12.0.1Auto-Learning Battery Run Times

As batteries age, the estimated runtimes may become less accurate. The GXT2-6000RTL630 is pro- grammed to “learn” from a full battery discharge and modify the estimated runtime for the measured battery capacity. This can improve accuracy and compensate for aging batteries or batteries that operate at different ambient temperatures.

The UPS will update the anticipated run time calculation only under certain conditions.

The UPS must have a steady load that is greater than 20%.

The UPS must be at 100% charge at the start of a battery discharge.

The battery discharge must continue uninterrupted until the batteries reach their end-of-dis- charge voltage.

If all conditions are not met, the run time calculation will not be modified.

If the configuration program is used to change the number of battery cabinets, then the values in the battery above table will be restored. This will override any value that is Auto-Learned.

35

Image 39
Contents Liebert GXT2-6000RTL630 Page Table of Contents Operating Instructions MaintenanceTroubleshooting SpecificationsElectromagnetic Compatibility Important Safety InstructionsPage Glossary of Symbols Introduction System Description Rectifier/Power Factor Correction PFC CircuitBattery Charger InverterBattery DC-to-DC ConverterDynamic Bypass Major Components Top Trim 2 pieces tower use only Status IndicatorsLower Bezel Battery Access Door Upper Main Frame and ElectronicsRelay Card Slot Internal Battery PacksBattery Disconnect External Battery Connector Fans UPS Output Circuit Breaker DB-9 Communication PortConnections Removable Power Distribution BoxBypass To UPS Switch ManualWHAT’S Included Configuration Disk DB-9 port coverAttach Bezels to Top Install the Main CabinetInstallation and Configuration Tower UPS InstallationReturn flanges Retaining Latches Front Innermembers members Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityScrews Apply grease inside Push it into the rack Install the Internal BatteriesUPS or CabinetRemove these screws to release connector Connect the Internal Batteries Using the External ConnectorConnect Input/Output Power Battery Door Captive ScrewsAttach Power Distribution Box Front of PD-L630 power distribution boxLoosen these three Distribution Box Electrical Connections UPSExternal Battery Cabinet Installation Initial START-UP and Electrical Checks GXT2-6000RTL630 Configuration Program Features Configuration ProgramWhat You Will Need Standby/Manual Bypass Button ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators All indicators illuminated for illustration onlyBypass Indicator LED Amber Load Level Indicators 4 Green, 1 AmberBattery Level Indicators 5 Green Fault Indicator LED RedBattery Recharge Mode Normal Mode OperationBattery Mode Operation Bypass Mode OperationDB-9 pin assignment Pin 4 Remote Shutdown on BatteryCommunications Interface Port CommunicationsLiebert’s Ocwebcard DB9 RS232 port covered UPS Intelligent CommunicationsRepo switch connection diagram Remote Emergency Power OffMaintenance Internal BatteryRetaining screw Retaining bracket Internal Battery ReplacementBattery Door Captive Screws 3U Battery Access Door Battery ConnectorsBox to AC Power ConnectionsDisconnect CaptiveReconnect Troubleshooting Indicator meaningsLED status Diagnosis/Audible alarm UPS Troubleshooting guideAlarm conditions Troubleshooting guide cont’dBattery run times Auto-Learning Battery Run Times UPS specifications SpecificationsOutput distribution specifications Internal battery specificationsExternal battery cabinet specifications Battery ParametersModel Number Page That Ne tIti Ti n