Liebert GXT2-6000RTL630 Connect the Internal Batteries Using the External Connector, Storage

Page 19

Installation and Configuration

1.Remove the 3U battery access panel on the front of the GXT2-6000RTL630 by loosening the two captive screws located between the bezels (see illustration at left).

Battery Door Captive Screws

!

UPStation GXT

!

- +

AC INPUT BATTERY UPS ON

BYPASS

3U Battery Access Door and

Battery Bezel

Retaining

Battery ConnectorsRetaining screw bracket (one of two)

2.Once the captive screws are loosened, tip the panel forward and lift to remove it from the main cabinet.

3.Unpack the GXT2-240BATKIT battery assembly.

4.Line up and slide in the battery pack while holding the internal connector out of the way.

5.Connect the electrical cables to each battery pack with the two slotted battery connectors.

6.Install the battery retaining brackets supplied in the accessory box.

7.Install the battery access panel and tighten the captive screws.

5.3Connect the Internal Batteries Using the External Connector

The connector attaches to the UPS in both the open and closed position using two screws. The picture on the left shows the connector in the open position, as shipped.

When the UPS is installed, remove the two screws to release the connector. Plug the connector into the socket. The internal batteries are now connected to the UPS electronics. Install the two screws to secure the connector in the closed position.

Remove these screws to release connector

5.3.1Storage

If the UPS is to be shipped or stored for an extended time, the connector should be removed and attached in the open position, as shown above. This will minimize any standby current drain on the batteries.

5.4Connect Input/Output Power

The Power Distribution box is shipped separately for easier handling of the UPS while the UPS is being placed in its final position.

15

Image 19
Contents Liebert GXT2-6000RTL630 Page Table of Contents Operating Instructions MaintenanceTroubleshooting SpecificationsElectromagnetic Compatibility Important Safety InstructionsPage Glossary of Symbols Introduction System Description Rectifier/Power Factor Correction PFC CircuitBattery Charger InverterDC-to-DC Converter BatteryDynamic Bypass Major Components Top Trim 2 pieces tower use only Status IndicatorsLower Bezel Battery Access Door Upper Main Frame and ElectronicsRelay Card Slot Internal Battery PacksBattery Disconnect External Battery Connector Fans UPS Output Circuit Breaker DB-9 Communication PortConnections Removable Power Distribution BoxBypass To UPS Switch ManualWHAT’S Included Configuration Disk DB-9 port coverAttach Bezels to Top Install the Main CabinetInstallation and Configuration Tower UPS InstallationReturn flanges Retaining Latches Front Innermembers members Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityScrews Apply grease inside Push it into the rack Install the Internal BatteriesUPS or CabinetRemove these screws to release connector Connect the Internal Batteries Using the External ConnectorConnect Input/Output Power Battery Door Captive ScrewsFront of PD-L630 power distribution box Attach Power Distribution BoxLoosen these three Distribution Box Electrical Connections UPSExternal Battery Cabinet Installation Initial START-UP and Electrical Checks Configuration Program GXT2-6000RTL630 Configuration Program FeaturesWhat You Will Need Standby/Manual Bypass Button ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators All indicators illuminated for illustration onlyBypass Indicator LED Amber Load Level Indicators 4 Green, 1 AmberBattery Level Indicators 5 Green Fault Indicator LED RedBattery Recharge Mode Normal Mode OperationBattery Mode Operation Bypass Mode OperationDB-9 pin assignment Pin 4 Remote Shutdown on BatteryCommunications Interface Port CommunicationsLiebert’s Ocwebcard DB9 RS232 port covered UPS Intelligent CommunicationsRepo switch connection diagram Remote Emergency Power OffMaintenance Internal BatteryRetaining screw Retaining bracket Internal Battery ReplacementBattery Door Captive Screws 3U Battery Access Door Battery ConnectorsBox to AC Power ConnectionsDisconnect CaptiveReconnect Indicator meanings TroubleshootingLED status Diagnosis/Audible alarm UPS Troubleshooting guideAlarm conditions Troubleshooting guide cont’dBattery run times Auto-Learning Battery Run Times UPS specifications SpecificationsOutput distribution specifications Internal battery specificationsBattery Parameters External battery cabinet specificationsModel Number Page That Ne tIti Ti n