Options—For Assembly Inside the UPS Cabinet

8.1.4Relay Card

The Relay card provides voltage-free contact closures for remote monitoring of alarm conditions.

Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS signals, the easy-to-install card integrates with AS/400 computers (additional cable required) and other relay contact monitoring systems.

The Relay card is rated for 24 VAC/VDC at 1A and supported in any of the three NX Intellislot bays.

Table 25 Relay Card pin configuration

Pin

Function

Operation

1

UPS Fault

Closed if no UPS failure

 

 

 

2-3

Not Used

 

 

 

 

4

UPS Fault

Closed if UPS fails

 

 

 

5

Summary Alarm**

Closed if SUMMARY ALARM** occurs

 

 

 

6

Summary Alarm**

Closed if no alarm conditions are present

 

 

 

7

Any Mode Shutdown return

Not Supported– use External EPO terminal

 

 

 

8

Not Used

 

 

 

 

9

Common - Low Battery

 

 

 

 

10

Low Battery

Closed if battery is OK

 

 

 

11

Low Battery

Closed if LOW BATTERY point occurs.

 

 

 

12-13

Not Used

 

 

 

 

14

UPS Any Mode Shutdown

Not supported– use External EPO terminal

 

 

 

15

On UPS

Closed if ON UPS (inverter) power

 

 

 

16

On Battery

Closed if ON BATTERY power (Utility failure)

 

 

 

17

Common - UPS Fault, Summary Alarm,

 

 

On UPS, On Battery, On Bypass

 

18

On Battery

Closed if not ON Battery power (Utility OK)

 

 

 

19 ÷ 23

Not Used

 

 

 

 

24

On Bypass

Closed if ON BYPASS

 

 

 

25

Not Used

 

 

 

 

**A Summary Alarm occurs when any of the following conditions exist:

Utility power is out of the acceptable range (voltage and/or frequency)

UPS is in BYPASS MODE (load not on Inverter power)

UPS Battery is LOW

UPS fault has occurred

Table 26 Relay card jumpers

#

Connection

Description

JP01

Pin 9 to Pin 17

Allows all relay COMMONS to be tied together.

 

 

 

JP02

Pin 7 to Pin 17

Irrelevant for NX - (Interconnects all relay COMMONS and the (not

supported) ANY MODE SHUTDOWN Return.

 

 

8.1.5Multiport-4 Card

The Multiport-4 card provides 4 sets of voltage-free contact closures for remote monitoring of alarm conditions UPS operation On Battery and battery low condition. A typical application is to allows a maximum of four computer systems to simultaneously monitor the status (e.g., utility power failure / low battery) of a single UPS.

This card is supported in any of the three NX Intellislot bays.

69

Image 77
Contents Liebert NX UPS Page Table of Contents Dual Bus System UPS MULTI-MODULEINSTALLATIONOPTIONS-FORASSEMBLY Inside the UPS Cabinet Operating ProceduresTechnical Specifications Operator Control Panel and DisplayFigures Tables Output Feature Set for Region InputAust/NZ Options Model IdentificationConformity and Standards Safety PrecautionsBattery Voltage Exceeds 400VDC User-Serviceable PartsPreliminary Checks IntroductionLocation External Battery RoomUPS Room StorageSystem Cabinets Positioning2 10 to 30kVA UPS Moving the CabinetsExternal Protective Devices UPS Output External BatteryEarth Leakage RCD Distance from floor to connection point on the equipment Power CablesMaximum steady state AC and DC currents Common Input Connections Cable TerminationOutput System Connections Control Cables and Communication Monitor Board FeaturesMaintenance Bypass Cabinet Interface X3 Ancillary Control and AlarmsDry Contacts Input Dry ContactsJumper connection for BCB interface External Circuit-Breaker InterfaceOutput dry contact relays Output Dry Contacts+12V J13 J21 J28X5 Auxiliary DC Power Output Emergency Power Off InputX7 External Battery Temperature Detector Interface X6 Analog Input InterfaceBattery Start Facility External Bypass Switch InterlockBattery Start Button Serial Ports RS232-1 and RS232-2Battery Installation Hazardous battery voltage present behind covers SafetyBattery Cabinet Moving the Battery Cabinets Battery Temperature Sensor OptionalCable W2 is packed with the temperature sensor Name W2 L=5m Name W1 L=30mGeneral Arrangement Drawings Battery cabinet bottom cable entry locationBottom cable entry Battery cabinet internal layout Item # Item Name Battery Power CablesConnection Principles Connecting the Battery Battery ControlBattery Room Design Fitting the BatteriesX23 X24 Monitor Board GeneralX24 X21Distribution Cabinet Cabinet InstallationParalleled UPS Modules External Protective Devices Power CablesControl Cables Intermodule Control Hot-Standby UPS ModulesInput Distribution Upstream Dual Bus System Extended Dual Bus Synchronization Option DBS Interface Box Control WiresParallel Board X2-2 X1-1 Parallel System Parallel Board DBS Cable X2-2 X1-1 Parallel SystemInstallation Drawings General arrangement-10-30kVA UPS module External Battery Input Output Main Input Bypass Input NXe 10-30kVA Top View Internal battery layout and connecting-GP12120 F2 12AH/12V Internal battery layout Split-Bypass Input Battery Temperature Compensation Static Transfer SwitchSocket Outlet Redundant Control Power Supply BoardMulti Module UPS-1+N Modes of Operation Maintenance Mode Manual Bypass Bypass ModeECO Mode Single UPS Only Parallel Redundancy Mode System ExpansionNormal Function Battery Management-Set During CommissioningBattery Protection settings by commissioning engineer UPS operating modes Power SwitchesRotary switch configurations UPS Startup Start-Up ProcedureIndicator State Verify Switching Between Operation Modes Powering Down the UPS Switching the UPS from Normal to Maintenance BypassPowering Down the UPS and Maintaining Power to Load Auto Restart Emergency Shutdown With EPOChanging the Current Date and Time Command PasswordLanguage Selection Isolating One Module in a Multi-Module System LED Function Status Inserting One Module into a Multi-Module SystemButton Function UPS control and display panel componentsComponent # Function Audible Alarm Buzzer Mimic Power FlowMenu key Icons and their meaning Direct Access Push Buttons KeysLCD Monitor and Menu keys Language Settings Command Version Load System Battery RecordsWhen configured, input transformer voltages are Displayed on the front LCD. When not activated,UPS system window Detailed Description of Menu ItemsDescriptions of UPS menus and data window items Menu Type Item Type ExplanationNumber to be dialed to send an alarm notification Message Description / Suggested Action if any UPS messagesBypass voltage exceeds the limit UPS is confirmed to overload and the overload times out UPS messages Prompt Pop-Up Windows Dynamic Energy Flow Chart and UPS Help ScreenPrompt windows, meanings Prompt MeaningDefault screen Default Screen SaverTerminal Name Definition Battery Ground Fault DetectionProtection Fan120 Redundant Fan for Power ModuleFan120 AC FanOC Web Card data summary window OC Web Card SNMP/HTTP Network Interface CardRelay Card Relay Card pin configurationMultiport-4 Card Relay card jumpersPin Description SiteNet MultiPort4 Intellislot pin assignmentAssignment OC485 Web Card Modbus, Jbus, IGM Net Remote Alarm MonitorDust Filter for 10-30kVA Dust filter replacementConformity and Standards Environmental characteristicsCompliance with European, international standards Overall efficiency, heat losses and air exchangeRectifier AC input mains Mechanical characteristicsInverter output to critical load Bypass mains input Technical Specifications Technical Specifications Page Iti Ne tTi n That