Liebert GXT2-6000RTL630 Attach Power Distribution Box, Front of PD-L630 power distribution box

Page 20

Installation and Configuration

5.4.1Attach Power Distribution Box

Whenever the power distribution box is not attached to the UPS, the cover must be slid over the elec- trical connections to prevent damage or injury.

To attach the PD-L630 power distribution box to the UPS:

1.Loosen the white cover over the electrical connections by backing out the three screws securing the cover one turn each.

2.Slide the cover open to expose the electrical connectors.

3.Gently retighten the three screws loosened in Step 1.

4.Align the connectors on the box and UPS.

5.Push the box into place.

6.Holding the box firmly against the UPS, tighten the three captive mounting screws until the box is secure. Do not overtighten.

Figure 6 PD-L630 power distribution box

FRONT of PD-L630 power distribution box

UPS

MAITANENCE BYPASS

AVAILABLE

UPS

ON

ON

 

 

 

OUTPUT

 

BREAKER

OUTPUT

20A

240V~/T

 

BREAKER

OFF

 

20A 240V~/T

OFF

 

 

 

 

 

INPPUT

BREA

30A

ON

 

 

OUTPUT ONLY

 

 

CB DOES NOT

CONNECT BYPASS

POWER TO

MANUAL

 

 

BYPASS SWITCH.

These captive screws attach the power distribution box to the UPS

INSIDE FACE of PD-L630 power distribution box

CONNECTOR PROTECTIVE COVER DO NOT REMOVE SCREWS PRIOR TO INSTALLATION OF BOX ON UPS

-LOOSEN THREE SCREWS 1 TURN

- SLIDE COVER TO EXPOSE CONNECTOR -TIGHTEN SCREWS GENTLY

UPON REMOVAL OF BOX FROM UPS -LOOSEN THREE SCREWS 1 TURN

-SLIDE COVER TO REACH END SCREW AND COVER COMMUNICATION -TIGHTEN SCREWS GENTLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Loosen these three

 

 

 

 

 

 

Slide the cover over

screws to move the

the connectors when

cover. Retighten the

the power distribution

screws after moving

box is removed from

the cover over the

the UPS.

connectors or off the

 

 

 

connectors.

16

Image 20
Contents Liebert GXT2-6000RTL630 Page Table of Contents Maintenance TroubleshootingSpecifications Operating InstructionsImportant Safety Instructions Electromagnetic CompatibilityPage Glossary of Symbols Introduction Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionDynamic Bypass BatteryDC-to-DC Converter Top Trim 2 pieces tower use only Status Indicators Lower Bezel Battery Access Door UpperMain Frame and Electronics Major ComponentsInternal Battery Packs Battery Disconnect External Battery ConnectorFans UPS Output Circuit Breaker DB-9 Communication Port Relay Card SlotRemovable Power Distribution Box Bypass To UPS SwitchManual ConnectionsConfiguration Disk DB-9 port cover WHAT’S IncludedInstall the Main Cabinet Installation and ConfigurationTower UPS Installation Attach Bezels to TopRack-Mount UPS Installation Installing the Adjustable Rack-Mount Kit-Sold SeparatelyQuantity Return flanges Retaining Latches Front Innermembers membersScrews Install the Internal Batteries UPS orCabinet Apply grease inside Push it into the rackConnect the Internal Batteries Using the External Connector Connect Input/Output PowerBattery Door Captive Screws Remove these screws to release connectorLoosen these three Attach Power Distribution BoxFront of PD-L630 power distribution box UPS Distribution Box Electrical ConnectionsExternal Battery Cabinet Installation Initial START-UP and Electrical Checks What You Will Need GXT2-6000RTL630 Configuration Program FeaturesConfiguration Program ON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsAll indicators illuminated for illustration only Standby/Manual Bypass ButtonLoad Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenFault Indicator LED Red Bypass Indicator LED AmberNormal Mode Operation Battery Mode OperationBypass Mode Operation Battery Recharge ModePin 4 Remote Shutdown on Battery Communications Interface PortCommunications DB-9 pin assignmentUPS Intelligent Communications Liebert’s Ocwebcard DB9 RS232 port coveredRemote Emergency Power Off Repo switch connection diagramInternal Battery MaintenanceInternal Battery Replacement Battery Door Captive Screws 3U Battery Access DoorBattery Connectors Retaining screw Retaining bracketAC Power Connections DisconnectCaptive Box toReconnect LED status Diagnosis/Audible alarm TroubleshootingIndicator meanings Troubleshooting guide UPSTroubleshooting guide cont’d Alarm conditionsBattery run times Auto-Learning Battery Run Times Specifications UPS specificationsInternal battery specifications Output distribution specificationsModel Number External battery cabinet specificationsBattery Parameters Page Ne t ItiTi n That