Operator Control Panel and Display

7.3Prompt (Pop-Up) Windows

The prompt window is displayed during the operation of the system to alert the user to certain condi- tions and / or to require user confirmation of a command.

Table 23 Prompt windows, meanings

Prompt

Meaning

 

Inverter and Bypass supplies are not synchronised and

Transfer with interrupt, please confirm or cancel

any load transfer between the supplies will cause a brief

 

load interruption.

 

The total load must be less than the capacity of one unit

The load is too high to be transferred with interrupt

to allow a parallel system to perform an interrupted

 

transfer from bypass to inverter.

This Operation Leads to Output Shutdown, Confirm or

No alternative supply is available and any Inverter Off

Cancel

operation will cause the load to be de-energised.

This operation leads to inverter overload, confirm or

The turn-off this inverter will lead to the overload of

cancel

remaining inverter(s) in a parallel system.

Turn on more UPS to carry current load

The number of paralleled inverters already turned on is

insufficient to carry the existing load.

 

Battery will be depleted, confirm

Battery Capacity test discharges the battery 100%

 

 

System self test finished - everything is ok.

No action required

 

 

System self test finished - Please check the current

Check “Current Records” window

warnings.

 

Enter control password

Required for Battery or UPS test (default = 12345)

 

 

 

Battery self-test condition is not enough. User should

Battery Self Test aborted, condition not met

check whether battery state is boost charging and

 

whether load level is greater than 20 percent.

Battery Refresh Charge aborted, condition not met

Boost charging condition is not enough, such as (No

battery, charger has failed, etc.).

 

7.4Dynamic Energy Flow Chart and UPS Help Screen

This screen displays a mimic diagram of the UPS that includes energy flow and status of isolation and transfer switches. Press the “Help” key to activate this screen. Press again to toggle between this screen and the main screen.

Figure 34 Help screen

 

 

Help information

 

 

 

Select the current record window

 

 

Select the previous menu item

 

Press help key back to main menu

 

F1

F2

F3

F4

HELP

 

 

64

 

 

Image 72
Contents Liebert NX UPS Page Table of Contents UPS MULTI-MODULEINSTALLATION Dual Bus SystemOperating Procedures OPTIONS-FORASSEMBLY Inside the UPS CabinetTechnical Specifications Operator Control Panel and DisplayFigures Tables Feature Set for Region Input OutputAust/NZ Options Model IdentificationSafety Precautions Conformity and StandardsUser-Serviceable Parts Battery Voltage Exceeds 400VDCIntroduction Preliminary ChecksExternal Battery Room LocationUPS Room StoragePositioning System Cabinets2 10 to 30kVA UPS Moving the CabinetsExternal Protective Devices External Battery Earth Leakage RCDUPS Output Power Cables Maximum steady state AC and DC currentsDistance from floor to connection point on the equipment Cable Termination Common Input ConnectionsOutput System Connections Monitor Board Features Control Cables and CommunicationX3 Ancillary Control and Alarms Maintenance Bypass Cabinet InterfaceDry Contacts Input Dry ContactsExternal Circuit-Breaker Interface Jumper connection for BCB interfaceOutput Dry Contacts Output dry contact relays+12V J13 J21 J28Emergency Power Off Input X5 Auxiliary DC Power OutputX7 External Battery Temperature Detector Interface X6 Analog Input InterfaceExternal Bypass Switch Interlock Battery Start FacilityBattery Start Button Serial Ports RS232-1 and RS232-2Battery Installation Safety Hazardous battery voltage present behind coversBattery Cabinet Battery Temperature Sensor Optional Moving the Battery CabinetsCable W2 is packed with the temperature sensor Name W2 L=5m Name W1 L=30mBattery cabinet bottom cable entry location General Arrangement DrawingsBottom cable entry Battery cabinet internal layout Battery Power Cables Connection PrinciplesItem # Item Name Battery Control Connecting the BatteryBattery Room Design Fitting the BatteriesGeneral X23 X24 Monitor BoardX24 X21Cabinet Installation Paralleled UPS ModulesDistribution Cabinet Power Cables External Protective DevicesHot-Standby UPS Modules Control Cables Intermodule ControlInput Distribution Upstream Dual Bus System Control Wires Extended Dual Bus Synchronization Option DBS Interface BoxParallel Board X2-2 X1-1 Parallel System Parallel Board DBS Cable X2-2 X1-1 Parallel SystemInstallation Drawings General arrangement-10-30kVA UPS module External Battery Input Output Main Input Bypass Input NXe 10-30kVA Top View Internal battery layout and connecting-GP12120 F2 12AH/12V Internal battery layout Split-Bypass Input Static Transfer Switch Battery Temperature CompensationRedundant Control Power Supply Board Multi Module UPS-1+NSocket Outlet Modes of Operation Bypass Mode Maintenance Mode Manual BypassECO Mode Single UPS Only Parallel Redundancy Mode System ExpansionBattery Management-Set During Commissioning Battery Protection settings by commissioning engineerNormal Function Power Switches Rotary switch configurationsUPS operating modes Start-Up Procedure Indicator StateUPS Startup Verify Switching Between Operation Modes Switching the UPS from Normal to Maintenance Bypass Powering Down the UPSPowering Down the UPS and Maintaining Power to Load Emergency Shutdown With EPO Auto RestartCommand Password Language SelectionChanging the Current Date and Time Isolating One Module in a Multi-Module System Inserting One Module into a Multi-Module System LED Function StatusUPS control and display panel components Component # FunctionButton Function Mimic Power Flow Audible Alarm BuzzerDirect Access Push Buttons Keys LCD Monitor and Menu keysMenu key Icons and their meaning Load System Battery Records Language Settings Command VersionWhen configured, input transformer voltages are Displayed on the front LCD. When not activated,Detailed Description of Menu Items UPS system windowDescriptions of UPS menus and data window items Menu Type Item Type ExplanationNumber to be dialed to send an alarm notification UPS messages Message Description / Suggested Action if anyBypass voltage exceeds the limit UPS is confirmed to overload and the overload times out UPS messages Dynamic Energy Flow Chart and UPS Help Screen Prompt Pop-Up WindowsPrompt windows, meanings Prompt MeaningDefault Screen Saver Default screenBattery Ground Fault Detection ProtectionTerminal Name Definition Redundant Fan for Power Module Fan120Fan120 AC FanOC Web Card SNMP/HTTP Network Interface Card OC Web Card data summary windowRelay Card pin configuration Relay CardMultiport-4 Card Relay card jumpersSiteNet MultiPort4 Intellislot pin assignment AssignmentPin Description Remote Alarm Monitor OC485 Web Card Modbus, Jbus, IGM NetDust filter replacement Dust Filter for 10-30kVAEnvironmental characteristics Conformity and StandardsCompliance with European, international standards Overall efficiency, heat losses and air exchangeMechanical characteristics Rectifier AC input mainsInverter output to critical load Bypass mains input Technical Specifications Technical Specifications Page Ne t ItiTi n That