Bay Technical Associates V80 PDI-2 Specifications V79 PDI-1 Switch Input Status Module

Page 7

These optically isolated inputs provide an efficient means for the monitoring of external process and control functions. All functions provided by the board are programmable through a series of detailed configuration menus. Additional functionality is made available through the use of BayTech or user provided application software. Input connections to the PDI-2 are made through a standard DC-37F connector.

2 SPECIFICATIONS

2.1V79 PDI-1 SWITCH INPUT STATUS MODULE

(typical for 25o C unless otherwise noted)

INPUTS: 16 with individual ground returns or common (single-point) ground.

DRIVE DISTANCE: Up to 1000 Ohms cable resistance, for

example: AWG 36 - 2400 ft., AWG 24 - 15000 ft., AWG 22 - 62000 ft.

POWER REQUIREMENTS: +5VDC, 40 ma typical (provided by M16/M8 pwr supply).

DEBOUNCE: 0 to 60000 ms (software selectable).

ENVIRONMENTAL:

Operating temperature range: 0o to 70o C

Storage temperature range: -40oto 85o C

Humidity: 5% to 95% non-condensing

3

Image 7
Contents BayTech Publication #U140E105 Page Table of Contents Reporting Method General V79 PDI-1 Module Specifications V79 PDI-1 Switch Input Status Module V80 PDI-2 Optically Isolated Input Module Cabling InstallationPDI-2 AC Input Setup Operation Reporting Method USER-PROGRAMMABLE FeaturesSampling Setup Reporting SetupReport Interval Report Start TimeHost Address Data Commands Dynamic ConfigurationTerminating Characters Take a single sample for Ports Clear Event Counter Command Clear Event Buffer CommandClear Event Latch Data Report Event Counter Command Report ALL Buffered Events CommandReport Event Duration Command Report Event Counter and Reset Command Report Event Latch Data CommandReport Event Latch Data and Reset Command Event Sample Reporting Report a Single Buffered Event CommandPage Event Sample Presentation 115,1 1320 11/18/93 MENU-DRIVEN Configuration ConfigurationPage Configuration Main Menu Module Status SET Latch Polarity Select Reporting Method Report Start Time Report Interval Enable / Disable Time Tagging Dynamic Configuration Commands Exit Dynamic Configuration Procedure and Commands Reporting Method Command Debounce Delay CommandTime TAG Command Front Panel Configuration Appendix a DATA/CONFIGURATION Command Summary Appendix B Eprom Upgrade Appendix C V79 PDI-1 Mechanical Layout Page Page Appendix D V80 PDI-2 Mechanical Layout Page Page Appendix E Index Fifo Page