Liebert user manual Troubleshooting, Liebert XDC troubleshooting

Page 56

Troubleshooting

7.0TROUBLESHOOTING

Table 24 Liebert XDC troubleshooting

Symptom

Possible Cause

Check or Remedy

 

 

 

 

No main power

Check L1, L2, and L3 for rated voltage.

 

 

 

Pump/compressor

Loose electrical connections

Tighten connections.

 

 

Overloads tripped

Allow pump to cool. Check amp draw.

will not energize

 

 

 

Tripped circuit breaker

Check circuit breaker to pump(s).

 

 

 

 

Incorrect phase wiring

See Table 18.

 

 

 

 

Isolation valve(s) on pump suction

Open all isolation valves completely during normal operation.

 

and/or discharge is closed.

 

 

 

Liebert XD cooling modules are Off.

Check Liebert XD cooling modules to make sure that they are

 

ON prior to starting the Liebert XDC

 

 

 

 

Check alarm(s) history on Liebert XDC. The Liebert XDC was

 

 

operating below the dew point for a significant amount of

 

Low Refrigerant Temperature

time. Check humidity in conditioned space; lower humidity if

 

(high dew point)

necessary to allow Liebert XDC to operate at a lower

Pump will not run

 

temperature. (Disconnect must be switched to Off then back

 

to On to allow Liebert XDC to reset.)

 

Incorrect location of

Place the sensor on the return air side of the primary air

 

mover (I.e., Liebert Deluxe System 3). Do not install the

 

temperature-humidity senors

 

sensor near unsealed doors, windows and similar areas.

 

 

 

 

 

 

 

Check both differential pressure settings. If not within 6 psi,

 

Pressure switch not making contact

±1 psi (41 kPa, ±7kPa; 0.41 bars, ±0.07 bars) then manually

 

 

change accordingly.

 

Not enough charge

See 2.7 - Filling the Direct Expansion (DX) Circuit—R-

 

407c.

 

 

 

 

Check for adequate charge in system, refer to the user

 

Cavitation due to vapor in pump

manual. 2.7 - Filling the Direct Expansion (DX) Circuit—R-

Pump noisy

 

407c

 

Pump is rotating in reverse

See Table 18

 

 

 

 

Worn motor bearings

Replace pump

 

 

 

 

Low Refrigerant Temperature

Check humidity of room along with location of remote

 

sensors. Make sure that the sensors are not located in a cold

 

(high dew point)

 

area where there is a lack of sufficient air flow.

 

 

 

 

 

Liebert XDC (Pump)

Loss of power

When power is restored, the Liebert XDC will automatically

suddenly stops

 

restart.

 

Clogged filter/dryer and/or impeller

Clean out debris.

 

 

 

 

Leak in system - loss of charge

Check the entire system for leaks with a refrigerant sniffer.

 

Repair as necessary.

 

 

 

Lack of load in the room

If there is no cooling required, turn the Liebert XDC off at the

 

I/O button.

 

 

Room becomes

Minimum room temperature setpoint

Check the setpoint by following instructions in 5.3.2 -

is too low.

SETPOINTS.

too cold

 

Incorrect location of temperature-

Place the sensor on the return air side of the primary air

 

mover (i.e., Liebert Deluxe System 3). Do not install the

 

humidity senors.

 

sensor near unsealed doors, windows, and similar areas.

 

 

 

 

 

Table continued on following page

 

50

Image 56
Contents Liebert XDC Example XDC160AA General Safety GuidelinesVoltage-phase-frequency Density system = 380/415-3ph-50Hz Table of Contents Alarm Descriptions and Solutions SpecificationsFigures Tables General Product Information Equipment InspectionEquipment Handling Product DescriptionHandling With Skid Removal of SkidRemove tie-down brackets Liebert XDC dimensions, weight Mechanical ConsiderationsRemoving Piano Jacks Positioning the Liebert XDCPiping locations Liebert XDC piping connection sizesPlacing the Liebert XDC on a Floor Stand Detail a Liebert XDC water/glycol piping connection SizesTOP View of Floor Stand Dimensions and clearances for Liebert XDC on floor stand Positioning the Liebert XDC with Floor StandConnecting High-Voltage Cables High Voltage ConnectionsElectrical enclosure knockout locations for field wiring Contactors Extra Low Voltage Connections Liebert XDC heat rejection connection pointsField Connections-Air Cooled Units only Field Connections-All UnitsField Connections-Optional for All Units Extra Low Voltage field connections points European Union Fluorinated Greenhouse Gas Requirements Recommended Pipe SizeLiebert XDC Interconnection With Liebert XD Cooling Module Supply, return pipe sizes for Liebert XD refrigerant loopPiping Mains Piping Installation MethodPiping Installation-R-134a Pumped Circuit Required Number Bypass Flow ControllersBypass flow controllers for a Liebert XDC-based system Liebert XDP Liebert XDC Evacuation and Leak Check-R-134a Pumped CircuitInsulation Filling the Pumped Circuit-R-134a System refrigerant charge for the supply and return mainsWorksheet to calculate refrigerant charge Calculating Refrigerant Charge-ExampleCalculating refrigerant charge-example Install Double Discharge Risers Double discharge riser layoutPage Installation data-Lee-Temp, one-circuit, four-fan model See for details on piping connections Piping Schematic General arrangement air cooled Liebert XDC Lee-Temp Control Recommended refrigerant line sizes, DX R-407c, OD copperRecommended refrigerant line sizes for DCSL616 For mounting instructions, refer to Figure Lee-Temp Piping Lee-Temp Control Materials SuppliedFilling the Direct Expansion DX Circuit-R-407c Indoor unit refrigerant charge-R-407cOutdoor air condenser charge-R-407c Indoor water/glycol cooled module R-407C refrigerant chargeInstallation Checklist Indicator Lights Description Green Red Checklist for Liebert XDC StartupLiebert XDC pump light indicator Compressor Type 407c Compressor oil typesRefrigerant Type Liebert XDC system is now ready to be turned on Feature Overview Microprocessor ControlDisplay User interface keypad functionsFeature Overview Viewing or Changing SettingsControls Main MenuSetpoint functions, default values and allowable ranges SetpointsMIN Temp SP HI AIR TempActive Alarms Alarm HistoryStatus TimeSetup Operation RestartDegrees Pump Start TDPump OFF TD Lead PumpLead Tandem DipswchSetpt Password Setup PasswordAlarm Enable Calibrate SensorsCustom Alarms Alarm Time DelayCOM Alarm Enable Diagnostics Custom TextAlarm Descriptions Alarm Descriptions and SolutionsRed and Green Lamp Indicators View Active Alarms Enable / Disable AlarmsAlarm Time Delays View Alarm History System Shutdown CausesTroubleshooting Liebert XDC troubleshootingToo warm Air Cooled Condenser MaintenanceFluorinated Greenhouse Gas Requirements Testing the Water Regulating Valve Function Glycol Solution MaintenanceWater/Glycol Floor Stand Condenser Shell and Tube CondensersSpecifications Liebert XDC specificationsPerformance Data Heat Rejection EquipmentPiping Connections Performance Data204 Page Ne t ItiTi n That