Operating Procedures
6.3Switching the UPS from Normal to Maintenance Bypass
Follow the procedure below to transfer the load from the inverter output to the Maintenance Bypass line of the UPS.
! CAUTION
Before performing this operation, read the messages on the LCD to be sure that bypass supply is regular and the inverter is synchronous with it. If those conditions are not present, there is a risk of a short interruption in powering the load.
This procedure assumes that UPS is operating normally.
1.Press the INVERTER OFF button on the right side of the operator control panel for longer than 2 seconds.
The Inverter indicator will turn off and the status indicator (6) will turn amber and an audible alarm will sound. The load will transfer to static bypass and the inverter will shut off.
NOTE
Pressing the Alarm Silence Switch cancels the audible alarm, but leaves the warning message displayed until the appropriate condition is rectified.
2.Open the UPS door to gain access to the main power switches, SW1 and CB1.
3.Turn the rotary switch to BYPASS position. The UPS Bypass Static Switch still supply power to load.
4.Turn the rotary switch to TEST. The load is now on maintenance bypass.
5.Turn the rotary switch to MAINT.
6.Open rectifier switch CB1. All operator indicators and messages will turn off as the utility driven internal power supplies decay. The unit will power down, but the load will continue to be supplied by the manual maintenance bypass.
! WARNING
Wait 5 minutes for the internal DC busbar capacitors to discharge before attempting to remove the internal protective barriers.
! WARNING
Even with the UPS rotary switch in maintenance bypass position portions of the unit are still energized. Service is to be performed by qualified personnel only.
! CAUTION
The load equipment is not protected from normal supply aberrations when operating in the maintenance bypass mode.
6.4Powering Down the UPS
To power down the UPS completely, follow the procedures in 6.3 - Switching the UPS from Nor- mal to Maintenance Bypass.
To completely isolate the UPS from the AC supplies, the main external power input isolator (both iso- lators, where separate supplies are provided for rectifier and bypass) should be opened (see Figure 30).
! WARNING
To prevent injury to personnel, lockout or tagout the service supplies.
48