Page 33

Maintenance

11.2AC Power Connections

Power connections may be disconnected from the UPS cabinet via a removable distribution box. This may be a convenient feature if the UPS must be moved a short distance or replaced. This box allows power connections to be conveniently disconnection from the main UPS cabinet. A label is attached to the UPS to describe these procedures.

11.2.1Disconnect

1.DO NOT turn off the branch circuit breaker feeding power the box unless you intend to disconnect all power to the load.

2.Ensure that the Maintenance Bypass Lamp is ON.

3.Switch to the maintenance bypass position.

The load is now unprotected from line disturbances or interruptions.

4.Turn off the UPS using the front panel controls.

a.If needed, push the OFF button for one second once to transfer the load to bypass.

b.Press the OFF button twice within four seconds to turn the UPS off.

5.Turn off the UPS input circuit breaker on the box at the rear of the UPS.

This input circuit breaker cuts off power only from the connector between the box and UPS. The input circuit breaker does not cut off power from the manual bypass switch.

6.Turn off the output circuit breaker on the rear of the UPS.

7.Remove the distribution box from the UPS

a.Loosen all three captive screws until the box releases.

b.Pull box away from the UPS and set the box aside on a padded surface.

8.Loosen the cover over the electrical connections by backing out the three screws one turn each.

9.Slide the cover over the electrical connections.

10.Gently retighten the three screws loosened in Step 8.

Whenever the power distribution box is not attached to the UPS, the cover must be slid over the electrical connections to prevent damage or injury.

! CAUTION

Power is still passing through the power distribution box from the utility supply to the load.

Figure 8 Power distribution box, PD-L630

REMOVE SCREWS

 

COVER COMMUNICATION

 

CONNECTOR PROTECTIVE COVER DO NOT

PRIOR TO INSTALLATION OF BOX ON UPS

-LOOSEN THREE SCREWS 1 TURN - SLIDE COVER TO EXPOSE CONNECTOR -TIGHTEN SCREWS GENTLY UPON REMOVAL OF BOX FROM UPS -LOOSEN THREE SCREWS 1 TURN -SLIDE COVER TO REACH END SCREW AND

-TIGHTEN SCREWS GENTLY

Maintenance

Maintenance

Bypass Switch

Bypass Lamps

 

PS

 

AVAILA

ANENCE BYPASS

 

AVAILABLE

Protective

 

 

 

UTILITY

 

 

 

 

UPS

Cover Over

ON

 

 

 

Connectors

OUTPUT

 

 

 

 

ON

 

 

 

BREAKER

OUTPUT

 

20A

240V~/T

BREAKER

 

OFF

 

20A

240V~/T

 

OFF

 

 

 

 

 

Captive

Screws

 

 

 

 

 

 

INPPUT

BREAKER

 

 

 

MANUAL BBYPASS POWER TO

(attach

 

30A

OFF

 

 

ON

 

 

 

 

 

 

OUTPUT ONLY CB

DOES NOT

 

 

 

 

 

CONNECT

box to

UPS)

Rear View

Front View

29

Image 33
Contents Liebert GXT2-6000RTL630 Page Table of Contents Troubleshooting MaintenanceSpecifications Operating InstructionsElectromagnetic Compatibility Important Safety InstructionsPage Glossary of Symbols Introduction Battery Charger Rectifier/Power Factor Correction PFC CircuitInverter System DescriptionBattery DC-to-DC ConverterDynamic Bypass Lower Bezel Battery Access Door Upper Top Trim 2 pieces tower use only Status IndicatorsMain Frame and Electronics Major ComponentsBattery Disconnect External Battery Connector Internal Battery PacksFans UPS Output Circuit Breaker DB-9 Communication Port Relay Card SlotBypass To UPS Switch Removable Power Distribution BoxManual ConnectionsWHAT’S Included Configuration Disk DB-9 port coverInstallation and Configuration Install the Main CabinetTower UPS Installation Attach Bezels to TopInstalling the Adjustable Rack-Mount Kit-Sold Separately Rack-Mount UPS InstallationQuantity Return flanges Retaining Latches Front Innermembers membersScrews UPS or Install the Internal BatteriesCabinet Apply grease inside Push it into the rackConnect Input/Output Power Connect the Internal Batteries Using the External ConnectorBattery Door Captive Screws Remove these screws to release connectorAttach Power Distribution Box Front of PD-L630 power distribution boxLoosen these three Distribution Box Electrical Connections UPSExternal Battery Cabinet Installation Initial START-UP and Electrical Checks GXT2-6000RTL630 Configuration Program Features Configuration ProgramWhat You Will Need Controls and Indicators ON/Alarm Silence/Manual Battery Test ButtonAll indicators illuminated for illustration only Standby/Manual Bypass ButtonBattery Level Indicators 5 Green Load Level Indicators 4 Green, 1 AmberFault Indicator LED Red Bypass Indicator LED AmberBattery Mode Operation Normal Mode OperationBypass Mode Operation Battery Recharge ModeCommunications Interface Port Pin 4 Remote Shutdown on BatteryCommunications DB-9 pin assignmentLiebert’s Ocwebcard DB9 RS232 port covered UPS Intelligent CommunicationsRepo switch connection diagram Remote Emergency Power OffMaintenance Internal BatteryBattery Door Captive Screws 3U Battery Access Door Internal Battery ReplacementBattery Connectors Retaining screw Retaining bracketDisconnect AC Power ConnectionsCaptive Box toReconnect Troubleshooting Indicator meaningsLED status Diagnosis/Audible alarm UPS Troubleshooting guideAlarm conditions Troubleshooting guide cont’dBattery run times Auto-Learning Battery Run Times UPS specifications SpecificationsOutput distribution specifications Internal battery specificationsExternal battery cabinet specifications Battery ParametersModel Number Page Iti Ne tTi n That