Liebert Comprehensive Troubleshooting Guide for GXT2 Models

Page 36

Troubleshooting

Table 3

Troubleshooting guide

 

 

 

 

Problem

Cause

Solution

 

 

 

 

UPS fails to start when the

UPS is short-circuited or

Ensure UPS is OFF. Disconnect all loads and ensure nothing is

lodged in output receptacles.

ON button is pressed.

overloaded.

Ensure loads are not defective or shorted internally.

 

 

 

 

 

UPS not plugged in.

UPS is operating from battery mode, make certain UPS is

 

 

securely plugged into the wall receptacle.

 

 

 

 

 

UPS input protection has

UPS is operating from battery mode. Save data and close

Battery indicator LED is

applications. Check UPS input circuit breaker, then restart

opened.

illuminated.

 

UPS.

 

 

 

 

Utility voltage out of UPS

UPS is operating from battery mode. Save data and close

 

 

applications. Ensure utility supply voltage is within acceptable

 

 

input range.

 

 

limits for UPS.

 

 

 

 

 

Batteries are not fully

Keep UPS plugged in continuously at least 24 hours to

 

 

charged.

recharge batteries.

UPS has reduced battery

UPS is overloaded.

Check load level display and reduce the load on the UPS.

time.

 

 

 

 

Batteries may not be able to

Replace batteries. Contact your local dealer, Liebert

 

 

 

 

representative or the Liebert Worldwide Support Group for

 

 

hold a full charge due to age.

 

 

replacement battery kit.

Fault and Bypass indicator

UPS overloaded or load

Check load level display and remove non-essential loads.

LEDs and all load level LEDs

Recalculate the load and reduce number of loads connected to

are illuminated.

equipment is faulty.

UPS. Check load equipment for faults.

 

 

 

UPS internal fan has a

Ensure UPS is not overloaded, ventilation openings not

Fault and Bypass indicator

blocked, or room ambient temperature is not excessive. Wait

problem or UPS shutdown

LEDs and diagnostic LED A

30 minutes to allow UPS to cool, then restart UPS. If UPS does

due to temperature condition.

are illuminated.

Load is on bypass power.

not restart, contact your local dealer, Liebert representative or

 

 

the Liebert Worldwide Support Group.

 

 

 

Fault and Bypass indicator

UPS internal DC bus

UPS requires service. Contact your local dealer, Liebert

LEDs and diagnostic LED B

overvoltage.

representative or the Liebert Worldwide Support Group.

are illuminated.

 

 

Fault indicator LED and

 

Bus voltage under 315VDC (O/P 220VAC) / 330VDC

DC-DC failure during battery

(O/P 230VAC) / 345VDC (O/P 240VAC). UPS requires service.

diagnostic LED C are

mode.

Contact your local dealer, Liebert representative or the Liebert

illuminated.

 

 

 

Worldwide Support Group.

 

 

 

Fault and Bypass indicator

UPS PFC (Power Factor

UPS requires service. Contact your local dealer, Liebert

LEDs and diagnostic LED D

Correction Circuit) fault.

representative or the Liebert Worldwide Support Group.

are illuminated.

 

 

Fault and Bypass indicator

 

UPS requires service. Contact your local dealer, Liebert

LEDs and diagnostic LED E

UPS inverter fault.

Representative or the Liebert Worldwide Support Group.

are illuminated.

 

 

 

Fault indicator LED and

 

Replace batteries. Contact your local dealer, Liebert

diagnostic LEDs A and C are

UPS failed the battery test.

representative or the Liebert Worldwide Support Group.

illuminated.

 

 

 

 

 

 

 

 

Your UPS has received a signal or command from the attached

Fault and Bypass indicator

UPS shutdown due to a

computer. If this was inadvertent, ensure the communication

LEDs and diagnostic LED C

command from the

cable used is correct for your system. For assistance, contact

and E are illuminated.

communications port(s).

your local dealer, Liebert representative or the Liebert

 

 

 

Worldwide Support Group.

Fault and LEDs A&E are

 

Check for external obstruction entering fan guard. UPS

Fan locked

requires service. Contact your local dealer, Liebert

Illuminated

 

 

 

representative or Liebert Worldwide Support Group.

 

 

 

Fault and LEDs B&C are

REPO active

REPO circuit loop is open. If not used, a wire jumper must

Illuminated

 

connect the REPO terminals.

 

 

 

 

UPS is OFF due to previous

 

Fault and LEDs B&D are

REPO shutdown, but the

 

REPO has been connected

Start the UPS using the front panel.

Illuminated

 

 

or reset. Autorestart

 

 

 

 

 

 

disabled.

 

32

Image 36
Contents Liebert GXT2-6000RTL630 Page Table of Contents Maintenance TroubleshootingSpecifications Operating InstructionsImportant Safety Instructions Electromagnetic CompatibilityPage Glossary of Symbols Introduction Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionBattery DC-to-DC ConverterDynamic Bypass Top Trim 2 pieces tower use only Status Indicators Lower Bezel Battery Access Door UpperMain Frame and Electronics Major ComponentsInternal Battery Packs Battery Disconnect External Battery ConnectorFans UPS Output Circuit Breaker DB-9 Communication Port Relay Card SlotRemovable Power Distribution Box Bypass To UPS SwitchManual ConnectionsConfiguration Disk DB-9 port cover WHAT’S IncludedInstall the Main Cabinet Installation and ConfigurationTower UPS Installation Attach Bezels to TopRack-Mount UPS Installation Installing the Adjustable Rack-Mount Kit-Sold SeparatelyQuantity Return flanges Retaining Latches Front Innermembers membersScrews Install the Internal Batteries UPS orCabinet Apply grease inside Push it into the rackConnect the Internal Batteries Using the External Connector Connect Input/Output PowerBattery Door Captive Screws Remove these screws to release connectorAttach Power Distribution Box Front of PD-L630 power distribution boxLoosen these three UPS Distribution Box Electrical ConnectionsExternal Battery Cabinet Installation Initial START-UP and Electrical Checks GXT2-6000RTL630 Configuration Program Features Configuration ProgramWhat You Will Need ON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsAll indicators illuminated for illustration only Standby/Manual Bypass ButtonLoad Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenFault Indicator LED Red Bypass Indicator LED AmberNormal Mode Operation Battery Mode OperationBypass Mode Operation Battery Recharge ModePin 4 Remote Shutdown on Battery Communications Interface PortCommunications DB-9 pin assignmentUPS Intelligent Communications Liebert’s Ocwebcard DB9 RS232 port coveredRemote Emergency Power Off Repo switch connection diagramInternal Battery MaintenanceInternal Battery Replacement Battery Door Captive Screws 3U Battery Access DoorBattery Connectors Retaining screw Retaining bracketAC Power Connections DisconnectCaptive Box toReconnect Troubleshooting Indicator meaningsLED status Diagnosis/Audible alarm Troubleshooting guide UPSTroubleshooting guide cont’d Alarm conditionsBattery run times Auto-Learning Battery Run Times Specifications UPS specificationsInternal battery specifications Output distribution specificationsExternal battery cabinet specifications Battery ParametersModel Number Page Ne t ItiTi n That