Single Module UPS Installation
1.6.1Cable Termination
NOTE
The operations described in this section must be performed by authorised electricians or qualified technical personnel. If you have any difficulties, do not hesitate to contact our Customer Service and Support Department. See the back page of this manual for contact information.
Once the equipment has been finally positioned and secured, connect the power cables as described in the following procedure.
Refer to the appropriate cable connection drawing in 4.0 - Installation Drawings.
1.Verify that the UPS equipment is isolated from its external power source and all the UPS power isolators are open. Check that these supplies are electrically isolated and post any necessary warning signs to prevent their inadvertent operation.
2.Open the door to the UPS cabinet and remove the front protective cover to gain access to the connections bars.
3.Connect the safety earth and any necessary bonding earth cables to the copper earth busbar located on the floor of the equipment below the power connections. All cabinets in the UPS must be connected to the user’s ground connection.
NOTE
The earthing and neutral bonding arrangement must be in accordance with local and national codes of practice.
Identify and make power connections for incoming cables according to one of the two procedures below, depending on the type of installation.
Common Input Connections
4.For common bypass and rectifier inputs, connect the AC input supply cables between the mains distribution panel and the UPS input
Split-Bypass Connections
5.If a
NOTE
For
The AC input and the AC bypass supplies must be referenced to the same neutral point.
Frequency Converter Mode
If a frequency converter configuration is used, connect the AC input supply cables to the rectifier input busbars
NOTE
For frequency converter operation, ensure that the linking busbars between bypass and rectifier input are removed.
9