Initial Start-Up and Electrical Checks

6.0INITIAL START-UP AND ELECTRICAL CHECKS

1.Verify that the input and output circuit breakers are off (open).

2.During initial system checks, disconnect all loads (open load disconnects).

3.Inspect all wiring, cables, and connection.

4.If external battery cabinets are used, verify that the battery interconnect cables are fully inserted in the sockets.

5.Turn on (close) the battery cabinet circuit breaker.

6.On the power distribution box, place the Manual Bypass Switch in the UTILITY position.

7.Turn on (close) the branch circuit disconnect to apply voltage to the input.

8.Using a voltmeter, verify the expected L1-L2 voltage.

Verify the same voltage is measured at the output receptacles. The BYPASS lamp by the Manual Bypass Switch will light.

9.After verifying proper input voltage to the UPS, turn on the Input circuit breaker located on the distribution box. The green AC Input indicator should illuminate on the UPS’ front panel.

10.Press the On button for 1 second. The BYPASS lamp will light for several seconds before the UPS ON lamp turns on continuously. If the batteries are determined to be charged above 80%, an automatic battery test will run for about 15 seconds.

11.Turn on (close) the output circuit breaker on the rear of the UPS. The UPS lamp on the power distribution box by the Manual Bypass Switch will light. Transfer the switch to the UPS position. The output will now be powered by the UPS.

12.Perform a Manual Battery Test - Press the ON button for 1 second. The front BATTERY lamp will light for about 15 seconds and then return to only the UPS ON and AC INPUT lamps being on.

13.Review all setting options provided by the configuration program. Some changes require that the UPS be Off. If this is the case, these should be programmed before powering the loads. The configuration program is described in 7.0 - Configuration Program.

14.Connect all loads for normal operation.

19

Image 23
Contents Liebert GXT2-6000RTL630 Page Table of Contents Operating Instructions MaintenanceTroubleshooting SpecificationsElectromagnetic Compatibility Important Safety InstructionsPage Glossary of Symbols Introduction System Description Rectifier/Power Factor Correction PFC CircuitBattery Charger InverterDynamic Bypass BatteryDC-to-DC Converter Major Components Top Trim 2 pieces tower use only Status IndicatorsLower Bezel Battery Access Door Upper Main Frame and ElectronicsRelay Card Slot Internal Battery PacksBattery Disconnect External Battery Connector Fans UPS Output Circuit Breaker DB-9 Communication PortConnections Removable Power Distribution BoxBypass To UPS Switch ManualWHAT’S Included Configuration Disk DB-9 port coverAttach Bezels to Top Install the Main CabinetInstallation and Configuration Tower UPS InstallationReturn flanges Retaining Latches Front Innermembers members Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityScrews Apply grease inside Push it into the rack Install the Internal BatteriesUPS or CabinetRemove these screws to release connector Connect the Internal Batteries Using the External ConnectorConnect Input/Output Power Battery Door Captive ScrewsLoosen these three Attach Power Distribution BoxFront of PD-L630 power distribution box Distribution Box Electrical Connections UPSExternal Battery Cabinet Installation Initial START-UP and Electrical Checks What You Will Need GXT2-6000RTL630 Configuration Program FeaturesConfiguration Program Standby/Manual Bypass Button ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators All indicators illuminated for illustration onlyBypass Indicator LED Amber Load Level Indicators 4 Green, 1 AmberBattery Level Indicators 5 Green Fault Indicator LED RedBattery Recharge Mode Normal Mode OperationBattery Mode Operation Bypass Mode OperationDB-9 pin assignment Pin 4 Remote Shutdown on BatteryCommunications Interface Port CommunicationsLiebert’s Ocwebcard DB9 RS232 port covered UPS Intelligent CommunicationsRepo switch connection diagram Remote Emergency Power OffMaintenance Internal BatteryRetaining screw Retaining bracket Internal Battery ReplacementBattery Door Captive Screws 3U Battery Access Door Battery ConnectorsBox to AC Power ConnectionsDisconnect CaptiveReconnect LED status Diagnosis/Audible alarm TroubleshootingIndicator meanings UPS Troubleshooting guideAlarm conditions Troubleshooting guide cont’dBattery run times Auto-Learning Battery Run Times UPS specifications SpecificationsOutput distribution specifications Internal battery specificationsModel Number External battery cabinet specificationsBattery Parameters Page That Ne tIti Ti n