Liebert NX UPS System user manual Bypass voltage exceeds the limit

Page 69

Operator Control Panel and Display

Table 22

UPS messages (continued)

 

 

 

Message

 

Description / Suggested Action (if any)

 

 

This alarm is triggered by an inverter software routine when the amplitude or frequency of

 

 

bypass voltage exceeds the limit.

 

 

This alarm automatically resets once the bypass voltage goes normal.

 

 

First check if there are some relevant alarms such as “Bypass disconnect open”, “Bypass phase

 

 

reverse” and “Mains neutral lost”. If they appear, solve them first.

Bypass Abnormal

1. Then verify that the bypass voltage and frequency displayed on the panel is within the bypass

limit. Note here the rated voltage and frequency are specified by “Output voltage level” and

 

 

 

 

“Output frequency level” respectively.

 

 

2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and

 

 

frequency presented to the UPS. Check the external bypass supply if it is found to be faulty. If

 

 

the utility is likely to trigger this alarm frequently, the bypass limit can be changed a little larger

 

 

through the configuration software according to the customer’s agreement.

 

 

This alarm is triggered by an inverter software routine when the inverter and bypass waveforms

 

 

are misaligned by more than 6 degrees in phase. This alarm resets automatically once the

 

 

condition is no longer true.

Inverter Asynchronous

1. First check if the alarm “Bypass unable to trace” or “Bypass abnormal” occurs. If so, solve it

 

 

first.

 

 

2. Verify the waveform of the bypass voltage. If it is too distorted, ask the customer to verify and

 

 

seek any possible measurements.

Inverter Fault

Inverter output voltage beyond limits. Load transfers to bypass.

 

 

 

 

 

The temperature of the inverter heat sink is too high to keep inverter running.

 

 

This alarm is triggered by the signal from a temperature monitoring thermostat on the inverter

 

 

bridge heat sink.

 

 

The UPS will recover automatically after a 5 minute delay from the disappearance of the

Inverter Overtemp.

overtemperature signal.

If the overtemperature condition is true, then check for and verify:

 

 

 

 

1. high ambient air temperature.

 

 

2. blocked cooling airway.

 

 

3. any fan failure.

 

 

4. prolonged inverter overload

Fan Fault

 

At least one of the cooling fans has failed

 

 

 

Inverter STS Fail

At least one of the static switches of inverter side is open or short circuit. This fault is locked until

power off.

 

 

Bypass STS Fail

At least one of the static switches of bypass side is open or short circuit. This fault is locked until

power off

 

 

Operation Invalid

This record is registered following an incorrect operation:

 

 

Output Fuse Fail

At least one of the inverter output fuses is blown. Inverter shuts down. Load transfers to bypass.

 

 

Control Power 2 Fail

UPS operates but Redundant Control Power is not available.

 

 

 

 

 

The UPS is confirmed to be overload when the load arises above 105% nominal rating.

 

 

The alarm automatically resets once the overload condition is removed.

 

 

1. Confirm that the alarm is true by checking the load percent indicated on the LCD panel to

Unit Over load

determine which phase is being overloaded.

 

 

2. If the alarm is true, measure the actual output current to verify that the indications are valid.

 

 

Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load sharing

 

 

error can also leads to the alarm.

 

 

The UPS parallel system is confirmed to overload when the total load arises above 105%

 

 

nominal rating for the set basic number of UPSs. The alarm automatically resets once the

 

 

overload condition is removed.

System Over load

1. Confirm that the alarm is true by checking the system load percent indicated on the LCD

panel to determine which phase is being overloaded.

 

 

 

 

2. If the alarm is true, measure the actual output current to verify that the indications are valid.

 

 

Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load sharing

 

 

error can also leads to the alarm.

61

Image 69
Contents Liebert NX UPS Page Table of Contents Dual Bus System UPS MULTI-MODULEINSTALLATIONOPTIONS-FORASSEMBLY Inside the UPS Cabinet Operating ProceduresTechnical Specifications Operator Control Panel and DisplayFigures Tables Output Feature Set for Region InputAust/NZ Options Model IdentificationConformity and Standards Safety PrecautionsBattery Voltage Exceeds 400VDC User-Serviceable PartsPreliminary Checks IntroductionLocation External Battery RoomUPS Room StorageSystem Cabinets Positioning2 10 to 30kVA UPS Moving the CabinetsExternal Protective Devices External Battery Earth Leakage RCDUPS Output Power Cables Maximum steady state AC and DC currentsDistance from floor to connection point on the equipment Common Input Connections Cable TerminationOutput System Connections Control Cables and Communication Monitor Board FeaturesMaintenance Bypass Cabinet Interface X3 Ancillary Control and AlarmsDry Contacts Input Dry ContactsJumper connection for BCB interface External Circuit-Breaker InterfaceOutput dry contact relays Output Dry Contacts+12V J13 J21 J28X5 Auxiliary DC Power Output Emergency Power Off InputX7 External Battery Temperature Detector Interface X6 Analog Input InterfaceBattery Start Facility External Bypass Switch InterlockBattery Start Button Serial Ports RS232-1 and RS232-2Battery Installation Hazardous battery voltage present behind covers SafetyBattery Cabinet Moving the Battery Cabinets Battery Temperature Sensor OptionalCable W2 is packed with the temperature sensor Name W2 L=5m Name W1 L=30mGeneral Arrangement Drawings Battery cabinet bottom cable entry locationBottom cable entry Battery cabinet internal layout Battery Power Cables Connection PrinciplesItem # Item Name Connecting the Battery Battery ControlBattery Room Design Fitting the BatteriesX23 X24 Monitor Board GeneralX24 X21Cabinet Installation Paralleled UPS ModulesDistribution Cabinet External Protective Devices Power CablesControl Cables Intermodule Control Hot-Standby UPS ModulesInput Distribution Upstream Dual Bus System Extended Dual Bus Synchronization Option DBS Interface Box Control WiresParallel Board X2-2 X1-1 Parallel System Parallel Board DBS Cable X2-2 X1-1 Parallel SystemInstallation Drawings General arrangement-10-30kVA UPS module External Battery Input Output Main Input Bypass Input NXe 10-30kVA Top View Internal battery layout and connecting-GP12120 F2 12AH/12V Internal battery layout Split-Bypass Input Battery Temperature Compensation Static Transfer SwitchRedundant Control Power Supply Board Multi Module UPS-1+NSocket Outlet Modes of Operation Maintenance Mode Manual Bypass Bypass ModeECO Mode Single UPS Only Parallel Redundancy Mode System ExpansionBattery Management-Set During Commissioning Battery Protection settings by commissioning engineerNormal Function Power Switches Rotary switch configurationsUPS operating modes Start-Up Procedure Indicator StateUPS Startup Verify Switching Between Operation Modes Powering Down the UPS Switching the UPS from Normal to Maintenance BypassPowering Down the UPS and Maintaining Power to Load Auto Restart Emergency Shutdown With EPOCommand Password Language SelectionChanging the Current Date and Time Isolating One Module in a Multi-Module System LED Function Status Inserting One Module into a Multi-Module SystemUPS control and display panel components Component # FunctionButton Function Audible Alarm Buzzer Mimic Power FlowDirect Access Push Buttons Keys LCD Monitor and Menu keysMenu key Icons and their meaning Language Settings Command Version Load System Battery RecordsWhen configured, input transformer voltages are Displayed on the front LCD. When not activated,UPS system window Detailed Description of Menu ItemsDescriptions of UPS menus and data window items Menu Type Item Type ExplanationNumber to be dialed to send an alarm notification Message Description / Suggested Action if any UPS messagesBypass voltage exceeds the limit UPS is confirmed to overload and the overload times out UPS messages Prompt Pop-Up Windows Dynamic Energy Flow Chart and UPS Help ScreenPrompt windows, meanings Prompt MeaningDefault screen Default Screen SaverBattery Ground Fault Detection ProtectionTerminal Name Definition Fan120 Redundant Fan for Power ModuleFan120 AC FanOC Web Card data summary window OC Web Card SNMP/HTTP Network Interface CardRelay Card Relay Card pin configurationMultiport-4 Card Relay card jumpersSiteNet MultiPort4 Intellislot pin assignment AssignmentPin Description OC485 Web Card Modbus, Jbus, IGM Net Remote Alarm MonitorDust Filter for 10-30kVA Dust filter replacementConformity and Standards Environmental characteristicsCompliance with European, international standards Overall efficiency, heat losses and air exchangeRectifier AC input mains Mechanical characteristicsInverter output to critical load Bypass mains input Technical Specifications Technical Specifications Page Iti Ne tTi n That