Operation
5.4Battery Management—Set During Commissioning
5.4.1Normal Function
•Constant charging
•Constant boost voltage boost (if
For Valve Regulated Lead Acid (VRLA) batteries, maximum boost charge voltage should not exceed 2.4V / cell.
•Float
•Float Charge Temperature Compensation
•End of discharge protection
•Battery Low Warning
5.4.2Advanced Functions (Software Settings Performed by the Commissioning Engineer) Battery
At periodic intervals 20% of the rated capacity of the battery will be discharged automatically. The minimum amount of load must exceed 20% of the nominal rating of the UPS module. If the load is less than 20%,
•
•
•Battery
5.5Battery Protection (settings by commissioning engineer)
Battery Undervoltage Pre-warning
The battery undervoltage
Battery End of Discharging (EOD) Protection
If the battery voltage is lower than the EOD, the battery converter will be shut down. EOD is settable from 1.6V to 1.75V per VRLA cell (or 1.0 to 1.1V per NiCd cell).
Battery Isolator Open Warning
If the battery isolator is open, this warning will occur.
The external battery to the UPS through an external battery isolator, which is manually closed and electronically tripped via the UPS control circuits.
44