Operator Control Panel and Display
Table 21 Descriptions of UPS menus and data window items (continued)
Menu |
|
| |
Type | Item Type | Explanation | |
|
|
| |
| Sout (kVA) | Sout: Apparent power | |
|
|
| |
| Pout (kW) | Pout: Active power | |
System |
|
| |
Qout (kVAR) | Qout: Reactive power | ||
|
|
| |
| Single unit, no parallel data | When configured as a single unit, UPS has only native load, no system | |
|
| load. | |
| Battery voltage (V) | Battery bus voltage | |
|
|
| |
| Battery current (A) | Battery bus current | |
|
|
| |
| Battery temperature (°C) | Internal battery temperature °C | |
Battery |
|
| |
Remain Time Min. | Battery run time remaining | ||
|
|
| |
| Battery boost charging | Battery is boost charging | |
|
|
| |
| Battery float charging | Battery is float charging | |
|
|
| |
| Battery disconnected | Battery is not connected | |
|
|
| |
Records | (history log) | Displays all records in the history log | |
|
|
| |
Language | (choices for text displayed) | User may select any of 12 languages for LCD text. | |
|
|
| |
| Display contrast | Adjust the LCD display contrast | |
|
|
| |
| Date format set | Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D | |
|
|
| |
| Date & time | Set the date and time | |
|
|
| |
| Comm1 baud rate | Communication baud rate setting for Intellislot 1 | |
|
|
| |
| Comm2 baud rate | Communication baud rate setting for Intellislot 2 | |
|
|
| |
| Comm3 baud rate | Communication baud rate setting for Intellislot 3 | |
|
|
| |
| Communication address | This setting is applicable to RS485 communication mode | |
|
|
| |
Settings | Communication mode | Communication Mode Setting | |
|
| ||
| Callback times | When Intellislot 1 Communication mode is Modem, this parameter sets | |
| the number of times a number is redialed to send an alarm notification. | ||
|
| ||
| Phone No.1 | When Intellislot 1 Communication mode is Modem, this is the first phone | |
| number to be dialed (to send an alarm notification). | ||
|
| ||
| Phone No.2 | When Intellislot 1 Communication mode is Modem, this is the second | |
| phone number to be dialed (to send an alarm notification). | ||
|
| ||
| Phone No.3 | When Intellislot 1 Communication mode is Modem, this is the third phone | |
| number to be dialed (to send an alarm notification). | ||
|
| ||
| Command password | User can modify the command password. | |
| Battery maintenance test | This test performs a partial discharge of the battery to obtain a rough | |
| estimate of the battery capacity. Load must be between 20% and 100%. | ||
|
| ||
| Battery capacity test | This test performs a full discharge of the battery to obtain a precise | |
| measure of the battery capacity. Load must be between 20% and 100%. | ||
Command |
| ||
| This is a | ||
(start/stop | System test | ||
battery & |
| up window appears about 5 seconds later to show the results. | |
system | Stop testing | Manually stops a battery maintenance test, battery capacity test or system | |
tests) | test. | ||
|
|
| |
| Freshening Charge | This command will allow a temporary Equalize charge for the batteries. | |
| This charge is configurable for 1 to 36 hours | ||
|
| ||
| Stop Freshening Charge | Manually stop a Freshening Charge | |
|
|
| |
| UPS version | Provides UPS firmware version numbers for the inverter, rectifier and | |
Version | software display board. | ||
| |||
| UPS model | Provides UPS model | |
|
|
|
59