8.1.4Relay Card
The Relay card provides
Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS signals, the
The Relay card is rated for 24 VAC/VDC at 1A and supported in any of the three NX Intellislot bays.
Table 25 Relay Card pin configuration
Pin | Function | Operation |
1 | UPS Fault | Closed if no UPS failure |
|
|
|
Not Used |
| |
|
|
|
4 | UPS Fault | Closed if UPS fails |
|
|
|
5 | Summary Alarm** | Closed if SUMMARY ALARM** occurs |
|
|
|
6 | Summary Alarm** | Closed if no alarm conditions are present |
|
|
|
7 | Any Mode Shutdown return | Not Supported– use External EPO terminal |
|
|
|
8 | Not Used |
|
|
|
|
9 | Common - Low Battery |
|
|
|
|
10 | Low Battery | Closed if battery is OK |
|
|
|
11 | Low Battery | Closed if LOW BATTERY point occurs. |
|
|
|
Not Used |
| |
|
|
|
14 | UPS Any Mode Shutdown | Not supported– use External EPO terminal |
|
|
|
15 | On UPS | Closed if ON UPS (inverter) power |
|
|
|
16 | On Battery | Closed if ON BATTERY power (Utility failure) |
|
|
|
17 | Common - UPS Fault, Summary Alarm, |
|
| On UPS, On Battery, On Bypass |
|
18 | On Battery | Closed if not ON Battery power (Utility OK) |
|
|
|
19 ÷ 23 | Not Used |
|
|
|
|
24 | On Bypass | Closed if ON BYPASS |
|
|
|
25 | Not Used |
|
|
|
|
**A Summary Alarm occurs when any of the following conditions exist:
•Utility power is out of the acceptable range (voltage and/or frequency)
•UPS is in BYPASS MODE (load not on Inverter power)
•UPS Battery is LOW
•UPS fault has occurred
Table 26 Relay card jumpers
# | Connection | Description | |
JP01 | Pin 9 to Pin 17 | Allows all relay COMMONS to be tied together. | |
|
|
| |
JP02 | Pin 7 to Pin 17 | Irrelevant for NX - (Interconnects all relay COMMONS and the (not | |
supported) ANY MODE SHUTDOWN Return. | |||
|
|
8.1.5Multiport-4 Card
The
This card is supported in any of the three NX Intellislot bays.