Liebert GXT2-6000RTL630 user manual Rack-Mount UPS Installation, Quantity

Page 16

Installation and Configuration

5.1.2Rack-Mount UPS Installation

When using the GXT2 in a rack-mount configuration, the UPS must be supported by a slide kit, fixed rails or a shelf.

When using the optional Adjustable Rack Mount Kit, you will use the following instructions. The fig- ures accompanying 5.1.3 - Installing the Adjustable Rack-MountKit—Sold Separately shows the positioning of the rack-mounting brackets. Liebert recommends taking the internal batteries out of the UPS during rack installation. This will make the UPS cabinet lighter and easier to handle.

! CAUTION

Only three (3) M4 screws are used on the side of the GXT2 where the Power Distribution Box is located. The fourth mounting hole is above the Power Distribution Box and is not used.

5.1.3Installing the Adjustable Rack-Mount Kit—Sold Separately

This kit contains parts needed to mount several different models of UPS and external battery cabi- nets into EIA310-D standard four-post racks that are 18-32" deep (457-813mm). The weight limit per pair of adjustable rack-mounting brackets is 200 lb (91kg).

Parts included are:

Item

Quantity

 

 

Rear bracket members

2

 

 

Front bracket members

2

 

 

Inner bracket members

2

 

 

M4 x 8mm machine screws

16

 

 

M4 locking hex nuts

8

 

 

M5 x 16 mm machine screws

12

 

 

Grease packet.

1

 

 

Tools needed for installation are:

one Phillips screwdriver

one 7mm wrench

The adjustable rack-mounting brackets (Part#: RMKIT18-32) feature retaining latches to prevent users from inadvertently sliding the UPS or battery cabinet out of the rack.

To install the rack mount brackets:

1.Unpack two (2) rack-mounting bracket assemblies and mounting hardware from this kit. Bracket assemblies are interchangeable between left-hand or right-hand.

Remove inner member of each bracket assembly as shown at right by extending it to its outermost position, depress- ing the retaining latch and then pulling the inner member out of the bracket assembly.

2.Determine the height position inside the rack enclosure where you want to mount the UPS or battery cabinet.

Return flanges

Retaining

Latches

Front

Innermembers members

! CAUTION

Reduce the risk of tipping the rack enclosure by placing the UPS or battery cabinet in the lowest possible rack position.

12

Image 16
Contents Liebert GXT2-6000RTL630 Page Table of Contents Maintenance TroubleshootingSpecifications Operating InstructionsImportant Safety Instructions Electromagnetic CompatibilityPage Glossary of Symbols Introduction Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionDC-to-DC Converter BatteryDynamic Bypass Top Trim 2 pieces tower use only Status Indicators Lower Bezel Battery Access Door UpperMain Frame and Electronics Major ComponentsInternal Battery Packs Battery Disconnect External Battery ConnectorFans UPS Output Circuit Breaker DB-9 Communication Port Relay Card SlotRemovable Power Distribution Box Bypass To UPS SwitchManual ConnectionsConfiguration Disk DB-9 port cover WHAT’S IncludedInstall the Main Cabinet Installation and ConfigurationTower UPS Installation Attach Bezels to TopRack-Mount UPS Installation Installing the Adjustable Rack-Mount Kit-Sold SeparatelyQuantity Return flanges Retaining Latches Front Innermembers membersScrews Install the Internal Batteries UPS orCabinet Apply grease inside Push it into the rackConnect the Internal Batteries Using the External Connector Connect Input/Output PowerBattery Door Captive Screws Remove these screws to release connectorFront of PD-L630 power distribution box Attach Power Distribution BoxLoosen these three UPS Distribution Box Electrical ConnectionsExternal Battery Cabinet Installation Initial START-UP and Electrical Checks Configuration Program GXT2-6000RTL630 Configuration Program FeaturesWhat You Will Need ON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsAll indicators illuminated for illustration only Standby/Manual Bypass ButtonLoad Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenFault Indicator LED Red Bypass Indicator LED AmberNormal Mode Operation Battery Mode OperationBypass Mode Operation Battery Recharge ModePin 4 Remote Shutdown on Battery Communications Interface PortCommunications DB-9 pin assignmentUPS Intelligent Communications Liebert’s Ocwebcard DB9 RS232 port coveredRemote Emergency Power Off Repo switch connection diagramInternal Battery MaintenanceInternal Battery Replacement Battery Door Captive Screws 3U Battery Access DoorBattery Connectors Retaining screw Retaining bracketAC Power Connections DisconnectCaptive Box toReconnect Indicator meanings TroubleshootingLED status Diagnosis/Audible alarm Troubleshooting guide UPSTroubleshooting guide cont’d Alarm conditionsBattery run times Auto-Learning Battery Run Times Specifications UPS specificationsInternal battery specifications Output distribution specificationsBattery Parameters External battery cabinet specificationsModel Number Page Ne t ItiTi n That