Specifications

13.0SPECIFICATIONS

Table 6

UPS specifications

 

 

 

 

 

Model Number

GXT2-6000RTL630

 

 

 

 

 

Model Rating

6000VA/4200W

 

 

 

 

 

Dimensions, in. (mm)

 

 

 

 

Unit, W x D x H

8.7 x 21.5 x 16.9 (221 x 547 x 430)

 

 

 

 

Shipping, W x D x H

22.0 x 27.2 x 19.7 (560 x 690 x 500)

 

 

 

 

Weight, lb (kg)

 

 

 

 

Unit

57.2 (26)

 

 

 

 

 

 

 

 

Shipping

81.5 (37)

 

 

 

 

 

 

Input AC Parameters

 

 

 

 

Nominal Operating Frequency

50 or 60Hz (Factory Default = 60)

 

 

 

 

 

 

Factory Default VAC

208VAC

 

 

 

 

 

 

User Configurable VAC

208/220/230/240VAC

 

(May be modified using configuration program)

 

 

Operating Voltage Range Without

176 – 276VAC

 

 

 

Battery Operation

 

 

 

 

 

 

 

Maximum Allowable VAC

276VAC

 

 

 

 

 

 

Input Frequency Without Battery

40 - 70Hz

 

 

 

Operation

 

 

 

 

 

 

 

Input Power Connection

L6-30P Plug (on PD-L630 power distribution box)

 

 

 

 

Output AC Parameters

 

 

 

 

Factory Default VAC

208VAC

 

 

 

 

 

 

Output Connections

(2) L6-20R and (2) L6-30R on 12" (300mm) cords

 

(on PD-L630 power distribution box)

 

 

 

Frequency

50Hz or 60Hz, Nominal

 

 

 

 

 

 

Waveform

Sinewave

 

 

 

 

 

 

Main Mode

>200% for 96 milliseconds; 131 - 199% for 2 seconds;

 

Overload

112- 129% for 10 seconds with transfer to bypass

Bypass Protection Limits

 

 

 

 

Disable Bypass operation

If input voltage exceeds ±15% of the nominal voltage

 

 

 

 

Re-enable Bypass operation

If input voltage returns to within ±10% of nominal output voltage

 

 

 

 

Disable Bypass operation

When the input frequency prevents synchronous operation

 

 

 

 

Environmental

 

 

 

 

Operating Temperature

32°F to 104° F (0°C to 40°C)

 

 

 

 

Storage Temperature

5°F to 122° F (-15°C to 50°C)

 

 

 

 

Relative Humidity

0-95% non-condensing

 

 

 

 

 

 

Operating Elevation

°

°

C) without derating

 

 

Up to 6600 ft (2000m) at 104 F (40

 

 

Storage Elevation

50,000 ft. (15,000m) maximum

 

 

 

 

Audible Noise

<55 dBA, at 3 ft. (1m) from the rear

 

<50 dBA, at 3 ft. (1m) from the front or sides

 

 

Agency

 

 

 

 

Safety

UL, C-UL Listed to UL1778

 

 

 

 

 

 

EMI/EMC

FCC Class B

 

 

 

 

 

 

ESD

EN61000-4-2, Level 4, Criteria A

 

 

 

 

Radiated Susceptibility

EN61000-4-3, Level 3, Criteria A

 

 

 

 

Electrical Fast Transient

EN61000-4-4, Level 4, Criteria A

 

 

 

 

Surge Immunity

EN61000-4-5, Level 3, Criteria A

 

 

 

 

Transportation

ISTA Procedure 1B

 

 

 

 

 

36

Image 40
Contents Liebert GXT2-6000RTL630 Page Table of Contents Maintenance TroubleshootingSpecifications Operating InstructionsImportant Safety Instructions Electromagnetic CompatibilityPage Glossary of Symbols Introduction Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionDC-to-DC Converter BatteryDynamic Bypass Top Trim 2 pieces tower use only Status Indicators Lower Bezel Battery Access Door UpperMain Frame and Electronics Major ComponentsInternal Battery Packs Battery Disconnect External Battery ConnectorFans UPS Output Circuit Breaker DB-9 Communication Port Relay Card SlotRemovable Power Distribution Box Bypass To UPS SwitchManual ConnectionsConfiguration Disk DB-9 port cover WHAT’S IncludedInstall the Main Cabinet Installation and ConfigurationTower UPS Installation Attach Bezels to TopRack-Mount UPS Installation Installing the Adjustable Rack-Mount Kit-Sold SeparatelyQuantity Return flanges Retaining Latches Front Innermembers membersScrews Install the Internal Batteries UPS orCabinet Apply grease inside Push it into the rackConnect the Internal Batteries Using the External Connector Connect Input/Output PowerBattery Door Captive Screws Remove these screws to release connectorFront of PD-L630 power distribution box Attach Power Distribution BoxLoosen these three UPS Distribution Box Electrical ConnectionsExternal Battery Cabinet Installation Initial START-UP and Electrical Checks Configuration Program GXT2-6000RTL630 Configuration Program FeaturesWhat You Will Need ON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsAll indicators illuminated for illustration only Standby/Manual Bypass ButtonLoad Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenFault Indicator LED Red Bypass Indicator LED AmberNormal Mode Operation Battery Mode OperationBypass Mode Operation Battery Recharge ModePin 4 Remote Shutdown on Battery Communications Interface PortCommunications DB-9 pin assignmentUPS Intelligent Communications Liebert’s Ocwebcard DB9 RS232 port coveredRemote Emergency Power Off Repo switch connection diagramInternal Battery MaintenanceInternal Battery Replacement Battery Door Captive Screws 3U Battery Access DoorBattery Connectors Retaining screw Retaining bracketAC Power Connections DisconnectCaptive Box toReconnect Indicator meanings TroubleshootingLED status Diagnosis/Audible alarm Troubleshooting guide UPSTroubleshooting guide cont’d Alarm conditionsBattery run times Auto-Learning Battery Run Times Specifications UPS specificationsInternal battery specifications Output distribution specificationsBattery Parameters External battery cabinet specificationsModel Number Page Ne t ItiTi n That