Liebert NX UPS System user manual Battery Control, Fitting the Batteries, Connecting the Battery

Page 33

Battery Installation

2.4.2Fitting the Batteries

1.In general, at least 10mm (3/8") must be left unobstructed on all vertical sides of the battery blocks to permit free air movement around the cells.

2.Clearance should be allowed between the top of the cells and the underside of the shelf above (this is necessary for monitoring and servicing the cells).

3.When installing the batteries on racks always work from the bottom shelf upwards to prevent raising the centre of gravity.

2.4.3Connecting the Battery

1.When the battery cabinet is installed on a raised floor the battery power cables and optional circuit breaker control cables can be routed to the UPS cabinet via the floor of the cabinet. If the UPS and battery cabinet are located adjacent to each other and located on a solid floor these cables can be passed between the cabinets via the lifting apertures located in the lower sides of the cabinets.

2.In general it is recommended that the inter-connecting cables be fitted to the batteries within their particular level before fitting the inter-level connecting cables, followed finally by the cables to the circuit breaker.

3.An insulating shroud should be fitted to each terminal after its connection has been made.

4.When connecting the cables between the battery string ends to the optional circuit breaker always connect the circuit breaker end of the cable first.

2.4.4Battery Room Design

Whatever the type of mounting system selected, the following conditions should be noted:

Cell Layout—1

Whichever battery mounting system is used, the batteries should be arranged to prevent the pos- sibility of simultaneous contact with two exposed live parts having a potential greater an 150V. Where this is not possible, insulated terminal shields must be installed and insulated cables must be used for connections.

Service Platform—2

The service platform (or duckboard) must be slip-proof, insulated from the floor and at least one metre (39 in.) wide.

Connections—3

All connections must be as short as possible.

Battery Protection Fuses/Circuit Breaker4

The battery circuit breaker is generally installed at the front of the battery room. See 2.5 - Bat- tery Control for details on connecting the circuit breaker box available for the Liebert NX.

Figure 12 Battery room design

4

1

3

2

2.5Battery Control

Battery temperature sensor cables are connected between UPS auxiliary terminal block X3 BCB, the Battery Temperature sensor and the battery as shown in Figure 7.

Cables connected to X3 BCB must contain a protective earth wire or a shield, be segregated from power circuits, double insulated and of a typical 0.5 to 1mm2 cross section area for maximum runs between 25 and 50 meters respectively. The shield should be connected to the protective earth of the battery cabinet or battery breaker, not at the UPS

25

Image 33
Contents Liebert NX UPS Page Table of Contents Dual Bus System UPS MULTI-MODULEINSTALLATIONOPTIONS-FORASSEMBLY Inside the UPS Cabinet Operating ProceduresTechnical Specifications Operator Control Panel and DisplayFigures Tables Output Feature Set for Region InputAust/NZ Options Model IdentificationConformity and Standards Safety PrecautionsBattery Voltage Exceeds 400VDC User-Serviceable PartsPreliminary Checks IntroductionLocation External Battery RoomUPS Room StorageSystem Cabinets Positioning2 10 to 30kVA UPS Moving the CabinetsExternal Protective Devices External Battery Earth Leakage RCDUPS Output Power Cables Maximum steady state AC and DC currentsDistance from floor to connection point on the equipment Common Input Connections Cable TerminationOutput System Connections Control Cables and Communication Monitor Board FeaturesMaintenance Bypass Cabinet Interface X3 Ancillary Control and AlarmsDry Contacts Input Dry ContactsJumper connection for BCB interface External Circuit-Breaker InterfaceOutput dry contact relays Output Dry Contacts+12V J13 J21 J28X5 Auxiliary DC Power Output Emergency Power Off InputX7 External Battery Temperature Detector Interface X6 Analog Input InterfaceBattery Start Facility External Bypass Switch InterlockBattery Start Button Serial Ports RS232-1 and RS232-2Battery Installation Hazardous battery voltage present behind covers SafetyBattery Cabinet Moving the Battery Cabinets Battery Temperature Sensor OptionalCable W2 is packed with the temperature sensor Name W2 L=5m Name W1 L=30mGeneral Arrangement Drawings Battery cabinet bottom cable entry locationBottom cable entry Battery cabinet internal layout Battery Power Cables Connection PrinciplesItem # Item Name Connecting the Battery Battery ControlBattery Room Design Fitting the BatteriesX23 X24 Monitor Board GeneralX24 X21Cabinet Installation Paralleled UPS ModulesDistribution Cabinet External Protective Devices Power CablesControl Cables Intermodule Control Hot-Standby UPS ModulesInput Distribution Upstream Dual Bus System Extended Dual Bus Synchronization Option DBS Interface Box Control WiresParallel Board X2-2 X1-1 Parallel System Parallel Board DBS Cable X2-2 X1-1 Parallel SystemInstallation Drawings General arrangement-10-30kVA UPS module External Battery Input Output Main Input Bypass Input NXe 10-30kVA Top View Internal battery layout and connecting-GP12120 F2 12AH/12V Internal battery layout Split-Bypass Input Battery Temperature Compensation Static Transfer SwitchRedundant Control Power Supply Board Multi Module UPS-1+NSocket Outlet Modes of Operation Maintenance Mode Manual Bypass Bypass ModeECO Mode Single UPS Only Parallel Redundancy Mode System ExpansionBattery Management-Set During Commissioning Battery Protection settings by commissioning engineerNormal Function Power Switches Rotary switch configurationsUPS operating modes Start-Up Procedure Indicator StateUPS Startup Verify Switching Between Operation Modes Powering Down the UPS Switching the UPS from Normal to Maintenance BypassPowering Down the UPS and Maintaining Power to Load Auto Restart Emergency Shutdown With EPOCommand Password Language SelectionChanging the Current Date and Time Isolating One Module in a Multi-Module System LED Function Status Inserting One Module into a Multi-Module SystemUPS control and display panel components Component # FunctionButton Function Audible Alarm Buzzer Mimic Power FlowDirect Access Push Buttons Keys LCD Monitor and Menu keysMenu key Icons and their meaning Language Settings Command Version Load System Battery RecordsWhen configured, input transformer voltages are Displayed on the front LCD. When not activated,UPS system window Detailed Description of Menu ItemsDescriptions of UPS menus and data window items Menu Type Item Type ExplanationNumber to be dialed to send an alarm notification Message Description / Suggested Action if any UPS messagesBypass voltage exceeds the limit UPS is confirmed to overload and the overload times out UPS messages Prompt Pop-Up Windows Dynamic Energy Flow Chart and UPS Help ScreenPrompt windows, meanings Prompt MeaningDefault screen Default Screen SaverBattery Ground Fault Detection ProtectionTerminal Name Definition Fan120 Redundant Fan for Power ModuleFan120 AC FanOC Web Card data summary window OC Web Card SNMP/HTTP Network Interface CardRelay Card Relay Card pin configurationMultiport-4 Card Relay card jumpersSiteNet MultiPort4 Intellislot pin assignment AssignmentPin Description OC485 Web Card Modbus, Jbus, IGM Net Remote Alarm MonitorDust Filter for 10-30kVA Dust filter replacementConformity and Standards Environmental characteristicsCompliance with European, international standards Overall efficiency, heat losses and air exchangeRectifier AC input mains Mechanical characteristicsInverter output to critical load Bypass mains input Technical Specifications Technical Specifications Page Iti Ne tTi n That