Operator Control Panel and Display
7.1.1Mimic Power Flow
The LEDs mounted on the mimic flow chart represent the various power paths and current UPS oper- ational status.
Table 12 | Rectifier | |
|
|
|
Green |
| Rectifier in Normal Operation |
|
|
|
Flashing |
| Input AC Normal, but rectifier not operating |
Green |
|
|
Red |
| Rectifier Failed |
|
|
|
Off |
| Rectifier Not operating, Input AC Not Available or out of normal range |
|
|
|
Table 13 | Battery | |
|
|
|
Green |
| Battery Normal, but discharging and powering the load |
|
|
|
Flashing |
| Battery End of Discharge |
Green |
|
|
|
| Battery abnormal (Failed, Absent or Polarity Reversed) or Battery |
Red |
| Converter abnormal |
|
| (Failed, overcurrent, overtemperature) |
Off |
| Battery and Converter Normal, Battery charging. |
|
|
|
Table 14 | Bypass | |
Green |
| Load on Bypass power |
|
|
|
Red |
| Bypass not available, out of normal range or Static bypass switch fault. |
|
|
|
Off |
| Bypass Normal, load not on bypass |
|
|
|
Table 15 | Inverter | |
|
|
|
Green |
| Inverter Normal and powering the load |
|
|
|
Flashing |
| Inverter ON, starting up, synchronising, |
Green |
| or standing by (ECO mode) |
Red |
| Inverter failed |
|
|
|
Off |
| Inverter not operating |
|
|
|
Table 16 | Load | |
Green |
| UPS output ON and Normal |
|
|
|
Red |
| UPS output ON and Overloaded |
|
|
|
Off |
| UPS output OFF. |
|
| |
Table 17 Status (Alarm) | ||
|
|
|
Green |
| Normal Operation |
|
|
|
Yellow |
| UPS Warning e.g. AC Input Failure |
|
|
|
Red |
| UPS fault e.g. Fuse or Hardware failure |
|
|
|
7.1.2Audible Alarm (Buzzer)
UPS activity is accompanied by the following sounds
Table 18 Audible alarm key
Single beep | Direct Access key acknowledgement |
|
|
One beep | UPS Warning e.g. AC Input Failure |
per second |
|
Continuous | Fault e.g. Fuse or Hardware failure |
beep |
|
55