American Power Conversion MX28B4800 LVD Option, LVD Reset, 48.00, LVD Trip, 42.00, Model, 000

Page 46

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

LVD 1 or 2 Option

Must be set to “Enable” if the unit has an LVD. If

LVD Option

m+

Security Level {1}

the unit has an LVD, but it is disabled, the

Enable

 

[MODULES/LVD/SET-ALM]

controller will not disconnect the LVD.

 

 

LVD 1 or 2 Reset

LVD Reset (reconnect) threshold voltage.

LVD Reset

m+

Security Level {1}

 

-48.00 V

[MODULES/LVD/PARAM]

 

 

 

LVD 1 or 2 Trip

LVD Trip (disconnect) threshold voltage.

LVD Trip

m+

Security Level {1}

 

-42.00 V

[MODULES/LVD/PARAM]

 

 

 

LVD Alarm

The output relay that is energized when the

LVD Open Alm m+

Security Level {1}

controller opens the LVD. If unit has a battery

Minor

 

[MODULES/LVD/SET-ALM]

LVD, no power will be available to turn on any

 

 

 

Output Relays.

 

 

Model Programming

Model type number for the MX28B DC power

Model

m+

Security Level {2}

plant. Choose the MX28B-1200 if you have the

MX28B-1200

[SYSTEM/SETUP]

2500 Amp battery shunt. Choose the MX28B-

 

 

 

4800 if you have the 5000 Amp battery shunt.

 

 

 

NOTE: Changing the model number causes the

 

 

 

system to reinitialize.

 

 

OEM R Gain

Voltage gain adjustment for factory calibration of

OEM R Gain

m+

Security Level {2}

system voltage readings/settings.

1.000

V

[OEM]

 

 

 

OEM R Offset

Voltage offset adjustment for factory calibration of

OEM R Offset

m+

Security Level {2}

system voltage readings/settings.

0.000 V

[OEM]

 

 

 

OEM S Gain

Current gain adjustment for factory calibration of

OEM S Gain

m+

Security Level {2}

battery current readings/settings.

1.000 A

[OEM]

 

 

 

OEM S Offset

Current offset adjustment for factory calibration of

OEM S Offset

m+

Security Level {2}

battery current readings/settings.

0.0 A

[OEM]

 

 

 

Output Relay 1 Alarm

Output Relay 1 Alarm can be “mapped” to activate

Out-Rly 1 Alm m+

Security Level {1}

other output relays (“Ignore” activates no

Ignore

 

[SYSTEM/OUT-RLY/RLY-

additional relays).

 

 

MAP]

 

 

 

 

 

 

Output Relay 6 Alarm

Output Relay 6 Alarm can be “mapped” to activate

Out-Rly 6 Alm m+

Security Level {1}

other output relays (“Ignore” activates no

Ignore

 

[SYSTEM/OUT-RLY/RLY-

additional relays).

 

 

 

MAP]

 

 

 

Output Relay 1 Alias

An alternate name (alias) can be assigned to

Out-Rly 1

m+

Security Level {1}

Output Relay 1 if desired.

Relay

1

[SYSTEM/OUT-RLY/ALIAS]

 

 

 

 

 

An alternate name (alias) can be assigned to

 

Output Relay 6 Alias {1}

Output Relay 6 if desired.

Out-Rly 6

m+

[SYSTEM/OUT-RLY/ALIAS]

 

Relay

6

MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual

Page 41

Image 46
Contents VDC Power Systems Table of Contents Commissioning and Preventive Maintenance APC Worldwide Customer Support Limited Product Warranty Revision History Revision Date DescriptionSafety First General PrecautionsIntroduction How to Use This ManualGeneral Information 1 MX28B-1200 -48 VDC Power Plant Rectifier Bay 2 MX28B Block Diagram Unpacking Equipment InstallationMechanical Installation Room / LocationPower Bus Connections Mounting2 MX28B-1200-2400 has a maximum Circuit Breaker/LVD Ribbon Cable Connections 5 Circuit Breaker / LVD Expansion BoardFuse Alarm Ribbon Cable Connections AC Power ConnectionsVentilation 1 AC Input Wiring Battery Connections Planning the Battery InstallationConnecting the Battery Cables 1 Battery Cable Connection Locations2 Battery Probe Connection DC System GroundingDC Power Output Over-Current Protection DC Plug-in Circuit BreakersBreaker Part Number Rating 2 Plug-in Circuit Breakers DC Bolt-in Circuit Breakers 4 Bolt-in Circuit BreakersTelecom Fuses 5 Telecom FusesInstallation of Circuit Breakers and Fuses Plug-in Circuit Breaker InstallationBolt-in Circuit Breaker Installation 2 Circuit Breaker Alarm WiringTelecom Fuse Installation GMT Fuse InstallationCircuit Breaker Connections 1 to 50 Amps Load ConnectionsCable Size Considerations Circuit Breaker Connections 60-100 AmpsFront Panel DB9 Connection Monitoring and Relay Output ConnectionsGMT Fuse Connections Smart Cable DB9 ConnectionRJ45 Ethernet Connector Relay Output ConnectionsExternal Alarm Input Connections NO-NC-CRectifier Module Installation Battery Visual and Safety Inspection Commissioning and Preventive MaintenanceElectrical Installation Pre-Commissioning InspectionCommissioning AC Power UpInitial Set-up Rectifier Test DC Power UpBattery Power Up LVD TestUser Inputs Battery Temperature CompensationCircuit Breaker/ Fuse Test Output RelaysFinal Inspection Technical Description OperationRectifier Management System Voltage Control System ManagementSystem Output Capacity System CurrentBattery Charging and Protection Battery ManagementSystem Status and Alarm Reporting DC DistributionBattery/Load Low Voltage Disconnect Controls and IndicatorsFront Panel User Interface Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default ValuesAddress Alarm ItemNo Alarms Switzer70.0 C Batt HT AlmBatt HT Thr Batt HV AlmCir Bkr 72 Almm+ Cir Bkr 1 Alm m+Major Comp HkneeHw Batt C Almm+ Fuse 1 AlmFuse 16 Alm Minor48.00 LVD ResetLVD Option LVD TripOut-Rly 6 Dly m+ Out-Rly 1 Dly m+Sec Relay MajorMRF28H54 DisableRect 1 Desc Rect 1ofN Almm+Sys LT Alm Sys HV AlmSys HV Thr Sys LT ThrTime 90025SYS MS System Module SET-ALM Setup DA Control Unit Menu StructureV e l C o n d L e v e l I r d L e v e l U r t h L e v e l SYS Sysin Modrec AM Info Modfuse LM Alias Fuse MOD Modlvd Modlvd LM Param Front Panel LED Indicators Alarm Outputs Output RelaysSection External Alarm Inputs Input Relays Description Command and Monitoring ProtocolRemote Monitoring Physical ConnectionsEquipment Preventive MaintenanceSystem Visual and Safety Inspection InspectionSystem Voltage Test TestRectifier Current Test Battery Current Test Rectifier Alarm TestSystem Temperature Test Rectifier Current Share TestBattery Temperature Test Battery Preventive Maintenance ProcedureFinal Inspection 1MRF28H54BV Rectifiers SpecificationsAC Input 1MRF28H54BV50 RectifiersVDC RectifiersPower Shelf Control Unit Environmental MechanicalCompliance Toll Free APC Worldwide Customer SupportUS and Canada WorldwideLimited Product Warranty