Liebert NX UPS System user manual Battery Cabinet

Page 27

Battery Installation

2.3Battery Cabinet

2.3.1Introduction

This cabinet can also be used in conjunction additional cabinets, to provide the necessary accommoda- tion required by the larger cells associated with system’s having a long autonomy time.

Where two (or more) cabinets are used they are positioned alongside each other and secured and bonded together. If the cabinet(s) is located immediately adjacent to the main UPS equipment the two units are bolted together.

2.3.2Temperature Considerations

Valve-regulated, lead acid battery cells are sensitive to ambient temperature and should be operated between 15°C and 25°C (59-77°F). Battery capacity is increased by 1% for every 1°C (2°F) increase in temperature up to 25°C (77°F). Battery life is reduced at temperatures above 25°C (77°F).

When batteries are mounted in the same room as the UPS unit, it is the battery that dictates the designed maximum ambient temperature, not the UPS. — i.e. in the case of valve-regulated cells, the ambient room temperature should be kept between 15°C and 25°C (59-77°F), and not between 0°C and 40°C (32-104°F) (which is the specified main equipment operating temperature range). Tempera- ture deviations are permissible for short periods, provided the average temperature does not exceed 25°C (77°F).

2.3.3Dimensions

The external dimensions are shown in Table 8. These are the same height and depth as the UPS module and provide a matching appearance when bolted together. All cabinets are fitted with doors, which must be fully opened in order to fit or remove the batteries. The door swing must therefore be taken into consideration when planning the positioning of the cabinets.

2.3.4Weight

The unladen weight is shown below in Table 8. When designing the battery installation the weight of the batteries and cables must be added to the unladen weight. This is particularly important when placing the NX on a raised floor.

Table 8

Dimensions and weight

 

 

 

 

 

Optional

 

Maximum

 

Cabinet Weight

 

 

Circuit Breaker

 

Discharge Current

External Cabinet

Without Batteries

Model

 

Amperes

 

(at EOD)

WxDxH mm (in)

kg (lb)

 

 

 

 

10kVA 22A

 

 

Battery Cabinet

50A

 

15kVA 33A

820x700x1400

170 (375)

 

 

20kVA 44A

 

 

(32-1/4x27-5/8x55)

 

 

80A

 

30kVA 66A

 

 

 

 

 

 

 

 

 

2.3.5Circuit Isolator Features

The UPS is fitted with Anderson connectors and fuses for connection and disconnection of internal batteries. External battery banks require battery fuses or circuit breaker (with optional status con- tacts). Refer to 1.8.3 - External Circuit-Breaker Interface for details.

19

Image 27
Contents Liebert NX UPS Page Table of Contents Dual Bus System UPS MULTI-MODULEINSTALLATIONOperator Control Panel and Display Operating ProceduresOPTIONS-FORASSEMBLY Inside the UPS Cabinet Technical SpecificationsFigures Tables Options Model Identification Feature Set for Region InputOutput Aust/NZConformity and Standards Safety PrecautionsBattery Voltage Exceeds 400VDC User-Serviceable PartsPreliminary Checks IntroductionStorage External Battery RoomLocation UPS RoomMoving the Cabinets PositioningSystem Cabinets 2 10 to 30kVA UPSExternal Protective Devices External Battery Earth Leakage RCDUPS Output Power Cables Maximum steady state AC and DC currentsDistance from floor to connection point on the equipment Common Input Connections Cable TerminationOutput System Connections Control Cables and Communication Monitor Board FeaturesInput Dry Contacts X3 Ancillary Control and AlarmsMaintenance Bypass Cabinet Interface Dry ContactsJumper connection for BCB interface External Circuit-Breaker InterfaceJ28 Output Dry ContactsOutput dry contact relays +12V J13 J21X6 Analog Input Interface Emergency Power Off InputX5 Auxiliary DC Power Output X7 External Battery Temperature Detector InterfaceSerial Ports RS232-1 and RS232-2 External Bypass Switch InterlockBattery Start Facility Battery Start ButtonBattery Installation Hazardous battery voltage present behind covers SafetyBattery Cabinet Name W2 L=5m Name W1 L=30m Battery Temperature Sensor OptionalMoving the Battery Cabinets Cable W2 is packed with the temperature sensorGeneral Arrangement Drawings Battery cabinet bottom cable entry locationBottom cable entry Battery cabinet internal layout Battery Power Cables Connection PrinciplesItem # Item Name Fitting the Batteries Battery ControlConnecting the Battery Battery Room DesignX21 GeneralX23 X24 Monitor Board X24Cabinet Installation Paralleled UPS ModulesDistribution Cabinet External Protective Devices Power CablesControl Cables Intermodule Control Hot-Standby UPS ModulesInput Distribution Upstream Dual Bus System Parallel Board DBS Cable X2-2 X1-1 Parallel System Control WiresExtended Dual Bus Synchronization Option DBS Interface Box Parallel Board X2-2 X1-1 Parallel SystemInstallation Drawings General arrangement-10-30kVA UPS module External Battery Input Output Main Input Bypass Input NXe 10-30kVA Top View Internal battery layout and connecting-GP12120 F2 12AH/12V Internal battery layout Split-Bypass Input Battery Temperature Compensation Static Transfer SwitchRedundant Control Power Supply Board Multi Module UPS-1+NSocket Outlet Modes of Operation Parallel Redundancy Mode System Expansion Bypass ModeMaintenance Mode Manual Bypass ECO Mode Single UPS OnlyBattery Management-Set During Commissioning Battery Protection settings by commissioning engineerNormal Function Power Switches Rotary switch configurationsUPS operating modes Start-Up Procedure Indicator StateUPS Startup Verify Switching Between Operation Modes Powering Down the UPS Switching the UPS from Normal to Maintenance BypassPowering Down the UPS and Maintaining Power to Load Auto Restart Emergency Shutdown With EPOCommand Password Language SelectionChanging the Current Date and Time Isolating One Module in a Multi-Module System LED Function Status Inserting One Module into a Multi-Module SystemUPS control and display panel components Component # FunctionButton Function Audible Alarm Buzzer Mimic Power FlowDirect Access Push Buttons Keys LCD Monitor and Menu keysMenu key Icons and their meaning Displayed on the front LCD. When not activated, Load System Battery RecordsLanguage Settings Command Version When configured, input transformer voltages areMenu Type Item Type Explanation Detailed Description of Menu ItemsUPS system window Descriptions of UPS menus and data window itemsNumber to be dialed to send an alarm notification Message Description / Suggested Action if any UPS messagesBypass voltage exceeds the limit UPS is confirmed to overload and the overload times out UPS messages Prompt Meaning Dynamic Energy Flow Chart and UPS Help ScreenPrompt Pop-Up Windows Prompt windows, meaningsDefault screen Default Screen SaverBattery Ground Fault Detection ProtectionTerminal Name Definition AC Fan Redundant Fan for Power ModuleFan120 Fan120OC Web Card data summary window OC Web Card SNMP/HTTP Network Interface CardRelay card jumpers Relay Card pin configurationRelay Card Multiport-4 CardSiteNet MultiPort4 Intellislot pin assignment AssignmentPin Description OC485 Web Card Modbus, Jbus, IGM Net Remote Alarm MonitorDust Filter for 10-30kVA Dust filter replacementOverall efficiency, heat losses and air exchange Environmental characteristicsConformity and Standards Compliance with European, international standardsRectifier AC input mains Mechanical characteristicsInverter output to critical load Bypass mains input Technical Specifications Technical Specifications Page That Ne tIti Ti n