Liebert GXT2-6000RTL630 user manual Ups, Distribution Box Electrical Connections

Page 21

Installation and Configuration

5.4.2Distribution Box Electrical Connections

Electrical connections are made through a removable power distribution box that attaches to the rear of the UPS.

The installer must provide a 30A branch circuit breaker, with NEMA L6-30R receptacle. The Input circuit breaker on the distribution box and the Output circuit breaker on the rear fixed-panel of the UPS disconnect all power between the main cabinet and the distribution box.

Models equipped with a manual bypass switch pass bypass power directly to the bypass switch from the input power cord. The input circuit breaker on the distribution box does not disconnect power from the manual bypass switch.

Figure 7 PD-L630 power distribution box electrical connections diagram

Utility Input

30A External

2-Pole Branch

Circuit Breaker

 

Utility

30

Input

UPS

 

CB

 

 

Output

30 UPS

Output

CB

UPS - PFC, Battery, Inverter

17

Image 21
Contents Liebert GXT2-6000RTL630 Page Table of Contents Troubleshooting MaintenanceSpecifications Operating InstructionsElectromagnetic Compatibility Important Safety InstructionsPage Glossary of Symbols Introduction Battery Charger Rectifier/Power Factor Correction PFC CircuitInverter System DescriptionBattery DC-to-DC ConverterDynamic Bypass Lower Bezel Battery Access Door Upper Top Trim 2 pieces tower use only Status IndicatorsMain Frame and Electronics Major ComponentsBattery Disconnect External Battery Connector Internal Battery PacksFans UPS Output Circuit Breaker DB-9 Communication Port Relay Card SlotBypass To UPS Switch Removable Power Distribution BoxManual ConnectionsWHAT’S Included Configuration Disk DB-9 port coverInstallation and Configuration Install the Main CabinetTower UPS Installation Attach Bezels to TopInstalling the Adjustable Rack-Mount Kit-Sold Separately Rack-Mount UPS InstallationQuantity Return flanges Retaining Latches Front Innermembers membersScrews UPS or Install the Internal BatteriesCabinet Apply grease inside Push it into the rackConnect Input/Output Power Connect the Internal Batteries Using the External ConnectorBattery Door Captive Screws Remove these screws to release connectorAttach Power Distribution Box Front of PD-L630 power distribution boxLoosen these three Distribution Box Electrical Connections UPSExternal Battery Cabinet Installation Initial START-UP and Electrical Checks GXT2-6000RTL630 Configuration Program Features Configuration ProgramWhat You Will Need Controls and Indicators ON/Alarm Silence/Manual Battery Test ButtonAll indicators illuminated for illustration only Standby/Manual Bypass ButtonBattery Level Indicators 5 Green Load Level Indicators 4 Green, 1 AmberFault Indicator LED Red Bypass Indicator LED AmberBattery Mode Operation Normal Mode OperationBypass Mode Operation Battery Recharge ModeCommunications Interface Port Pin 4 Remote Shutdown on BatteryCommunications DB-9 pin assignmentLiebert’s Ocwebcard DB9 RS232 port covered UPS Intelligent CommunicationsRepo switch connection diagram Remote Emergency Power OffMaintenance Internal BatteryBattery Door Captive Screws 3U Battery Access Door Internal Battery ReplacementBattery Connectors Retaining screw Retaining bracketDisconnect AC Power ConnectionsCaptive Box toReconnect Troubleshooting Indicator meaningsLED status Diagnosis/Audible alarm UPS Troubleshooting guideAlarm conditions Troubleshooting guide cont’dBattery run times Auto-Learning Battery Run Times UPS specifications SpecificationsOutput distribution specifications Internal battery specificationsExternal battery cabinet specifications Battery ParametersModel Number Page Iti Ne tTi n That