Liebert XDC user manual Lee-Temp Piping, Lee-Temp Control Materials Supplied

Page 36

Piping and Filling with Refrigerant: R-134a and R-407c Circuits

2.6.1Air Cooled Condenser with Lee-Temp “Flooded Condenser” Head Pressure Control System—R-407c (DX) Circuit

The Lee-Temp system consists of a modulating type head pressure control valves and insulated receivers with heater pads to ensure operation at ambient temperatures as low as -30°F (-34.4°C).

Lee-Temp Piping

Two discharge lines and two liquid lines must be field-installed between the indoor unit and the out- door condenser. See Figures 24 and 27 for details.

Lee-Temp Control Materials Supplied

Built-in, pre-wired condenser control box

Air cooled condenser

Piping access cover to be reinstalled when piping is complete

Bolts—four per leg (3/8" x 5/8")

Terminal block for two-wire, 24V interlock connection between unit and condenser

Condensate legs—four with one-fan, six on two-and three-fan models and eight on four-fan mod- els

Bolts—used to mount receiver (3/8" x 1-1/4")

Lee-Temp system:

Insulated storage receiver—one per circuit

Head pressure control assembly (head pressure valves and check valves) - one per circuit

Service valve—one per circuit

Pressure relief valve—one per circuit

Liquid level sight glasses

NOTE

Lee-Temp heater pads require a separate, continuous electrical source. See nameplate on unit for proper voltage.

Evacuation and Leak Check—R-407c (DX) Circuit (Air and Water/Glycol Systems)

1.Make sure the unit is Off. Open all disconnects and pull all fuses except the control fuses. On units supplied with circuit breakers, open all breakers except for the transformer.

2.Energize the liquid line solenoid valves via 24VAC or through Diagnostics under “Test Outputs,” select DEHYDRATION to be On (see 5.3.17 - DIAGNOSTICS). This will energize the solenoids and hot gas valves to open simultaneously on Circuit 1 and Circuit 2.

NOTE

The procedures above allow the technician to use 24VAC power and controls to open liquid line solenoid valve(s) for the dehydration process. If no power is at the unit disconnect, the technician is to use a separate 24VAC source rated at 75 VA and connect to the system liquid line solenoid valve(s) directly.

3.Attach refrigerant gauges to the suction and discharge service valves of the compressor.

4.Open all compressor service valves, including those located outside the Liebert XDC.

5.Connect the tank of dry nitrogen to the Schrader valves on the liquid lines and the hot gas lines.

6.Pressurize the system circuit(s) to 150 PSIG (1034 kPa; 10.34 bars) with dry nitrogen with a trace of refrigerant. Check the system for leaks with a suitable leak finder.

7.After completion of leak testing, release the test pressure (per local code) and connect to vacuum pump(s) at the Schrader valves on the liquid lines and on the hot gas lines.

8.After 4 hours of pulling a deep vacuum, check the vacuum levels and, if they have not changed, break the vacuum with dry nitrogen.

9.Pull a second and third vacuum to 250 microns or less. Recheck the vacuum level after 2 hours.

30

Image 36
Contents Liebert XDC General Safety Guidelines Voltage-phase-frequency Density system = 380/415-3ph-50HzExample XDC160AA Table of Contents Alarm Descriptions and Solutions SpecificationsFigures Tables General Product Information Equipment InspectionEquipment Handling Product DescriptionHandling With Skid Removal of SkidRemove tie-down brackets Liebert XDC dimensions, weight Mechanical ConsiderationsRemoving Piano Jacks Positioning the Liebert XDCPiping locations Liebert XDC piping connection sizesPlacing the Liebert XDC on a Floor Stand Detail a Liebert XDC water/glycol piping connection SizesTOP View of Floor Stand Dimensions and clearances for Liebert XDC on floor stand Positioning the Liebert XDC with Floor StandConnecting High-Voltage Cables High Voltage ConnectionsElectrical enclosure knockout locations for field wiring Contactors Extra Low Voltage Connections Liebert XDC heat rejection connection pointsField Connections-All Units Field Connections-Optional for All UnitsField Connections-Air Cooled Units only Extra Low Voltage field connections points European Union Fluorinated Greenhouse Gas Requirements Recommended Pipe SizeLiebert XDC Interconnection With Liebert XD Cooling Module Supply, return pipe sizes for Liebert XD refrigerant loopPiping Installation Method Piping Installation-R-134a Pumped CircuitPiping Mains Bypass Flow Controllers Bypass flow controllers for a Liebert XDC-based systemRequired Number Evacuation and Leak Check-R-134a Pumped Circuit InsulationLiebert XDP Liebert XDC Filling the Pumped Circuit-R-134a System refrigerant charge for the supply and return mainsCalculating Refrigerant Charge-Example Calculating refrigerant charge-exampleWorksheet to calculate refrigerant charge Install Double Discharge Risers Double discharge riser layoutPage Installation data-Lee-Temp, one-circuit, four-fan model See for details on piping connections Piping Schematic General arrangement air cooled Liebert XDC Lee-Temp Control Recommended refrigerant line sizes, DX R-407c, OD copperRecommended refrigerant line sizes for DCSL616 For mounting instructions, refer to Figure Lee-Temp Piping Lee-Temp Control Materials SuppliedFilling the Direct Expansion DX Circuit-R-407c Indoor unit refrigerant charge-R-407cOutdoor air condenser charge-R-407c Indoor water/glycol cooled module R-407C refrigerant chargeInstallation Checklist Checklist for Liebert XDC Startup Liebert XDC pump light indicatorIndicator Lights Description Green Red Compressor oil types Refrigerant TypeCompressor Type 407c Liebert XDC system is now ready to be turned on Feature Overview Microprocessor ControlDisplay User interface keypad functionsFeature Overview Viewing or Changing SettingsControls Main MenuSetpoint functions, default values and allowable ranges SetpointsMIN Temp SP HI AIR TempActive Alarms Alarm HistoryStatus TimeSetup Operation RestartDegrees Pump Start TDPump OFF TD Lead PumpLead Tandem DipswchSetpt Password Setup PasswordAlarm Enable Calibrate SensorsAlarm Time Delay COM Alarm EnableCustom Alarms Diagnostics Custom TextAlarm Descriptions Alarm Descriptions and SolutionsRed and Green Lamp Indicators Enable / Disable Alarms Alarm Time DelaysView Active Alarms View Alarm History System Shutdown CausesTroubleshooting Liebert XDC troubleshootingToo warm Maintenance Fluorinated Greenhouse Gas RequirementsAir Cooled Condenser Testing the Water Regulating Valve Function Glycol Solution MaintenanceWater/Glycol Floor Stand Condenser Shell and Tube CondensersSpecifications Liebert XDC specificationsPerformance Data Heat Rejection EquipmentPiping Connections Performance Data204 Page Ne t ItiTi n That