Liebert XDC user manual Install Double Discharge Risers, Double discharge riser layout

Page 28

Piping and Filling with Refrigerant: R-134a and R-407c Circuits

2.5.2Piping for Direct Expansion (DX) Circuit—R-407c Air Cooled Units

! WARNING

Risk of refrigerant system explosion or rupture from overpressurization. Can cause death, injury and equipment damage.

Installer must install a 400 psig pressure relief valve in each of the two R-407c refrigerant circuits of the Liebert XDC system. Do not install shutoff valves between the compressors and the pressure relief valves.

For systems requiring EU CE compliance, the pressure relief valves must be CE-certified by a notified body to the EU Pressure Equipment Directive.

2.6Install Double Discharge Risers

For air-cooled systems, double discharge risers must be installed in the hot gas lines that have verti- cal heights of 15 feet (4.6m) or more (see Figure 23). This will allow proper oil return to the compres- sors when the system is running at low loads. A double riser system is constructed of a large diameter riser with a trap at the base and a riser with a smaller diameter in parallel.

At full-load operation, the refrigerant vapor flows up both risers at velocities that are adequate to carry the oil. At low loads, refrigerant vapor velocities are lower and the trap at the bottom of the riser becomes filled with oil. When this happens, refrigerant flows up only the smaller riser.

The trap at the top of the riser must be tied into the top of the line to prevent oil from filling the larger riser. For each double riser used, the maximum height of the riser must not exceed 15 feet (4.6m). Multiple risers must be installed in series as the height of the hot gas line increases. Total maximum height of the hot gas line must not exceed 60 feet (18.3m).

Horizontal discharge lines should be pitched downward in the direction of flow to aid in oil drainage with downward pitch of at least 1/2 inch in 10 feet (13mm in 3m).

Figure 23 Double discharge riser layout

Connection point of upper trap is at the top of the line

Larger riser 1-1/8" O.D. copper

Smaller riser is 5/8" O.D. copper

Trap size is 1-1/8" large riser size with minimum internal

Contact your local Liebert representative for factory approval whenever a refrigerant piping run exceeds 200 feet (60m) equivalent length or when condensers must be installed below the level of the cooling coil.

22

Image 28
Contents Liebert XDC Voltage-phase-frequency Density system = 380/415-3ph-50Hz General Safety GuidelinesExample XDC160AA Table of Contents Alarm Descriptions and Solutions SpecificationsFigures Tables General Product Information Equipment InspectionEquipment Handling Product DescriptionHandling With Skid Removal of SkidRemove tie-down brackets Liebert XDC dimensions, weight Mechanical ConsiderationsRemoving Piano Jacks Positioning the Liebert XDCPiping locations Liebert XDC piping connection sizesPlacing the Liebert XDC on a Floor Stand Detail a Liebert XDC water/glycol piping connection SizesTOP View of Floor Stand Dimensions and clearances for Liebert XDC on floor stand Positioning the Liebert XDC with Floor StandConnecting High-Voltage Cables High Voltage ConnectionsElectrical enclosure knockout locations for field wiring Contactors Extra Low Voltage Connections Liebert XDC heat rejection connection pointsField Connections-Optional for All Units Field Connections-All UnitsField Connections-Air Cooled Units only Extra Low Voltage field connections points European Union Fluorinated Greenhouse Gas Requirements Recommended Pipe SizeLiebert XDC Interconnection With Liebert XD Cooling Module Supply, return pipe sizes for Liebert XD refrigerant loopPiping Installation-R-134a Pumped Circuit Piping Installation MethodPiping Mains Bypass flow controllers for a Liebert XDC-based system Bypass Flow ControllersRequired Number Insulation Evacuation and Leak Check-R-134a Pumped CircuitLiebert XDP Liebert XDC Filling the Pumped Circuit-R-134a System refrigerant charge for the supply and return mainsCalculating refrigerant charge-example Calculating Refrigerant Charge-ExampleWorksheet to calculate refrigerant charge Install Double Discharge Risers Double discharge riser layoutPage Installation data-Lee-Temp, one-circuit, four-fan model See for details on piping connections Piping Schematic General arrangement air cooled Liebert XDC Lee-Temp Control Recommended refrigerant line sizes, DX R-407c, OD copperRecommended refrigerant line sizes for DCSL616 For mounting instructions, refer to Figure Lee-Temp Piping Lee-Temp Control Materials SuppliedFilling the Direct Expansion DX Circuit-R-407c Indoor unit refrigerant charge-R-407cOutdoor air condenser charge-R-407c Indoor water/glycol cooled module R-407C refrigerant chargeInstallation Checklist Liebert XDC pump light indicator Checklist for Liebert XDC StartupIndicator Lights Description Green Red Refrigerant Type Compressor oil typesCompressor Type 407c Liebert XDC system is now ready to be turned on Feature Overview Microprocessor ControlDisplay User interface keypad functionsFeature Overview Viewing or Changing SettingsControls Main MenuSetpoint functions, default values and allowable ranges SetpointsMIN Temp SP HI AIR TempActive Alarms Alarm HistoryStatus TimeSetup Operation RestartDegrees Pump Start TDPump OFF TD Lead PumpLead Tandem DipswchSetpt Password Setup PasswordAlarm Enable Calibrate SensorsCOM Alarm Enable Alarm Time DelayCustom Alarms Diagnostics Custom TextAlarm Descriptions Alarm Descriptions and SolutionsRed and Green Lamp Indicators Alarm Time Delays Enable / Disable AlarmsView Active Alarms View Alarm History System Shutdown CausesTroubleshooting Liebert XDC troubleshootingToo warm Fluorinated Greenhouse Gas Requirements MaintenanceAir Cooled Condenser Testing the Water Regulating Valve Function Glycol Solution MaintenanceWater/Glycol Floor Stand Condenser Shell and Tube CondensersSpecifications Liebert XDC specificationsPerformance Data Heat Rejection EquipmentPiping Connections Performance Data204 Page Ne t ItiTi n That