Liebert GXT2-6000RTL630 user manual Install the Internal Batteries, UPS or, Cabinet

Page 18
Insert the UPS into the front
members, lift the front ...

Installation and Configuration

7.Insert the equipment, with inner members attached in Step 5, into the bracket assemblies by inserting the top

and bottom edges of the inner members into the top and

UPS or

bottom curved tracks of the front members and sliding

battery

the equipment into the rack (see figure at right). Ends of

cabinet

inner members are tapered to allow the rear of the

 

equipment to be angled upward before insertion, if space

 

allows.

 

Then the rear, bottom edges of the inner members can

 

be placed into the front edge of the bottom tracks and

 

the front of the equipment can be tipped up so they are

 

level to insert the top edges of the inner members before

 

sliding the equipment into the rack (see figure below

 

right). The equipment should move smoothly into the

 

bracket assemblies. If it does not, recheck the alignment

 

of the front and rear members from Steps 2 and 3.

 

8.Secure the front of the equipment to the rack mounting rails to prevent the equipment from sliding out of position. If securing holes are provided on the front of the equipment that align with the center holes on the return flange of the front members, you can use the four

(4) extra M5 screws provided in the kit to secure the equipment. Otherwise, the equipment should be secured

to the front of the rack with four (4) customer-supplied fasteners.

Apply grease

Apply grease (inside)

... and push it into the rack.

5.2Install the Internal Batteries

For ease of installation and configuration, the GXT2-6000RTL630 is shipped without its internal bat- teries installed. After the UPS is prepared and installed as either a tower or in a rack, install the GXT2-240BATKIT battery packs.

To install the internal batteries:

! CAUTION

A battery can present a risk of electrical shock and high short circuit current. Observe the following precautions before replacing the batteries:

Remove rings, watches and other metal objects.

Use a Phillips (cross-head) screwdriver with insulated grips.

Do not lay tools or other metal objects on top of the batteries.

If the battery replacement kit is damaged in any way or shows signs of leakage, contact your local dealer or Liebert representative immediately.

Do not dispose of batteries in a fire. The batteries may explode.

Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It is toxic.

14

Image 18
Contents Liebert GXT2-6000RTL630 Page Table of Contents Specifications MaintenanceTroubleshooting Operating InstructionsImportant Safety Instructions Electromagnetic CompatibilityPage Glossary of Symbols Introduction Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger System DescriptionBattery DC-to-DC ConverterDynamic Bypass Main Frame and Electronics Top Trim 2 pieces tower use only Status IndicatorsLower Bezel Battery Access Door Upper Major ComponentsFans UPS Output Circuit Breaker DB-9 Communication Port Internal Battery PacksBattery Disconnect External Battery Connector Relay Card SlotManual Removable Power Distribution BoxBypass To UPS Switch ConnectionsConfiguration Disk DB-9 port cover WHAT’S IncludedTower UPS Installation Install the Main CabinetInstallation and Configuration Attach Bezels to TopQuantity Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately Return flanges Retaining Latches Front Innermembers membersScrews Cabinet Install the Internal BatteriesUPS or Apply grease inside Push it into the rackBattery Door Captive Screws Connect the Internal Batteries Using the External ConnectorConnect Input/Output Power Remove these screws to release connectorAttach Power Distribution Box Front of PD-L630 power distribution boxLoosen these three UPS Distribution Box Electrical ConnectionsExternal Battery Cabinet Installation Initial START-UP and Electrical Checks GXT2-6000RTL630 Configuration Program Features Configuration ProgramWhat You Will Need All indicators illuminated for illustration only ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators Standby/Manual Bypass ButtonFault Indicator LED Red Load Level Indicators 4 Green, 1 AmberBattery Level Indicators 5 Green Bypass Indicator LED AmberBypass Mode Operation Normal Mode OperationBattery Mode Operation Battery Recharge ModeCommunications Pin 4 Remote Shutdown on BatteryCommunications Interface Port DB-9 pin assignmentUPS Intelligent Communications Liebert’s Ocwebcard DB9 RS232 port coveredRemote Emergency Power Off Repo switch connection diagramInternal Battery MaintenanceBattery Connectors Internal Battery ReplacementBattery Door Captive Screws 3U Battery Access Door Retaining screw Retaining bracketCaptive AC Power ConnectionsDisconnect Box toReconnect Troubleshooting Indicator meaningsLED status Diagnosis/Audible alarm Troubleshooting guide UPSTroubleshooting guide cont’d Alarm conditionsBattery run times Auto-Learning Battery Run Times Specifications UPS specificationsInternal battery specifications Output distribution specificationsExternal battery cabinet specifications Battery ParametersModel Number Page Ti n Ne tIti That