Liebert XDC user manual Too warm

Page 57

Troubleshooting

Table 24 Liebert XDC troubleshooting (continued)

Symptom

Possible Cause

Check or Remedy

 

Liebert XDC is off.

Check status of the Liebert XDC at the user interface. Turn

 

system On at I/O button if system is Off.

 

 

 

 

Check temperature and relative humidity (RH) of room.

 

High dew point

Lower RH setpoint if necessary to lower dew point. At normal

 

room temperature of 68°F (20°C), the RH should be set to

 

 

Room becomes

 

50% or lower.

 

 

Liebert XD cooling modules are Off.

Check Liebert XD cooling modules to make sure that they are

too warm

On before starting the Liebert XDC.

 

 

 

 

 

 

Minimum room temperature setpoint

Check the setpoint by following instructions in 5.3.2 -

 

is too high.

SETPOINTS.

 

Incorrect location of temperature-

Place the sensor on the return air side of the primary air

 

mover (I.e., Liebert Deluxe System 3). Do not install the

 

humidity senors

 

sensor near unsealed doors, windows, and similar areas.

 

 

 

 

 

Pipe rattle

Loose pipe connections

Check pipe connections.

 

 

 

 

No 24VAC power to motor

Check for 24VAC between P2-1 and P2-4.

 

 

 

Actuator motors

No signal from control

Check 24VAC at P22-1 (close) or P22-3 (close).

 

 

 

Unplug P22 completely off of the board. Jumper P22-5 to P2-

(if applicable)

 

Motor not operating

4 for grounding, then jumper P22-1 to P2-1 to drive close.

 

 

Remove jumper to close, and then jumper P22-3 to P2-1 to

 

 

 

 

drive open. If motor fails to work, replace it.

 

 

 

 

Check control panel for welded

 

Motor burnout

contactor contacts or welded

Replace defective components.

 

overload contacts

 

Main 24VAC

Shorts or loose connections

Check the wiring connections of the 24VAC circuit.

fuse trips

Faulty circuit board

Replace the circuit board.

 

 

 

Unstable pump

R-134a pump loop is overcharged

While pump is running R-134a receiver level must be within

operation

recommended levels (see Figure 31).

 

51

Image 57
Contents Liebert XDC General Safety Guidelines Voltage-phase-frequency Density system = 380/415-3ph-50HzExample XDC160AA Table of Contents Specifications Alarm Descriptions and SolutionsFigures Tables Equipment Inspection General Product InformationEquipment Handling Product DescriptionRemoval of Skid Handling With SkidRemove tie-down brackets Mechanical Considerations Liebert XDC dimensions, weightRemoving Piano Jacks Positioning the Liebert XDCLiebert XDC piping connection sizes Piping locationsPlacing the Liebert XDC on a Floor Stand Liebert XDC water/glycol piping connection Sizes Detail aTOP View of Floor Stand Positioning the Liebert XDC with Floor Stand Dimensions and clearances for Liebert XDC on floor standHigh Voltage Connections Connecting High-Voltage CablesElectrical enclosure knockout locations for field wiring Contactors Liebert XDC heat rejection connection points Extra Low Voltage ConnectionsField Connections-All Units Field Connections-Optional for All UnitsField Connections-Air Cooled Units only Extra Low Voltage field connections points Recommended Pipe Size European Union Fluorinated Greenhouse Gas RequirementsLiebert XDC Interconnection With Liebert XD Cooling Module Supply, return pipe sizes for Liebert XD refrigerant loopPiping Installation Method Piping Installation-R-134a Pumped CircuitPiping Mains Bypass Flow Controllers Bypass flow controllers for a Liebert XDC-based systemRequired Number Evacuation and Leak Check-R-134a Pumped Circuit InsulationLiebert XDP Liebert XDC System refrigerant charge for the supply and return mains Filling the Pumped Circuit-R-134aCalculating Refrigerant Charge-Example Calculating refrigerant charge-exampleWorksheet to calculate refrigerant charge Double discharge riser layout Install Double Discharge RisersPage Installation data-Lee-Temp, one-circuit, four-fan model See for details on piping connections Piping Schematic Recommended refrigerant line sizes, DX R-407c, OD copper General arrangement air cooled Liebert XDC Lee-Temp ControlRecommended refrigerant line sizes for DCSL616 For mounting instructions, refer to Figure Lee-Temp Control Materials Supplied Lee-Temp PipingIndoor unit refrigerant charge-R-407c Filling the Direct Expansion DX Circuit-R-407cOutdoor air condenser charge-R-407c Indoor water/glycol cooled module R-407C refrigerant chargeInstallation Checklist Checklist for Liebert XDC Startup Liebert XDC pump light indicatorIndicator Lights Description Green Red Compressor oil types Refrigerant TypeCompressor Type 407c Liebert XDC system is now ready to be turned on Microprocessor Control Feature OverviewDisplay User interface keypad functionsViewing or Changing Settings Feature OverviewControls Main MenuSetpoints Setpoint functions, default values and allowable rangesMIN Temp SP HI AIR TempAlarm History Active AlarmsStatus TimeRestart Setup OperationDegrees Pump Start TDLead Pump Pump OFF TDLead Tandem DipswchSetup Password Setpt PasswordCalibrate Sensors Alarm EnableAlarm Time Delay COM Alarm EnableCustom Alarms Custom Text DiagnosticsAlarm Descriptions and Solutions Alarm DescriptionsRed and Green Lamp Indicators Enable / Disable Alarms Alarm Time DelaysView Active Alarms System Shutdown Causes View Alarm HistoryLiebert XDC troubleshooting TroubleshootingToo warm Maintenance Fluorinated Greenhouse Gas RequirementsAir Cooled Condenser Glycol Solution Maintenance Testing the Water Regulating Valve FunctionWater/Glycol Floor Stand Condenser Shell and Tube CondensersLiebert XDC specifications SpecificationsHeat Rejection Equipment Performance DataPiping Connections Performance Data204 Page Iti Ne tTi n That