Liebert NX UPS System user manual Introduction, Preliminary Checks

Page 11

Single Module UPS Installation

1.0SINGLE MODULE UPS INSTALLATION

1.1Introduction

This following section describes the requirements that must be taken into account when planning the positioning and cabling of the Liebert NX uninterruptible power supply and related equipment.

This chapter is a guide as to general procedures and practices that should be observed by the install- ing engineer. The particular conditions of each site will determine the applicability of such proce- dures.

! WARNING

Professional Installation Required

Do not apply electrical power to the UPS equipment before being authorised to do so by the commissioning engineer.

The UPS equipment shall be installed by a qualified electrical tradesperson in accordance with the information contained in this manual. All equipment not referred to this manual is shipped with details of its own mechanical and electrical installation.

NOTE

Three-phase, 4-wire input supply required.

The standard Liebert NX UPS is suitable for connection to 3-phase, 4-wire (+ Earth) TN, TT and IT AC power distribution systems (IEC60364-3). Optional 3-wire to 4-wire conversion transformers are available. If it is used in IT AC power distribution systems, a 4-pole circuit breaker must be used on the input and refer to the relative IT Systems’ standard

! WARNING

Battery Hazards

Special care should be taken when working with the batteries associated with this equipment. When connected together, the battery terminal voltage will exceed 400VDC and is hazardous.

Eye protection should be worn to prevent injury from accidental electrical arcs. Remove rings, watches and all other metal objects.

Use only tools with insulated handles. Wear rubber gloves.

If a battery leaks electrolyte or is otherwise physically damaged, it must be replaced, stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations.

If electrolyte comes into contact with the skin, the affected area should be washed immediately with water.

1.2Preliminary Checks

Before installing the UPS, please carry out the following preliminary checks:

1.Visually examine the UPS and battery equipment for transit damage, both internally and externally. Report any damage to the shipper immediately.

2.Verify that the correct equipment is being installed. The equipment supplied has an identification tag on the back of the main door reporting: the type, size and main calibration parameters of the UPS.

3

Image 11
Contents Liebert NX UPS Page Table of Contents Dual Bus System UPS MULTI-MODULEINSTALLATIONOperator Control Panel and Display Operating ProceduresOPTIONS-FORASSEMBLY Inside the UPS Cabinet Technical SpecificationsFigures Tables Options Model Identification Feature Set for Region InputOutput Aust/NZConformity and Standards Safety PrecautionsBattery Voltage Exceeds 400VDC User-Serviceable PartsPreliminary Checks IntroductionStorage External Battery RoomLocation UPS RoomMoving the Cabinets PositioningSystem Cabinets 2 10 to 30kVA UPSExternal Protective Devices UPS Output External BatteryEarth Leakage RCD Distance from floor to connection point on the equipment Power CablesMaximum steady state AC and DC currents Common Input Connections Cable TerminationOutput System Connections Control Cables and Communication Monitor Board FeaturesInput Dry Contacts X3 Ancillary Control and AlarmsMaintenance Bypass Cabinet Interface Dry ContactsJumper connection for BCB interface External Circuit-Breaker InterfaceJ28 Output Dry ContactsOutput dry contact relays +12V J13 J21X6 Analog Input Interface Emergency Power Off InputX5 Auxiliary DC Power Output X7 External Battery Temperature Detector InterfaceSerial Ports RS232-1 and RS232-2 External Bypass Switch InterlockBattery Start Facility Battery Start ButtonBattery Installation Hazardous battery voltage present behind covers SafetyBattery Cabinet Name W2 L=5m Name W1 L=30m Battery Temperature Sensor OptionalMoving the Battery Cabinets Cable W2 is packed with the temperature sensorGeneral Arrangement Drawings Battery cabinet bottom cable entry locationBottom cable entry Battery cabinet internal layout Item # Item Name Battery Power CablesConnection Principles Fitting the Batteries Battery ControlConnecting the Battery Battery Room DesignX21 GeneralX23 X24 Monitor Board X24Distribution Cabinet Cabinet InstallationParalleled UPS Modules External Protective Devices Power CablesControl Cables Intermodule Control Hot-Standby UPS ModulesInput Distribution Upstream Dual Bus System Parallel Board DBS Cable X2-2 X1-1 Parallel System Control WiresExtended Dual Bus Synchronization Option DBS Interface Box Parallel Board X2-2 X1-1 Parallel SystemInstallation Drawings General arrangement-10-30kVA UPS module External Battery Input Output Main Input Bypass Input NXe 10-30kVA Top View Internal battery layout and connecting-GP12120 F2 12AH/12V Internal battery layout Split-Bypass Input Battery Temperature Compensation Static Transfer SwitchSocket Outlet Redundant Control Power Supply BoardMulti Module UPS-1+N Modes of Operation Parallel Redundancy Mode System Expansion Bypass ModeMaintenance Mode Manual Bypass ECO Mode Single UPS OnlyNormal Function Battery Management-Set During CommissioningBattery Protection settings by commissioning engineer UPS operating modes Power SwitchesRotary switch configurations UPS Startup Start-Up ProcedureIndicator State Verify Switching Between Operation Modes Powering Down the UPS Switching the UPS from Normal to Maintenance BypassPowering Down the UPS and Maintaining Power to Load Auto Restart Emergency Shutdown With EPOChanging the Current Date and Time Command PasswordLanguage Selection Isolating One Module in a Multi-Module System LED Function Status Inserting One Module into a Multi-Module SystemButton Function UPS control and display panel componentsComponent # Function Audible Alarm Buzzer Mimic Power FlowMenu key Icons and their meaning Direct Access Push Buttons KeysLCD Monitor and Menu keys Displayed on the front LCD. When not activated, Load System Battery RecordsLanguage Settings Command Version When configured, input transformer voltages areMenu Type Item Type Explanation Detailed Description of Menu ItemsUPS system window Descriptions of UPS menus and data window itemsNumber to be dialed to send an alarm notification Message Description / Suggested Action if any UPS messagesBypass voltage exceeds the limit UPS is confirmed to overload and the overload times out UPS messages Prompt Meaning Dynamic Energy Flow Chart and UPS Help ScreenPrompt Pop-Up Windows Prompt windows, meaningsDefault screen Default Screen SaverTerminal Name Definition Battery Ground Fault DetectionProtection AC Fan Redundant Fan for Power ModuleFan120 Fan120OC Web Card data summary window OC Web Card SNMP/HTTP Network Interface CardRelay card jumpers Relay Card pin configurationRelay Card Multiport-4 CardPin Description SiteNet MultiPort4 Intellislot pin assignmentAssignment OC485 Web Card Modbus, Jbus, IGM Net Remote Alarm MonitorDust Filter for 10-30kVA Dust filter replacementOverall efficiency, heat losses and air exchange Environmental characteristicsConformity and Standards Compliance with European, international standardsRectifier AC input mains Mechanical characteristicsInverter output to critical load Bypass mains input Technical Specifications Technical Specifications Page That Ne tIti Ti n