4. Access to measurements and personalisation data
4.4 UPS set-up
Local settings
Function | Factory setting | Options |
|
|
|
Language | English | French, German, Italian, Portuguese, Spanish |
|
|
|
Date / Time Format | International | US |
|
| |
|
|
|
Date / Time Change | GMT + 1 | |
| (Continental Europe) |
|
|
|
|
Audible Alarm | Yes | No |
|
|
|
Output settings
Function | Factory setting | Options | Comments |
|
|
|
|
Output Voltage | 230 V | 200 V / 208 V / 220 V / |
|
|
| 240 V / 250 V |
|
|
|
|
|
Freq Converter | Disable | Enable |
|
|
|
|
|
Output Frequency | 50 Hz | 60 Hz | User selectable under frequency- |
|
|
| converter mode |
|
|
|
|
Eco Mode | DisablE | Enable | See glossary |
|
|
|
|
Slew Rate | 1 Hz / sec. | 0.5 Hz / sec. |
|
|
|
|
|
Bypass Transfer | Yes | No | Transfer to bypass if Normal AC |
If bypass Ac nok? |
|
| source is out of tolerance |
|
|
|
|
Interrupt Time | 10 ms | 20 ms, ...... , 200 ms | Break time calibration during load |
|
|
| transfer on Normal AC source out of |
|
|
| tolerance |
|
|
|
|
Overload Prealarm | 105 % | 40 %, 50 %, 70 % | Alarm if threshold is overrun |
|
|
|
|
Redundancy Mode | No | Yes | On parallel sequence : Alarm if |
|
|
| redundancy loss |
|
|
|
|
ON/OFF settings
Function | Factory setting | Options | Comments |
|
|
|
|
Cold Start | Disable | Enable | Start on battery |
|
|
|
|
Forced Reboot | Enable | Disable | Enables automatic restart of the |
|
|
| system even if Normal AC source is |
|
|
| restored before the end of the |
|
|
| shutdown sequence |
|
|
|
|
Auto Restart | Enable | Disable | UPS restarts automatically when |
|
|
| Normal AC source is restored |
|
|
|
|
Energy Saving | Disable | Enable | Automatic shutdown on battery if |
|
|
| output load level < 10 % |
|
|
|
|
Sleep Mode | Enable | Disable |
|
|
|
|
|
Remote Command | Enable | Disable | Enables consideration of shutdown |
|
|
| or restart orders from software to be |
|
|
| authorised |
|
|
|
|