For example, if the PDI is installed in a non-cascaded unit as Module 2 and you are using the default port select code ($BT), send $BT2<cr>$CONFIG<cr> to enter into configuration mode. No characters should be typed between $BT2<cr> and $CONFIG<cr>. If this happens, the entire configuration sequence will be discarded and you will have to send the configuration sequence again.

NOTE: All commands must be in uppercase.

To access the menu-driven configuration mode of the PDI from the service port, use the following procedure:

1.Connect a terminal to the EIA-232service port and configure the terminal's serial parameters to 9600 baud rate, 8 word size, 1 stop bit, and no parity.

2.Connect to the PDI by sending $BAYTECH, the desired module number (2 to 16), and Carriage Return or Line Feed.

3.Access configuration mode by sending $CONFIG<cr>. Following the example on the previous page, you would send $BAYTECH2<cr>$CONFIG<cr> to configure Module 2.

NOTE: All commands must be in uppercase.

20

Image 24
Contents BayTech Publication #U140E105 Page Table of Contents Reporting Method General V79 PDI-1 Module Specifications V79 PDI-1 Switch Input Status Module V80 PDI-2 Optically Isolated Input Module Installation CablingPDI-2 AC Input Setup Operation USER-PROGRAMMABLE Features Sampling SetupReporting Setup Reporting MethodReport Start Time Report IntervalHost Address Dynamic Configuration Data CommandsTerminating Characters Take a single sample for Ports Clear Event Buffer Command Clear Event Counter CommandClear Event Latch Data Report ALL Buffered Events Command Report Event Counter CommandReport Event Duration Command Report Event Latch Data Command Report Event Counter and Reset CommandReport Event Latch Data and Reset Command Report a Single Buffered Event Command Event Sample ReportingPage Event Sample Presentation 115,1 1320 11/18/93 Configuration MENU-DRIVEN ConfigurationPage Configuration Main Menu Module Status SET Latch Polarity Select Reporting Method Report Start Time Report Interval Enable / Disable Time Tagging Dynamic Configuration Commands Exit Dynamic Configuration Procedure and Commands Debounce Delay Command Reporting Method CommandTime TAG Command Front Panel Configuration Appendix a DATA/CONFIGURATION Command Summary Appendix B Eprom Upgrade Appendix C V79 PDI-1 Mechanical Layout Page Page Appendix D V80 PDI-2 Mechanical Layout Page Page Appendix E Index Fifo Page