Technical Specifications
Table 36 Bypass mains input
Rated power, kVA | Unit of | 10 |
| 15 |
| 20 |
| 30 | |
Measurement |
|
|
| ||||||
|
|
|
|
|
|
|
| ||
Rated AC Voltage 1 |
|
|
|
| 380/400/415 V |
| |||
VAC | |||||||||
|
|
| and providing neutral reference to the output |
| |||||
Rated Current |
|
|
|
|
|
|
|
| |
380V | A | 15 |
| 23 |
| 30 |
| 45 | |
400V | A | 15 |
| 22 |
| 29 |
| 43 | |
415V | A | 14 |
| 21 |
| 28 |
| 42 | |
|
|
|
| 135% long term |
| ||||
Overload Capacity | % |
|
|
| 170% 10 min |
| |||
|
|
|
|
| 1000% 100 ms |
| |||
Upstream Protection, | N/A |
| Thermomagnetic circuit breaker, rated up to 125% |
| |||||
Bypass Line (by others) |
| of nominal output current. IEC |
| ||||||
|
|
| |||||||
Current Rating of Neutral Cable | A |
|
|
| 1.7 x In |
| |||
Frequency 2 | Hz |
|
|
| 50 / 60 |
|
| ||
Transfer Time (between |
|
|
| Synchronous transfer: ≤1ms |
| ||||
ms | Asynchronous transfer (default): 15 ms (50 Hz), 13.3 ms (60 Hz) | ||||||||
bypass and inverter) | |||||||||
|
|
| or 40, 60, 80, 100 ms, selectable |
| |||||
|
|
|
|
| |||||
|
|
| Upper limit: +10, +15 or +20, default +15 |
| |||||
Bypass Voltage Tolerance | % VAC |
| Lower limit |
| |||||
|
| (delay time to accept steady bypass voltage: 10 sec) | |||||||
Bypass Frequency Tolerance | % |
|
| ± 2.5 ± 5 ± 10 or ± 20 default ±10 |
| ||||
Synchronisation - Window | Hz |
| Rated frequency ±2Hz (selectable ± 0.5 to ±3Hz) |
|
1.Factory set to 400V – 380 or 415V selectable by commissioning engineer.
2.Factory set to 50Hz; 60 Hz selectable by commissioning engineer. Bypass condition ignored when UPS set as frequency converter.
76