Liebert GXT2-6000RTL630 user manual External Battery Cabinet Installation

Page 22

Installation and Configuration

5.5External Battery Cabinet Installation

Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed on one side of the UPS or stacked beneath the UPS.

! CAUTION

The external battery cabinet(s) are heavy (see 13.0 - Specifications). External battery cabinets can be used in rack-mount or tower configuration. Take proper precautions when lifting them.

1.Visually inspect the external battery cabinet for freight damage. Report damage to the carrier and your local dealer or Liebert representative.

2.For slide rail installations, first remove the top/side fin. Top/side fin slides forward and then lift up to remove. Optional rack-mount handles are shipped with the external battery cabinet and may be installed at this time if desired.

3.Securing hardware and slide rails are sold separately. Please contact your local dealer or Liebert representative for these additional options and any assistance needed. Fasten the slides into position with the screws per the instructions included with the slide rails.

4.Use the enclosed support bases for the tower option to prevent tip-over. One additional set of support base extensions ships with each external battery cabinet.

5.Connect the supplied external battery cabinet cable to the rear of the external battery cabinet, then to the rear of the UPS.

6.The UPS is now equipped with additional backup battery run time. For approximate battery run times, refer to Table 5.

! CAUTION

Do not turn on (close) the battery cabinet circuit breaker yet. Complete the installation first.

NOTE

You must use the included configuration program to program the UPS for the number of external battery cabinets connected. Instructions for the configuration program are in 7.0 - Configuration Program.

3U

+ -

2U

2U

Spacers added to support base to accommodate additional battery cabinets

18

Image 22
Contents Liebert GXT2-6000RTL630 Page Table of Contents Specifications MaintenanceTroubleshooting Operating InstructionsImportant Safety Instructions Electromagnetic CompatibilityPage Glossary of Symbols Introduction Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger System DescriptionDC-to-DC Converter BatteryDynamic Bypass Main Frame and Electronics Top Trim 2 pieces tower use only Status IndicatorsLower Bezel Battery Access Door Upper Major ComponentsFans UPS Output Circuit Breaker DB-9 Communication Port Internal Battery PacksBattery Disconnect External Battery Connector Relay Card SlotManual Removable Power Distribution BoxBypass To UPS Switch ConnectionsConfiguration Disk DB-9 port cover WHAT’S IncludedTower UPS Installation Install the Main CabinetInstallation and Configuration Attach Bezels to TopQuantity Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately Return flanges Retaining Latches Front Innermembers membersScrews Cabinet Install the Internal BatteriesUPS or Apply grease inside Push it into the rackBattery Door Captive Screws Connect the Internal Batteries Using the External ConnectorConnect Input/Output Power Remove these screws to release connectorFront of PD-L630 power distribution box Attach Power Distribution BoxLoosen these three UPS Distribution Box Electrical ConnectionsExternal Battery Cabinet Installation Initial START-UP and Electrical Checks Configuration Program GXT2-6000RTL630 Configuration Program FeaturesWhat You Will Need All indicators illuminated for illustration only ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators Standby/Manual Bypass ButtonFault Indicator LED Red Load Level Indicators 4 Green, 1 AmberBattery Level Indicators 5 Green Bypass Indicator LED AmberBypass Mode Operation Normal Mode OperationBattery Mode Operation Battery Recharge ModeCommunications Pin 4 Remote Shutdown on BatteryCommunications Interface Port DB-9 pin assignmentUPS Intelligent Communications Liebert’s Ocwebcard DB9 RS232 port coveredRemote Emergency Power Off Repo switch connection diagramInternal Battery MaintenanceBattery Connectors Internal Battery ReplacementBattery Door Captive Screws 3U Battery Access Door Retaining screw Retaining bracketCaptive AC Power ConnectionsDisconnect Box toReconnect Indicator meanings TroubleshootingLED status Diagnosis/Audible alarm Troubleshooting guide UPSTroubleshooting guide cont’d Alarm conditionsBattery run times Auto-Learning Battery Run Times Specifications UPS specificationsInternal battery specifications Output distribution specificationsBattery Parameters External battery cabinet specificationsModel Number Page Ti n Ne tIti That