Alarm Time Delays Enable / Disable AlarmsView Active Alarms View Alarm History System Shutdown CausesTroubleshooting Liebert XDC troubleshootingToo warm Fluorinated Greenhouse Gas Requirements MaintenanceAir Cooled Condenser Water/Glycol Floor Stand Condenser Testing the Water Regulating Valve FunctionGlycol Solution Maintenance Shell and Tube CondensersSpecifications Liebert XDC specificationsPiping Connections Performance DataHeat Rejection Equipment Performance Data204 Page Ti n Ne tIti That