Outback Power Systems manual PG1 Charge AUX PG3 ADV/DC/AUX Control

Page 27

ADV/DC/PAGE 1----------------

choose category

ADV BAT SHUNT PG2

ADV/DC/PAGE 2-----------------

choose category:

PG1 CHARGE AUX PG3

ADV/DC/AUX CONTROL--------

currently:

Auto

On

DOWN

OFF AUTO

ON

ADV/DC/AUX HIGH VOLT------

high volts

vdc

DOWN INC

DEC TOP

ADV/DC/AUX LOW VOLT------

low volts

vdc

DOWN INC DEC

TOP

ADV/DC/AUX SOC HIGH--------

SOC high

%

DOWN INC

DEC TOP

Press the <PG2> soft key.

Press the <AUX> soft key.

Pressing the <OFF> or <ON> soft keys will manually shut the AUX off (the relay is open) or turn it on (the relay is closed), respectively. In AUTO mode, the AUX is controlled by user- determined set points. After setting the AUX control, press the <DOWN> soft key.

Use the high volts screen and the <INC> and <DEC> soft keys to control the AUX by a high voltage value. Press the <DOWN> soft key to view the low volts screen.

Use the low volts screen and the <INC> and <DEC> soft keys to control the AUX by a low voltage value. Press the <DOWN> soft key to view the SOC high % screen.

Use the <INC> and <DEC> soft keys to change the SOC high percentage to trigger the AUX function. Press the <DOWN> soft key to view the SOC low % screeen.

26

Image 27
Contents NetTM DC Warranty About OutBack Power SystemsFLEXnet DC User’s Guide 2007 All rights reserved January DisclaimerDate and Revision Contact InformationTable of Contents Introduction OutBack Power Systems FLEXnet DCSystem Overview Reading the FLEXnet DC Postion wiring blockFLEXNet DC package includes Installing the FLEXnet DCConnect each twisted pair to a shunt Wiring Block Connections Torque ValuesWhite to BAT Black to BAT + Installing the FLEXnet DC Maximum amp charged Maximum battery voltageFLEXNet DC Measurements KiloWattsUser Adjustable Set Points Logged DataData Logging Programming and Using the Mate for FLEXNet DC Operations Typical charge cycle All unused channels should be set to disabledFLEXNet DC Modes Charge CycleGreen Yellow RED Invert Logic Hi Set Point Satisfied Auto ModeProgramming the Auxiliary Relay Relay LogicMate Screens Readings Press the DC soft key to view the status of the FlexNet DCDown Status STATUS/FN Stats Meter Shunt Batt TOP STATUS/DC/SHUNT a Down UP Reset Down UP Reset TOP STATUS/DC/BATT UP TOP Status ADV BAT Shunt PG2 Press the ADV soft key Press the DC soft key Press the Charge soft keyPG1 Charge AUX PG3 ADV/DC/AUX Control ADV/DC/AUX SOC LOW PG2 Reset CLR Main Technical Notes Battery Charge Factor BCFFLEXnet Products Year Limited WarrantyRevision.2007-08-29 Outback Power Systems Inc 19009 62nd Ave. NE Limited Warranty RegistrationREV B