American Power Conversion MX28B2400, MX28B4800 manual AC Input Wiring

Page 15

input. The AC wiring, from the AC input terminal block connections to the hot-pluggable AC input connector for each rectifier, is factory installed.

The AC input enclosure, located at the top rear of the MX28B rectifier bay, is provided with nine

¼-inch pilot holes in the top plate. Remove the ac input enclosure from the box frame in order to punch or drill the appropriate number of conduit openings for the conduit size(s) desired. Do not leave the ac input enclosure in place when punching or drilling holes in order to prevent metal pieces from falling into the power system.

AC wiring passing through the conduit will be routed through the access opening in the ac input enclosure into the vertical wiring channel where safety ground bar and rectifier input terminal blocks are located. The terminal block(s) is labeled as Rectifier 1 through Rectifier 4 with each position having inputs designated “L1” and “L2/N” for connection of the two ac wires Figure 3.3-1.Each terminal block represents connections for one shelf, with positions 1 through 4 corresponding to the rectifier shelf positions numbered from left to right as viewed from the front.

Figure 3.3-1 AC Input Wiring

The suggested wire size is #10 AWG rated at 90°C or higher; however, the ambient temperature and number of wires in a conduit must also be considered in accordance with NEC requirements. It is suggested that feeds for four rectifiers (8 wires) and one safety ground wire be run in a one-inch conduit; however, be sure to follow any local electrical wiring codes.

MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual

Page 10

Image 15
Contents VDC Power Systems Table of Contents Commissioning and Preventive Maintenance APC Worldwide Customer Support Limited Product Warranty Revision Date Description Revision HistoryGeneral Precautions Safety FirstHow to Use This Manual IntroductionGeneral Information 1 MX28B-1200 -48 VDC Power Plant Rectifier Bay 2 MX28B Block Diagram Room / Location InstallationMechanical Installation Unpacking EquipmentMounting Power Bus Connections2 MX28B-1200-2400 has a maximum 5 Circuit Breaker / LVD Expansion Board Circuit Breaker/LVD Ribbon Cable ConnectionsAC Power Connections Fuse Alarm Ribbon Cable ConnectionsVentilation 1 AC Input Wiring Planning the Battery Installation Battery Connections1 Battery Cable Connection Locations Connecting the Battery CablesDC System Grounding 2 Battery Probe ConnectionDC Plug-in Circuit Breakers DC Power Output Over-Current ProtectionBreaker Part Number Rating 2 Plug-in Circuit Breakers 4 Bolt-in Circuit Breakers DC Bolt-in Circuit Breakers5 Telecom Fuses Telecom FusesPlug-in Circuit Breaker Installation Installation of Circuit Breakers and Fuses2 Circuit Breaker Alarm Wiring Bolt-in Circuit Breaker InstallationGMT Fuse Installation Telecom Fuse InstallationCircuit Breaker Connections 60-100 Amps Load ConnectionsCable Size Considerations Circuit Breaker Connections 1 to 50 AmpsSmart Cable DB9 Connection Monitoring and Relay Output ConnectionsGMT Fuse Connections Front Panel DB9 ConnectionRelay Output Connections RJ45 Ethernet ConnectorNO-NC-C External Alarm Input ConnectionsRectifier Module Installation Pre-Commissioning Inspection Commissioning and Preventive MaintenanceElectrical Installation Battery Visual and Safety InspectionAC Power Up CommissioningInitial Set-up LVD Test DC Power UpBattery Power Up Rectifier TestOutput Relays Battery Temperature CompensationCircuit Breaker/ Fuse Test User InputsFinal Inspection Operation Technical DescriptionRectifier Management System Current System ManagementSystem Output Capacity System Voltage ControlDC Distribution Battery ManagementSystem Status and Alarm Reporting Battery Charging and ProtectionControls and Indicators Battery/Load Low Voltage DisconnectFront Panel User Interface Parameter Locations, Descriptions, and Default Values Status Alarms System Modules Batt PIN OEMSwitzer Alarm ItemNo Alarms AddressBatt HV Alm Batt HT AlmBatt HT Thr 70.0 CComp Hknee Cir Bkr 1 Alm m+Major Cir Bkr 72 Almm+Minor Fuse 1 AlmFuse 16 Alm Hw Batt C Almm+LVD Trip LVD ResetLVD Option 48.00Relay Major Out-Rly 1 Dly m+Sec Out-Rly 6 Dly m+Rect 1ofN Almm+ DisableRect 1 Desc MRF28H54Sys LT Thr Sys HV AlmSys HV Thr Sys LT Alm90025 TimeControl Unit Menu Structure SYS MS System Module SET-ALM Setup DAV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin Modrec AM Info Modfuse LM Alias Fuse MOD Modlvd Modlvd LM Param Alarm Outputs Output Relays Front Panel LED IndicatorsSection External Alarm Inputs Input Relays Physical Connections Command and Monitoring ProtocolRemote Monitoring DescriptionInspection Preventive MaintenanceSystem Visual and Safety Inspection EquipmentTest System Voltage TestRectifier Current Test Rectifier Current Share Test Rectifier Alarm TestSystem Temperature Test Battery Current TestBattery Preventive Maintenance Procedure Battery Temperature TestFinal Inspection 1MRF28H54BV50 Rectifiers SpecificationsAC Input 1MRF28H54BV RectifiersRectifiers VDCPower Shelf Control Unit Mechanical EnvironmentalCompliance Worldwide APC Worldwide Customer SupportUS and Canada Toll FreeLimited Product Warranty