MGE UPS Systems 4000 RT Communication ports, Connection to the RS 232 communication port

Page 16

2. Installation

2.5 Communication ports

Pulsar MX RT provides 3 communication methods that can be used simultaneously:

2 COM ports provide RS232 or USB communications using MGE UPS SYSTEMS SHUT protocol. Compatible with most power management software applications available into the enclosed Solution Pac CD-Rom. Please, note that both ports cannot be used at the same time.

The output contact port is used for basic signaling or for protection of IT systems like IBM iSeries (formerly AS400) and more.

The slot is compatible with any MGE UPS SYSTEMS communication card (check www.mgeups.com web site for the complete list of compatible cards).

Connection to the RS 232 communication port

SWITCHED

SWITCHED

GROUP 2

GROUP 1

42

PARALLEL

1 - Connect the RS232 (42) communications cable to the serial port on the computer equipment.

2 - Connect the other end of the communication cable (42) to the RS232 (13) communications port on the UPS.

The UPS can now communicate with various MGE UPS SYSTEMS power management application software. Please note that the configuration software is included with Personal Solution Pac for Windows.

RS232 CONTACTS BAT NO. RPO

13

Connection to the communication port by relays (14)

(see page 8)

 

5

4

3

2

1

14

 

 

9

8

7

6

 

n.c.

n.o.

 

n.o.

 

n.o.

n.o.

 

common

 

 

 

 

Pin 1, 2: not used,

Pin 3: remote Power Off signal (5 to 27 V DC, 10 mA max),

Pin 4: operation on mains (not on battery),

Pin 5: user common,

Pin 6: operation on automatic by-pass,

Pin 7: low battery,

Pin 8: load protected,

Pin 9: operation on battery.

n.o.: contact normally open.

n.c.: contact normally closed.

When the status is active, the contact between the common (Pin 5) and the relevant information pin is closed.

Output relays specifications

Voltage: 48 V DC max,

Current: 2 A max,

Power: 62,5 VA, 30 W.

Example: for 48 V DC, Imax=625 mA

34008030EN/AA - Page 16

Image 16
Contents Pulsar MX 34008030EN/AA Introduction Environmental protectionSubstances PackingPictograms Contents Troubleshooting Technical specifications GlossaryDimensions H x W x D in mm / Inches PresentationStandard positions Tower position Rack positionRear panels Pulsar MX EXB RT optional battery modulePulsar MX 4000 RT / 5000 RT Display and control panel OptionsRack mounting kit Telescopic rails, 639 mm to 1005 mmPulsar MX RT Pulsar MX RT ModularEasy ModularEasyPulsar MX RT Battery Integration System Battery extension cable 1,8 m / 6 ftBattery extensions for Pulsar MX RT Pulsar MX EXB RT Pulsar MX 4000 RT Min 29 min 53 minUnpacking and contents check InstallationInternal battery connection Battery start-up Installation in tower position Installation in rack position UPS or battery module rack mounting optional rails required Connection to the RS 232 communication port Communication portsConnection to the communication port by relays Remote power off contact normally open Remote Power Off communication portRemote power off contact normally closed Required protective devices and cable cross-sections Recommended upstream protectionRecommended downstream protection Required cable cross-sectionsConnection of input/output power cables on UPS terminals Always connect first the earthing wireConnection of IEC cables to output receptacles Operation Initial start-upFinal start-up sequence UPS personalisationNormal mode Eco modeEquipments are supplied in ECO mode Operating modesOperation on battery power Transfer to battery powerLow battery warning End of backup timeUPS shutdown Press the 0 button 28 more than 3sAccess to measurements and personalisation data Access to measurementsMaintenance menu Display organisationLocal settings Output settingsON/OFF settings UPS set-upPersonalisation using external software MaintenanceBattery settings Troubleshooting Troubleshooting Leds 21But the operation is downgraded By the UPSIndication Diagnostic Correction Display Signification CorrectionSecure your installation power continuity Life Cycle Monitoring LCMDescription Get free offersReset or disable LCM Hot swapping the power sub-module MaintenanceHot swapping the battery sub-module Reconnecting the battery sub-module MaintenanceReturn to normal operation Test positionTraining centre Hz training centreTechnical specifications AppendicesGlossary 34008030EN/AA 34008030EN/AA