MGE UPS Systems 4000 RT Maintenance, Personalisation using external software, Battery settings

Page 27

4. Access to measurements and personalisation data

Battery settings

Function

Factory setting

Options

Comments

 

 

 

 

Auto Battery Test

Everyweek

No test / everyday /

 

 

 

everyweek /everymonth

 

 

 

 

 

Low Batt Warning

20%

0 to 100%

1% increment

 

 

 

 

User Batt Settings

UPS reads number of

From 0 to 40 Ah

5 Ah increment

 

battery modules

 

 

 

connected

 

 

 

 

 

 

Deep Disch Protect

Yes

No

Protection against deep discharge.

 

 

 

If disable, MGE UPS SYSTEMS

 

 

 

warranty will be void

 

 

 

 

4.5 Maintenance

Function

Sub-Function

Option / Display

Comments

 

 

 

 

Model

Power Module

SN: xxxxxxxxx

Serial number

 

 

SOFT: xxx

Soft version

 

Frame

 

NT: xxx

Technical level

 

 

 

 

 

 

Alarm History

Read

Description

10 alarms can be stored

 

 

Date Hour

automatically

 

 

Alarm xxx

 

 

 

 

 

 

Erase

No / Yes

 

 

 

 

 

Manual Batt Test

Manual Battery Test

No / Yes

 

 

 

 

 

Led & Buzzer Test

Led & Buzzer Test

No / Yes

 

 

 

 

 

Life Cycle Monitoring

LCM

Enable / Disable

Life cycling monitoring alarms

 

 

 

 

Statistics

Auto Statistics

Statistics

You need to register at

 

 

 

www.mgeups.com/Icm to get the

 

Custom Statistics

Reset Date ?

 

code and get access to free statistics

 

 

Are you sure ?

 

 

 

 

 

 

 

Operation Limits

Operation Limits

 

Automatic alarms displayed when

 

 

 

UPS is operating near the limits

 

 

 

 

4.6Personalisation using external software

Insert the Solution-PacCD-ROM in the drive.

On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the Personal Solution-Pacsoftware.

Then select "Settings", "Advanced settings" and "UPS settings".

Note that only the Windows versions of the Personal Solution-Pacsoftware offer this possibility.

34008030EN/AA - Page 27

Image 27
Contents Pulsar MX 34008030EN/AA Packing IntroductionEnvironmental protection SubstancesPictograms Contents Technical specifications Glossary TroubleshootingTower position Rack position Dimensions H x W x D in mm / InchesPresentation Standard positionsPulsar MX EXB RT optional battery module Rear panelsPulsar MX 4000 RT / 5000 RT Telescopic rails, 639 mm to 1005 mm Display and control panelOptions Rack mounting kitModularEasy Pulsar MX RT Pulsar MX RT ModularEasyPulsar MX RT Pulsar MX EXB RT Pulsar MX 4000 RT Min 29 min 53 min Battery Integration SystemBattery extension cable 1,8 m / 6 ft Battery extensions for Pulsar MX RTInstallation Unpacking and contents checkInternal battery connection Battery start-up Installation in tower position Installation in rack position UPS or battery module rack mounting optional rails required Communication ports Connection to the RS 232 communication portConnection to the communication port by relays Remote Power Off communication port Remote power off contact normally openRemote power off contact normally closed Required cable cross-sections Required protective devices and cable cross-sectionsRecommended upstream protection Recommended downstream protectionAlways connect first the earthing wire Connection of input/output power cables on UPS terminalsConnection of IEC cables to output receptacles UPS personalisation OperationInitial start-up Final start-up sequenceOperating modes Normal modeEco mode Equipments are supplied in ECO modeEnd of backup time Operation on battery powerTransfer to battery power Low battery warningPress the 0 button 28 more than 3s UPS shutdownDisplay organisation Access to measurements and personalisation dataAccess to measurements Maintenance menuUPS set-up Local settingsOutput settings ON/OFF settingsMaintenance Personalisation using external softwareBattery settings By the UPS TroubleshootingTroubleshooting Leds 21 But the operation is downgradedDisplay Signification Correction Indication Diagnostic CorrectionGet free offers Secure your installation power continuityLife Cycle Monitoring LCM DescriptionReset or disable LCM Maintenance Hot swapping the power sub-moduleHot swapping the battery sub-module Test position Reconnecting the battery sub-moduleMaintenance Return to normal operationHz training centre Training centreAppendices Technical specificationsGlossary 34008030EN/AA 34008030EN/AA