Liebert NX UPS System user manual Input Dry Contacts, X3 Ancillary Control and Alarms

Page 20

Single Module UPS Installation

1.8Dry Contacts

The UPS provides input dry contacts and output dry contacts.

1.8.1Input Dry Contacts

There are several input dry contacts at the X3 slot.

Figure 3 Input dry contacts

12V 12V

12V

12V

X3

 

J4

 

 

12V

GEN

BtG

ENV

 

J26

 

 

GND

12V

AUX I

T IT

 

J30

 

 

AUX O

T OT

F FAN

FUSE

J10

OL

GND

FB

DRV

X3 Ancillary Control and Alarms

X3 IN DRY: Environmental, Battery Ground Fault and Generator Contacts

The UPS accepts external signalling from voltage-free (dry) contacts connected to finger-proof, push-in ter- minal X3 IN DRY. Subject to prior software programming, the signalling is accepted by the UPS when connection between the relevant terminal and the +12V terminal is altered. Cables connected to X3 IN DRY must be segregated from power circuits (for screening purposes), double insulated and of a typical 0.5 to 1mm2 cross-section area for maximum runs between 25 and 50 meters (82-164 ft), respectively.

Table 3

Input dry contacts at X3

 

 

 

 

Position

 

Name

Description

J4.1

 

ENV3

Battery Room Alarm (NC)

J4.2

 

BtG

Battery Ground Fault Detection (NC)

J4.3

 

GEN1,2

On Generator (NO)

J4.4

 

+12V

+12V Power

1 - Must be configured by configuration software before becoming active.

2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%). 3 - Activating this feature turns the battery charger off.

1.8.2Maintenance Bypass Cabinet Interface

J26 and J30 are the MBC interface.

Table 4 Maintenance bypass cabinet interface

Position

Name

Description

J26.1

T_IT1

Input transformer overtemperature (NC)

J26.2

AUX_I

Reserved

J26.3

+12V

+12V Power

J26.4

GND

Power Ground

J30.1

FUSE

Reserved

J30.2

F_FAN

Fan Fail Alarm (NC)

J30.3

T_OT1

Output Transformer Overtemperature (NC)

J30.4

AUX_O

Reserved

1- Must be configured by software before becoming active

NOTE

All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm2

(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.

12

Image 20
Contents Liebert NX UPS Page Table of Contents UPS MULTI-MODULEINSTALLATION Dual Bus SystemOperating Procedures OPTIONS-FORASSEMBLY Inside the UPS CabinetTechnical Specifications Operator Control Panel and DisplayFigures Tables Feature Set for Region Input OutputAust/NZ Options Model IdentificationSafety Precautions Conformity and StandardsUser-Serviceable Parts Battery Voltage Exceeds 400VDCIntroduction Preliminary ChecksExternal Battery Room LocationUPS Room StoragePositioning System Cabinets2 10 to 30kVA UPS Moving the CabinetsExternal Protective Devices UPS Output External BatteryEarth Leakage RCD Distance from floor to connection point on the equipment Power CablesMaximum steady state AC and DC currents Cable Termination Common Input ConnectionsOutput System Connections Monitor Board Features Control Cables and CommunicationX3 Ancillary Control and Alarms Maintenance Bypass Cabinet InterfaceDry Contacts Input Dry ContactsExternal Circuit-Breaker Interface Jumper connection for BCB interfaceOutput Dry Contacts Output dry contact relays+12V J13 J21 J28Emergency Power Off Input X5 Auxiliary DC Power OutputX7 External Battery Temperature Detector Interface X6 Analog Input InterfaceExternal Bypass Switch Interlock Battery Start FacilityBattery Start Button Serial Ports RS232-1 and RS232-2Battery Installation Safety Hazardous battery voltage present behind coversBattery Cabinet Battery Temperature Sensor Optional Moving the Battery CabinetsCable W2 is packed with the temperature sensor Name W2 L=5m Name W1 L=30mBattery cabinet bottom cable entry location General Arrangement DrawingsBottom cable entry Battery cabinet internal layout Item # Item Name Battery Power CablesConnection Principles Battery Control Connecting the BatteryBattery Room Design Fitting the BatteriesGeneral X23 X24 Monitor BoardX24 X21Distribution Cabinet Cabinet InstallationParalleled UPS Modules Power Cables External Protective DevicesHot-Standby UPS Modules Control Cables Intermodule ControlInput Distribution Upstream Dual Bus System Control Wires Extended Dual Bus Synchronization Option DBS Interface BoxParallel Board X2-2 X1-1 Parallel System Parallel Board DBS Cable X2-2 X1-1 Parallel SystemInstallation Drawings General arrangement-10-30kVA UPS module External Battery Input Output Main Input Bypass Input NXe 10-30kVA Top View Internal battery layout and connecting-GP12120 F2 12AH/12V Internal battery layout Split-Bypass Input Static Transfer Switch Battery Temperature CompensationSocket Outlet Redundant Control Power Supply BoardMulti Module UPS-1+N Modes of Operation Bypass Mode Maintenance Mode Manual BypassECO Mode Single UPS Only Parallel Redundancy Mode System ExpansionNormal Function Battery Management-Set During CommissioningBattery Protection settings by commissioning engineer UPS operating modes Power SwitchesRotary switch configurations UPS Startup Start-Up ProcedureIndicator State Verify Switching Between Operation Modes Switching the UPS from Normal to Maintenance Bypass Powering Down the UPSPowering Down the UPS and Maintaining Power to Load Emergency Shutdown With EPO Auto RestartChanging the Current Date and Time Command PasswordLanguage Selection Isolating One Module in a Multi-Module System Inserting One Module into a Multi-Module System LED Function StatusButton Function UPS control and display panel componentsComponent # Function Mimic Power Flow Audible Alarm BuzzerMenu key Icons and their meaning Direct Access Push Buttons KeysLCD Monitor and Menu keys Load System Battery Records Language Settings Command VersionWhen configured, input transformer voltages are Displayed on the front LCD. When not activated,Detailed Description of Menu Items UPS system windowDescriptions of UPS menus and data window items Menu Type Item Type ExplanationNumber to be dialed to send an alarm notification UPS messages Message Description / Suggested Action if anyBypass voltage exceeds the limit UPS is confirmed to overload and the overload times out UPS messages Dynamic Energy Flow Chart and UPS Help Screen Prompt Pop-Up WindowsPrompt windows, meanings Prompt MeaningDefault Screen Saver Default screenTerminal Name Definition Battery Ground Fault DetectionProtection Redundant Fan for Power Module Fan120Fan120 AC FanOC Web Card SNMP/HTTP Network Interface Card OC Web Card data summary windowRelay Card pin configuration Relay CardMultiport-4 Card Relay card jumpersPin Description SiteNet MultiPort4 Intellislot pin assignmentAssignment Remote Alarm Monitor OC485 Web Card Modbus, Jbus, IGM NetDust filter replacement Dust Filter for 10-30kVAEnvironmental characteristics Conformity and StandardsCompliance with European, international standards Overall efficiency, heat losses and air exchangeMechanical characteristics Rectifier AC input mainsInverter output to critical load Bypass mains input Technical Specifications Technical Specifications Page Ne t ItiTi n That