Liebert NX UPS System user manual UPS messages, Message Description / Suggested Action if any

Page 68

Operator Control Panel and Display

Current Record Window

Keeps a log the events that resulted in the current mode of operation. Ignores transient conditions that have been resolved.

Use “page” (F1) and up / down arrow to read the events.

For a complete history log, refer to the Records tab of the Menu and Data Window. Refer to Table 22 for a complete list of supported status messages.

7.2All Status and Event Messages Displayed on the UPS Front Panel

This is the complete list of UPS events and status messages supported for display in either the Record window (Historic data) or in the Current window (Prevailing data) as described in 7.1.4 - LCD Moni- tor and Menu keys.

Table 22

UPS messages

 

 

 

Message

 

Description / Suggested Action (if any)

Inverter Comm. Fail

Internal RS485 communication failure between monitor and inverter

 

 

Rectifier Comm. Fail

Internal RS485 communication failure between monitor and rectifier

 

 

 

 

 

The CAN communication between different UPSs within a parallel system fails.

Parallel Comm. Fail

1.Check if there are some UPSs not powered on in the parallel system. If so, power on these

UPSs and check if the alarm disappears.

 

 

 

 

2. Press Fault Clear push button.

 

 

Battery Overtemp.

The Battery temperature is over limit. Check the battery temperature and ventilation

 

 

Ambient Overtemp.

The Ambient temperature is over limit. Check the ventilation of UPS room.

 

 

 

Battery Fault

 

Battery detected faulty (Reserved)

Replace Battery

Battery test failed, Battery should be replaced.

 

 

 

 

 

Before the end of discharge, battery undervoltage pre-warning should occur. After this pre-

Battery Low Pre-warning

warning, battery should have the capacity for 3 minutes discharging with full load. The time is

user-configured from 3 to 60 minutes.

 

 

 

 

Shut down the load in time.

 

 

Battery End of Discharge

Inverter turned off due to low battery voltage. Check the utility failure and try to recover it.

 

 

 

Mains Volt. Abnormal

Mains Voltage exceeds the upper or lower limit and results in rectifier shutdown.

Check the input line-to-neutral voltage amplitude of rectifier.

 

 

Mains Undervoltage

Mains Voltage is undervoltage with derated load.

Check the input line-to-line voltage amplitude of rectifier

 

 

Mains Freq. Abnormal

Mains frequency is out of limit range and results in rectifier shutdown.

Check the rectifier’s input voltage frequency

 

 

Rectifier Fault

Rectifier detected faulty. Rectifier shuts down. Battery discharges.

 

 

 

Rectifier Overtemp.

The temperature of heat sink is too high to keep the rectifier running.

The UPS can recover automatically. Check the environment and ventilation.

 

 

Batt. Contactor Fail

Battery contactor or circuit breaker not responding to control signals.

 

 

Batt. Charger Fault

The voltage of the battery charger is too high.

 

 

Control Power 1 Fail

UPS operates but Redundant Control Power is not available.

 

 

Mains Phase Reversed

AC Input phase sequence is reversed.

 

 

Rectifier Overcurrent

Rectifier is overloaded.

 

 

Soft Start Fail

Rectifier could not start due to low DC bus voltage

 

 

 

 

 

This alarm is triggered by an inverter software routine when the amplitude or frequency of

 

 

bypass voltage is beyond the normal range.

 

 

The amplitude threshold is fixed for positive and negative 10% rating.

 

 

This alarm automatically resets once the bypass voltage goes normal.

Bypass Unable to Trace

1. First verify that the bypass voltage and frequency displayed on the panel is within the

 

 

selected range. Note here the rated voltage and frequency are specified by “Output voltage

 

 

level” and “Output frequency level” respectively.

 

 

2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and

 

 

frequency presented to the UPS. Check the external supply if it is found to be faulty.

60

Image 68
Contents Liebert NX UPS Page Table of Contents UPS MULTI-MODULEINSTALLATION Dual Bus SystemOperating Procedures OPTIONS-FORASSEMBLY Inside the UPS CabinetTechnical Specifications Operator Control Panel and DisplayFigures Tables Feature Set for Region Input OutputAust/NZ Options Model IdentificationSafety Precautions Conformity and StandardsUser-Serviceable Parts Battery Voltage Exceeds 400VDCIntroduction Preliminary ChecksExternal Battery Room LocationUPS Room StoragePositioning System Cabinets2 10 to 30kVA UPS Moving the CabinetsExternal Protective Devices UPS Output External BatteryEarth Leakage RCD Distance from floor to connection point on the equipment Power CablesMaximum steady state AC and DC currents Cable Termination Common Input ConnectionsOutput System Connections Monitor Board Features Control Cables and CommunicationX3 Ancillary Control and Alarms Maintenance Bypass Cabinet InterfaceDry Contacts Input Dry ContactsExternal Circuit-Breaker Interface Jumper connection for BCB interfaceOutput Dry Contacts Output dry contact relays+12V J13 J21 J28Emergency Power Off Input X5 Auxiliary DC Power OutputX7 External Battery Temperature Detector Interface X6 Analog Input InterfaceExternal Bypass Switch Interlock Battery Start FacilityBattery Start Button Serial Ports RS232-1 and RS232-2Battery Installation Safety Hazardous battery voltage present behind coversBattery Cabinet Battery Temperature Sensor Optional Moving the Battery CabinetsCable W2 is packed with the temperature sensor Name W2 L=5m Name W1 L=30mBattery cabinet bottom cable entry location General Arrangement DrawingsBottom cable entry Battery cabinet internal layout Item # Item Name Battery Power CablesConnection Principles Battery Control Connecting the BatteryBattery Room Design Fitting the BatteriesGeneral X23 X24 Monitor BoardX24 X21Distribution Cabinet Cabinet InstallationParalleled UPS Modules Power Cables External Protective DevicesHot-Standby UPS Modules Control Cables Intermodule ControlInput Distribution Upstream Dual Bus System Control Wires Extended Dual Bus Synchronization Option DBS Interface BoxParallel Board X2-2 X1-1 Parallel System Parallel Board DBS Cable X2-2 X1-1 Parallel SystemInstallation Drawings General arrangement-10-30kVA UPS module External Battery Input Output Main Input Bypass Input NXe 10-30kVA Top View Internal battery layout and connecting-GP12120 F2 12AH/12V Internal battery layout Split-Bypass Input Static Transfer Switch Battery Temperature CompensationSocket Outlet Redundant Control Power Supply BoardMulti Module UPS-1+N Modes of Operation Bypass Mode Maintenance Mode Manual BypassECO Mode Single UPS Only Parallel Redundancy Mode System ExpansionNormal Function Battery Management-Set During CommissioningBattery Protection settings by commissioning engineer UPS operating modes Power SwitchesRotary switch configurations UPS Startup Start-Up ProcedureIndicator State Verify Switching Between Operation Modes Switching the UPS from Normal to Maintenance Bypass Powering Down the UPSPowering Down the UPS and Maintaining Power to Load Emergency Shutdown With EPO Auto RestartChanging the Current Date and Time Command PasswordLanguage Selection Isolating One Module in a Multi-Module System Inserting One Module into a Multi-Module System LED Function StatusButton Function UPS control and display panel componentsComponent # Function Mimic Power Flow Audible Alarm BuzzerMenu key Icons and their meaning Direct Access Push Buttons KeysLCD Monitor and Menu keys Load System Battery Records Language Settings Command VersionWhen configured, input transformer voltages are Displayed on the front LCD. When not activated,Detailed Description of Menu Items UPS system windowDescriptions of UPS menus and data window items Menu Type Item Type ExplanationNumber to be dialed to send an alarm notification UPS messages Message Description / Suggested Action if anyBypass voltage exceeds the limit UPS is confirmed to overload and the overload times out UPS messages Dynamic Energy Flow Chart and UPS Help Screen Prompt Pop-Up WindowsPrompt windows, meanings Prompt MeaningDefault Screen Saver Default screenTerminal Name Definition Battery Ground Fault DetectionProtection Redundant Fan for Power Module Fan120Fan120 AC FanOC Web Card SNMP/HTTP Network Interface Card OC Web Card data summary windowRelay Card pin configuration Relay CardMultiport-4 Card Relay card jumpersPin Description SiteNet MultiPort4 Intellislot pin assignmentAssignment Remote Alarm Monitor OC485 Web Card Modbus, Jbus, IGM NetDust filter replacement Dust Filter for 10-30kVAEnvironmental characteristics Conformity and StandardsCompliance with European, international standards Overall efficiency, heat losses and air exchangeMechanical characteristics Rectifier AC input mainsInverter output to critical load Bypass mains input Technical Specifications Technical Specifications Page Ne t ItiTi n That