Liebert NX UPS System user manual UPS is confirmed to overload and the overload times out

Page 70

Operator Control Panel and Display

Table 22

UPS messages (continued)

 

 

 

Message

 

Description / Suggested Action (if any)

 

 

The UPS is confirmed to overload and the overload times out.

 

 

Note 1: the highest loaded phase will indicate overload timing-out first.

 

 

Note 2: When the timer is active then alarm “unit overload” should also be active as the load is

 

 

above nominal.

 

 

Note 3: When the timer has expired, the inverter Static Switch is opened and the load

Unit Over load Timeout

transferred to bypass. The inverter shutdown and will restart after 10 seconds.

 

 

Note 4: If the load decreases lower than 95% after 5 minutes, the system will transfer back to

 

 

inverter mode.

 

 

Confirm that the alarm is genuine by checking the load percent indicated on the LCD. If an

 

 

overload is indicated then check the load, and investigate any additional load connected prior to

 

 

the alarm (if applicable).

Byp. Abnormal Shutdown

Both bypass and inverter voltages unavailable. Load interruption

 

 

Inverter Over Current

Inverter Pulse Width Modulation module overloaded.

 

 

 

 

 

The phase sequence direction of bypass voltage is reversed.

 

 

Normally, the phase of phase B lags 120 degrees behind phase A, and the phase of phase C

Bypass Phase Reversed

lags 120 degrees behind phase B.

 

 

Verify that the phase rotation of the bypass supply presented to the UPS is correct, and rectify it

 

 

if it is found to be in error

Load Impact Transfer

A transfer to bypass occurred due to a large step load. The UPS should recover automatically.

Turn on connected equipment in sequential order to reduce the step loading of the inverter.

 

 

 

 

The load is on bypass power due to excessive number of transfers that occurred within the last

Transfer Time-out

hour.

The UPS will recover automatically and will transfer the load back to inverter power within an

 

 

 

 

hour.

 

 

Load Sharing Fault

UPS modules within a parallel system are not sharing the load current equally.

 

 

DC Bus Abnormal

DC input voltage to inverter beyond limits. Inverter shuts down. Load transfers to bypass.

 

 

 

System Transfer

The whole paralleled UPS system transferred to bypass at the same time. This message will

appear on the UPS which passive transfer to bypass

 

 

Parallel Board Fault

Malfunction of the paralleling control circuits of this UPS module. Can cause “System Transfer”

to bypass.

 

 

 

 

Rectifier, inverter and battery converter were shutdown because DC bus voltage is too high.

DC Bus Over Voltage

Check whether there is a fault in rectifier side. If no, then check whether overload occurs.

 

 

Restart the inverter after resetting the fault

 

 

The parallel cables are not connected correctly in a parallel system.

Parallel Connect Fault

Reset the fault by pressing the “fault clear” button, then restart the inverter by pressing the

 

 

“inverter on” button.

Bypass Over Current

Bypass current is over limit above 135% rating. The UPS just alarms and does nothing.

 

 

 

LBS Active

 

Load Bus Synchronisation is active. The UPS is acting as an LBS master or slave in a dual bus

 

configuration.

 

 

Setting Save Error

History records not saved. (Reserved)

 

 

Mains Neutral Lost

AC Input mains reference neutral not detected.

 

 

Protocol version clash

Firmware incompatibility between Monitor Board and Digital Signal Processor Board.

 

 

Battery ground fault

Battery leakage to ground detected (option)

 

 

Inv. Turned On Manually

Manual Turn On via front panel

 

 

Inv. Turned Off Manually

Manual Turn Off via front panel

 

 

 

EPO

 

Emergency Power Off direct access key pressed or external command received

 

 

 

Transfer Confirm

Prompt to press “enter” key to acknowledge that an interrupted load transfer to bypass will

happen.

 

 

Transfer Cancel

Prompt to press “ESC” key to avoid that an interrupted load transfer to bypass will happen.

 

 

 

Unit Off Confirm

Prompt to press “enter” key to acknowledge that the UPS will be disconnected from other

paralleled UPS modules.

 

 

System Off Confirm

Prompt to press “enter” key to acknowledge that the all paralleled UPS will be disconnected

from the load.

 

 

62

Image 70
Contents Liebert NX UPS Page Table of Contents UPS MULTI-MODULEINSTALLATION Dual Bus SystemTechnical Specifications Operating ProceduresOPTIONS-FORASSEMBLY Inside the UPS Cabinet Operator Control Panel and DisplayFigures Tables Aust/NZ Feature Set for Region InputOutput Options Model IdentificationSafety Precautions Conformity and StandardsUser-Serviceable Parts Battery Voltage Exceeds 400VDCIntroduction Preliminary ChecksUPS Room External Battery RoomLocation Storage2 10 to 30kVA UPS PositioningSystem Cabinets Moving the CabinetsExternal Protective Devices Earth Leakage RCD External BatteryUPS Output Maximum steady state AC and DC currents Power CablesDistance from floor to connection point on the equipment Cable Termination Common Input ConnectionsOutput System Connections Monitor Board Features Control Cables and CommunicationDry Contacts X3 Ancillary Control and AlarmsMaintenance Bypass Cabinet Interface Input Dry ContactsExternal Circuit-Breaker Interface Jumper connection for BCB interface+12V J13 J21 Output Dry ContactsOutput dry contact relays J28X7 External Battery Temperature Detector Interface Emergency Power Off InputX5 Auxiliary DC Power Output X6 Analog Input InterfaceBattery Start Button External Bypass Switch InterlockBattery Start Facility Serial Ports RS232-1 and RS232-2Battery Installation Safety Hazardous battery voltage present behind coversBattery Cabinet Cable W2 is packed with the temperature sensor Battery Temperature Sensor OptionalMoving the Battery Cabinets Name W2 L=5m Name W1 L=30mBattery cabinet bottom cable entry location General Arrangement DrawingsBottom cable entry Battery cabinet internal layout Connection Principles Battery Power CablesItem # Item Name Battery Room Design Battery ControlConnecting the Battery Fitting the BatteriesX24 GeneralX23 X24 Monitor Board X21Paralleled UPS Modules Cabinet InstallationDistribution Cabinet Power Cables External Protective DevicesHot-Standby UPS Modules Control Cables Intermodule ControlInput Distribution Upstream Dual Bus System Parallel Board X2-2 X1-1 Parallel System Control WiresExtended Dual Bus Synchronization Option DBS Interface Box Parallel Board DBS Cable X2-2 X1-1 Parallel SystemInstallation Drawings General arrangement-10-30kVA UPS module External Battery Input Output Main Input Bypass Input NXe 10-30kVA Top View Internal battery layout and connecting-GP12120 F2 12AH/12V Internal battery layout Split-Bypass Input Static Transfer Switch Battery Temperature CompensationMulti Module UPS-1+N Redundant Control Power Supply BoardSocket Outlet Modes of Operation ECO Mode Single UPS Only Bypass ModeMaintenance Mode Manual Bypass Parallel Redundancy Mode System ExpansionBattery Protection settings by commissioning engineer Battery Management-Set During CommissioningNormal Function Rotary switch configurations Power SwitchesUPS operating modes Indicator State Start-Up ProcedureUPS Startup Verify Switching Between Operation Modes Switching the UPS from Normal to Maintenance Bypass Powering Down the UPSPowering Down the UPS and Maintaining Power to Load Emergency Shutdown With EPO Auto RestartLanguage Selection Command PasswordChanging the Current Date and Time Isolating One Module in a Multi-Module System Inserting One Module into a Multi-Module System LED Function StatusComponent # Function UPS control and display panel componentsButton Function Mimic Power Flow Audible Alarm BuzzerLCD Monitor and Menu keys Direct Access Push Buttons KeysMenu key Icons and their meaning When configured, input transformer voltages are Load System Battery RecordsLanguage Settings Command Version Displayed on the front LCD. When not activated,Descriptions of UPS menus and data window items Detailed Description of Menu ItemsUPS system window Menu Type Item Type Explanation Number to be dialed to send an alarm notification UPS messages Message Description / Suggested Action if anyBypass voltage exceeds the limit UPS is confirmed to overload and the overload times out UPS messages Prompt windows, meanings Dynamic Energy Flow Chart and UPS Help ScreenPrompt Pop-Up Windows Prompt MeaningDefault Screen Saver Default screenProtection Battery Ground Fault DetectionTerminal Name Definition Fan120 Redundant Fan for Power ModuleFan120 AC FanOC Web Card SNMP/HTTP Network Interface Card OC Web Card data summary windowMultiport-4 Card Relay Card pin configurationRelay Card Relay card jumpersAssignment SiteNet MultiPort4 Intellislot pin assignmentPin Description Remote Alarm Monitor OC485 Web Card Modbus, Jbus, IGM NetDust filter replacement Dust Filter for 10-30kVACompliance with European, international standards Environmental characteristicsConformity and Standards Overall efficiency, heat losses and air exchangeMechanical characteristics Rectifier AC input mainsInverter output to critical load Bypass mains input Technical Specifications Technical Specifications Page Ti n Ne tIti That