Liebert NX UPS System user manual Emergency Power Off Input, X5 Auxiliary DC Power Output

Page 23

Single Module UPS Installation

1.8.5Emergency Power Off Input

The UPS has an Emergency Power Off (EPO) function that operates by a button on the control panel or by a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.

The X2 slot, shown in Figure 5, is the remote EPO input interface. The EPO has an NO/NC contact point that becomes active when shorting terminals X2: 3 and 4 or open terminal connection X2: 2 and 1

If an external emergency stop facility is required, it is connected terminals X2: 1&2 or X2: 3&4 of the auxiliary terminal block (X2). It also is connected to the normally open or normally closed remote stop switch between these two terminals using shielded cable (see Figure 5 and Table 7). If this function is not used, terminals X2: 3&4 must be opened and X2: 1&2 must be closed.

Table 7 EPO input contact relays

Position

Name

Description

J28.1

EPO_NC

EPO activated when opened to J28.2

 

 

 

J28.2

EPO_NC

EPO activated when opened to J28.1

 

 

 

J28.3

EPO_NO

EPO activated when shorted to J28.4

 

 

 

J28.4

EPO_NO

EPO activated when shorted to J28.3

 

 

 

NOTE

The emergency stop action within the UPS shuts down the rectifier, inverter and static bypass. It does not internally disconnect the input power supply. To disconnect ALL power to the UPS, open the upstream feeder breaker(s) when the remote EPO is activated.

NOTE

Normally closed EPO – X2: 1,2, these terminals are supplied factory-linked on the monitor board and must remain installed if using NC contacts.

NOTE

All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm2

(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.

X5: Auxiliary DC Power Output

Auxiliary DC power for modem or external SNMP card. The voltage is between 9V to 12V. The maxi- mum current is 500mA.

X6: Analog Input Interface

Two analog signal channels with an input range is from 0 to +12V. The precision of detection is ÷3%.

X6 pin 1: Not used

X6 pin 2: +12V

X6 pin 3: ENV-T – environment temperature detection

X6 pin 4: GND

X7: External Battery Temperature Detector Interface

Interface for TMP12Z temperature detector, normally connected to an external battery cabinet (see Figure 7).

Pin reference:

X7 pin 1: Not used

X7 pin 2: +12V (Power supply for Temperature Monitoring Probe)

X7 pin 3: BAT-T (Battery Temperature signal)

X7 pin 4: GND

15

Image 23
Contents Liebert NX UPS Page Table of Contents Dual Bus System UPS MULTI-MODULEINSTALLATIONOperator Control Panel and Display Operating ProceduresOPTIONS-FORASSEMBLY Inside the UPS Cabinet Technical SpecificationsFigures Tables Options Model Identification Feature Set for Region InputOutput Aust/NZConformity and Standards Safety PrecautionsBattery Voltage Exceeds 400VDC User-Serviceable PartsPreliminary Checks IntroductionStorage External Battery RoomLocation UPS RoomMoving the Cabinets PositioningSystem Cabinets 2 10 to 30kVA UPSExternal Protective Devices UPS Output External BatteryEarth Leakage RCD Distance from floor to connection point on the equipment Power CablesMaximum steady state AC and DC currents Common Input Connections Cable TerminationOutput System Connections Control Cables and Communication Monitor Board FeaturesInput Dry Contacts X3 Ancillary Control and AlarmsMaintenance Bypass Cabinet Interface Dry ContactsJumper connection for BCB interface External Circuit-Breaker InterfaceJ28 Output Dry ContactsOutput dry contact relays +12V J13 J21X6 Analog Input Interface Emergency Power Off InputX5 Auxiliary DC Power Output X7 External Battery Temperature Detector InterfaceSerial Ports RS232-1 and RS232-2 External Bypass Switch InterlockBattery Start Facility Battery Start ButtonBattery Installation Hazardous battery voltage present behind covers SafetyBattery Cabinet Name W2 L=5m Name W1 L=30m Battery Temperature Sensor OptionalMoving the Battery Cabinets Cable W2 is packed with the temperature sensorGeneral Arrangement Drawings Battery cabinet bottom cable entry locationBottom cable entry Battery cabinet internal layout Item # Item Name Battery Power CablesConnection Principles Fitting the Batteries Battery ControlConnecting the Battery Battery Room DesignX21 GeneralX23 X24 Monitor Board X24Distribution Cabinet Cabinet InstallationParalleled UPS Modules External Protective Devices Power CablesControl Cables Intermodule Control Hot-Standby UPS ModulesInput Distribution Upstream Dual Bus System Parallel Board DBS Cable X2-2 X1-1 Parallel System Control WiresExtended Dual Bus Synchronization Option DBS Interface Box Parallel Board X2-2 X1-1 Parallel SystemInstallation Drawings General arrangement-10-30kVA UPS module External Battery Input Output Main Input Bypass Input NXe 10-30kVA Top View Internal battery layout and connecting-GP12120 F2 12AH/12V Internal battery layout Split-Bypass Input Battery Temperature Compensation Static Transfer SwitchSocket Outlet Redundant Control Power Supply BoardMulti Module UPS-1+N Modes of Operation Parallel Redundancy Mode System Expansion Bypass ModeMaintenance Mode Manual Bypass ECO Mode Single UPS OnlyNormal Function Battery Management-Set During CommissioningBattery Protection settings by commissioning engineer UPS operating modes Power SwitchesRotary switch configurations UPS Startup Start-Up ProcedureIndicator State Verify Switching Between Operation Modes Powering Down the UPS Switching the UPS from Normal to Maintenance BypassPowering Down the UPS and Maintaining Power to Load Auto Restart Emergency Shutdown With EPOChanging the Current Date and Time Command PasswordLanguage Selection Isolating One Module in a Multi-Module System LED Function Status Inserting One Module into a Multi-Module SystemButton Function UPS control and display panel componentsComponent # Function Audible Alarm Buzzer Mimic Power FlowMenu key Icons and their meaning Direct Access Push Buttons KeysLCD Monitor and Menu keys Displayed on the front LCD. When not activated, Load System Battery RecordsLanguage Settings Command Version When configured, input transformer voltages areMenu Type Item Type Explanation Detailed Description of Menu ItemsUPS system window Descriptions of UPS menus and data window itemsNumber to be dialed to send an alarm notification Message Description / Suggested Action if any UPS messagesBypass voltage exceeds the limit UPS is confirmed to overload and the overload times out UPS messages Prompt Meaning Dynamic Energy Flow Chart and UPS Help ScreenPrompt Pop-Up Windows Prompt windows, meaningsDefault screen Default Screen SaverTerminal Name Definition Battery Ground Fault DetectionProtection AC Fan Redundant Fan for Power ModuleFan120 Fan120OC Web Card data summary window OC Web Card SNMP/HTTP Network Interface CardRelay card jumpers Relay Card pin configurationRelay Card Multiport-4 CardPin Description SiteNet MultiPort4 Intellislot pin assignmentAssignment OC485 Web Card Modbus, Jbus, IGM Net Remote Alarm MonitorDust Filter for 10-30kVA Dust filter replacementOverall efficiency, heat losses and air exchange Environmental characteristicsConformity and Standards Compliance with European, international standardsRectifier AC input mains Mechanical characteristicsInverter output to critical load Bypass mains input Technical Specifications Technical Specifications Page That Ne tIti Ti n