MGE UPS Systems 4000 RT Reconnecting the battery sub-module, Maintenance, Test position

Page 33

7. Maintenance

Reconnecting the battery sub-module :

Carry out the above instructions in reverse order.

To ensure safety and high performance, use only batteries supplied by MGE UPS SYSTEMS.

7.3 Maintenance on a UPS equipped with the ModularEasy MX module

Before any action on the manual bypass (61) located on the ModularEasy module front panel, always check that the inverter is stopped (press the "0" button more than 3 seconds).

The equipments should be powered via the Normal AC source, and not protected by the UPS.

TEST

1

NORMAL

BYPASS

 

 

TEST

3

NORMAL

BYPASS

The ModularEasy module makes possible to service or even replace the UPS without affecting the connected equipments (HotSwap function).

Maintenance:

1 - Set the manual bypass (61) to the Bypass

61

position.

 

 

The equipments are supplied directly with

 

Normal AC source.

 

2 - Check the UPS main bezel and wait the

 

LCD stops (30 seconds).

 

3 - Padlock the manual bypass (61) on

 

bypass position.

 

4 - The UPS can now be disconnected and

 

replaced.

 

Return to normal operation:

 

5 - Properly wire the UPS (see section 2), and

 

connect internal batteries.

 

6 - Set the manual bypass (61) to the Test

 

ESC

 

30

32

34

6

TEST

NORMAL

BYPASS

I

O

7

 

29

 

position then to Normal position : the

equipments are powered via the Normal AC

source, but not protected by the UPS..

7 - Push the "I" button (29) till the buzzer

beeps. LED (20) is ON, and LEDs (30), (32)

and (34) (see page 9) are green: the

equipments are protected by the UPS.

Test position:

It is also possible to fully test the UPS before

the manual bypass (61) is set on Normal

position.

To check the UPS, after step 5, follow this

operating method:

6bis - Set the manual bypass (61) to the test

position.

7bis - Push the "I" button (29) till the buzzer

beeps. After UPS Internal test, LED’s (30),

(32) and (22) should be ON: no failure has

been detected.

To return to normal operation:

Push the "0" button (28) more than 3

seconds.

Then follow the operating method from step

6.

34008030EN/AA - Page 33

Image 33
Contents Pulsar MX 34008030EN/AA Environmental protection IntroductionSubstances PackingPictograms Contents Technical specifications Glossary TroubleshootingPresentation Dimensions H x W x D in mm / InchesStandard positions Tower position Rack positionPulsar MX EXB RT optional battery module Rear panelsPulsar MX 4000 RT / 5000 RT Options Display and control panelRack mounting kit Telescopic rails, 639 mm to 1005 mmModularEasy Pulsar MX RT Pulsar MX RT ModularEasyPulsar MX RT Battery extension cable 1,8 m / 6 ft Battery Integration SystemBattery extensions for Pulsar MX RT Pulsar MX EXB RT Pulsar MX 4000 RT Min 29 min 53 minInstallation Unpacking and contents checkInternal battery connection Battery start-up Installation in tower position Installation in rack position UPS or battery module rack mounting optional rails required Communication ports Connection to the RS 232 communication portConnection to the communication port by relays Remote Power Off communication port Remote power off contact normally openRemote power off contact normally closed Recommended upstream protection Required protective devices and cable cross-sectionsRecommended downstream protection Required cable cross-sectionsAlways connect first the earthing wire Connection of input/output power cables on UPS terminalsConnection of IEC cables to output receptacles Initial start-up OperationFinal start-up sequence UPS personalisationEco mode Normal modeEquipments are supplied in ECO mode Operating modesTransfer to battery power Operation on battery powerLow battery warning End of backup timePress the 0 button 28 more than 3s UPS shutdownAccess to measurements Access to measurements and personalisation dataMaintenance menu Display organisationOutput settings Local settingsON/OFF settings UPS set-upMaintenance Personalisation using external softwareBattery settings Troubleshooting Leds 21 TroubleshootingBut the operation is downgraded By the UPSDisplay Signification Correction Indication Diagnostic CorrectionLife Cycle Monitoring LCM Secure your installation power continuityDescription Get free offersReset or disable LCM Maintenance Hot swapping the power sub-moduleHot swapping the battery sub-module Maintenance Reconnecting the battery sub-moduleReturn to normal operation Test positionHz training centre Training centreAppendices Technical specificationsGlossary 34008030EN/AA 34008030EN/AA