4. Access to measurements and personalisation data

4.4 UPS set-up

Local settings

Function

Factory setting

Options

 

 

 

Language

English

French, German, Italian, Portuguese, Spanish

 

 

 

Date / Time Format

International

US (MM-DD-YYYY/HH:MM AM/PM)

 

(DD-MM-YYYY/HH :MM)

 

 

 

 

Date / Time Change

GMT + 1

MM-DD-YYYY/HH :MM adjustable

 

(Continental Europe)

 

 

 

 

Audible Alarm

Yes

No

 

 

 

Output settings

Function

Factory setting

Options

Comments

 

 

 

 

Output Voltage

230 V

200 V / 208 V / 220 V /

 

 

 

240 V / 250 V

 

 

 

 

 

Freq Converter

Disable

Enable

 

 

 

 

 

Output Frequency

50 Hz

60 Hz

User selectable under frequency-

 

 

 

converter mode

 

 

 

 

Eco Mode

DisablE

Enable

See glossary

 

 

 

 

Slew Rate

1 Hz / sec.

0.5 Hz / sec.

 

 

 

 

 

Bypass Transfer

Yes

No

Transfer to bypass if Normal AC

If bypass Ac nok?

 

 

source is out of tolerance

 

 

 

 

Interrupt Time

10 ms

20 ms, ...... , 200 ms

Break time calibration during load

 

 

 

transfer on Normal AC source out of

 

 

 

tolerance

 

 

 

 

Overload Prealarm

105 %

40 %, 50 %, 70 %

Alarm if threshold is overrun

 

 

 

 

Redundancy Mode

No

Yes

On parallel sequence : Alarm if

 

 

 

redundancy loss

 

 

 

 

ON/OFF settings

Function

Factory setting

Options

Comments

 

 

 

 

Cold Start

Disable

Enable

Start on battery

 

 

 

 

Forced Reboot

Enable

Disable

Enables automatic restart of the

 

 

 

system even if Normal AC source is

 

 

 

restored before the end of the

 

 

 

shutdown sequence

 

 

 

 

Auto Restart

Enable

Disable

UPS restarts automatically when

 

 

 

Normal AC source is restored

 

 

 

 

Energy Saving

Disable

Enable

Automatic shutdown on battery if

 

 

 

output load level < 10 %

 

 

 

 

Sleep Mode

Enable

Disable

 

 

 

 

 

Remote Command

Enable

Disable

Enables consideration of shutdown

 

 

 

or restart orders from software to be

 

 

 

authorised

 

 

 

 

34008030EN/AA - Page 26

Image 26
Contents Pulsar MX 34008030EN/AA Substances IntroductionEnvironmental protection PackingPictograms Contents Troubleshooting Technical specifications GlossaryStandard positions Dimensions H x W x D in mm / InchesPresentation Tower position Rack positionPulsar MX 4000 RT / 5000 RT Pulsar MX EXB RT optional battery moduleRear panels Rack mounting kit Display and control panelOptions Telescopic rails, 639 mm to 1005 mmPulsar MX RT ModularEasyPulsar MX RT Pulsar MX RT ModularEasy Battery extensions for Pulsar MX RT Battery Integration SystemBattery extension cable 1,8 m / 6 ft Pulsar MX EXB RT Pulsar MX 4000 RT Min 29 min 53 minInternal battery connection Battery start-up InstallationUnpacking and contents check Installation in tower position Installation in rack position UPS or battery module rack mounting optional rails required Connection to the communication port by relays Communication portsConnection to the RS 232 communication port Remote power off contact normally closed Remote Power Off communication portRemote power off contact normally open Recommended downstream protection Required protective devices and cable cross-sectionsRecommended upstream protection Required cable cross-sectionsConnection of input/output power cables on UPS terminals Always connect first the earthing wireConnection of IEC cables to output receptacles Final start-up sequence OperationInitial start-up UPS personalisationEquipments are supplied in ECO mode Normal modeEco mode Operating modesLow battery warning Operation on battery powerTransfer to battery power End of backup timeUPS shutdown Press the 0 button 28 more than 3sMaintenance menu Access to measurements and personalisation dataAccess to measurements Display organisationON/OFF settings Local settingsOutput settings UPS set-upBattery settings MaintenancePersonalisation using external software But the operation is downgraded TroubleshootingTroubleshooting Leds 21 By the UPSIndication Diagnostic Correction Display Signification CorrectionDescription Secure your installation power continuityLife Cycle Monitoring LCM Get free offersReset or disable LCM Hot swapping the battery sub-module MaintenanceHot swapping the power sub-module Return to normal operation Reconnecting the battery sub-moduleMaintenance Test positionTraining centre Hz training centreTechnical specifications AppendicesGlossary 34008030EN/AA 34008030EN/AA